HomeMy WebLinkAbout029-O-22 Amending Title 4 of the City Code, “Building Regulations,” by Adopting 2021 Model Codes by Reference, with Amendments3/16/2022
29-0-22
AN ORDINANCE
Amending Title 4 of the City Code, "Building Regulations," by
Adopting 2021 Model Codes by Reference, with Amendments
WHEREAS, the City Council of the City of Evanston finds that it is in the
interest of the public health, safety, and welfare to adopt, as its standards for building
construction, alteration, and installation permits, certain 2021-2022 model building
codes,
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF
THE CITY OF EVANSTON, COOK COUNTY, ILLINOIS, THAT:
SECTION 1: The foregoing recitals are hereby found as fact and
incorporated herein by reference.
SECTION 2: Title 4, Chapter 1 of the Evanston City Code of 2012, as
amended (the "City Code"), "Building and Inspection Services Division," is hereby
deleted in its entirety and replaced with the text set forth in Exhibit A, attached hereto
and incorporated herein by reference.
SECTION 3: Title 4, Chapter 2 of the City Code, "Building Code," is
hereby deleted in its entirety and replaced with the text set forth in Exhibit B, attached
hereto and incorporated herein by reference.
SECTION 4: Title 4, Chapter 4 of the City Code, "Fire Prevention
Regulations," is hereby deleted in its entirety and replaced with the text set forth in
Exhibit C, attached hereto and incorporated herein by reference.
MIC
Page 1 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
29-0-22
SECTION 5: Title 4, Chapter 5 of the City Code, "Plumbing Code," is
hereby deleted in its entirety and replaced with the text set forth in Exhibit D, attached
hereto and incorporated herein by reference.
SECTION 6: Title 4, Chapter 6 of the City Code, "Electrical Code," is
hereby deleted in its entirety and replaced with the text set forth in Exhibit E, attached
hereto and incorporated herein by reference.
SECTION 7: Title 4, Chapter 7 of the City Code, "Mechanical Code," is
hereby deleted in its entirety and replaced with the text set forth in Exhibit F, attached
hereto and incorporated herein by reference.
SECTION 8: Title 4, Chapter 9 of the City Code, "Residential Code," is
hereby deleted in its entirety and replaced with the text set forth in Exhibit G, attached
hereto and incorporated herein by reference.
SECTION 9: Title 4, Chapter 17 of the City Code, "Fuel Gas Code," is
hereby deleted in its entirety and replaced with the text set forth in Exhibit H, attached
hereto and incorporated herein by reference.
SECTION 10: Title 5, Chapter 1 of the City Code, "Property
Maintenance," is hereby deleted in its entirety and replaced with the text set forth in
Exhibit I, attached hereto and incorporated herein by reference.
SECTION 11: All ordinances or parts of ordinances in conflict herewith
are hereby repealed.
SECTION 12: If any provision of this ordinance or application thereof to
any person or circumstance is held unconstitutional or otherwise invalid, such invalidity
shall not affect other provisions or applications of this ordinance that can be given effect
--2-
Page 2 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
29-0-22
without the invalid application or provision, and each invalid provision or invalid
application of this ordinance is severable.
SECTION 13: The findings and recitals contained herein are declared to
be prima facie evidence of the law of the City and shall be received in evidence as
provided by the Illinois Compiled Statutes and the courts of the State of Illinois.
SECTION 14: This ordinance shall be in full force and effect 30 days
after its passage, approval and publication in the manner provided by law.
Introduced: March 16 12022 Approved:
Adopted: April 25 , 2022 April 27 , 2022
IsanLd ldz' ,j
Daniel Biss, Mayor
Attest: Approved as to form:
��"'� �cchola,s �. Cu�tartciu�s
Stephanie Mendoza, City Clerk Nicholas E. Cummings, Corporation
Counsel
-3-
Page 3 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit A
CHAPTER 1 BUILDING AND INSPECTION SERVICES DIVISION
4-1-1. DIVISION CREATED; COMPOSITION.
There is hereby created an executive division of the city's Community Development
Department which shall be known as the Division of Building and Inspection Services.
Said division shall consist of the Manager of Building and Inspection Services and such
other deputies and employees as may from time to time be assigned thereto. The
Manager of Building and Inspection Services shall be the City's Building Official.
4-1-2. BUILDING OFFICIAL.
(A) Powers And Duties. The Building Official shall have the powers and duties as
described in the adopted building code.
(B) Police Powers. In addition to the powers authorized in the adopted building code,
the Building Official and his/her duly appointed building and technical inspectors
shall have full police powers to issue complaints, citations, notices to appear, and
summonses for the violation of any provision of the various building, mechanical,
electrical, structural, plumbing and energy codes that the Building Official is
charged with enforcing.
4-1-3. DEPUTY DIRECTORS OF BUILDING AND INSPECTION SERVICES.
The Fire Chief and the Director of Health and Human Services of the city are each
hereby made ex officio deputy Managers of Building and Inspection Services.
(A) Fire Chief. It is hereby made the duty of the Fire Chief, as ex officio deputy
Manager of Building and Inspection Services, to aid the Manager of Building and
Inspection Services in administering and enforcing the building code. Such deputy
Manager of Building and Inspection Services shall give special attention to and
render assistance in enforcing all provisions of the building code pertaining to
safeguarding life and property against, and in the event of, fire in any building,
structure or portion thereof, now existing or which may hereafter be constructed.
(B) Director Of Health. It is hereby made the duty of the Director of the Health
Department, as ex officio deputy Manager of Building and Inspection Services, to
aid the Manager of Building and Inspection Services in enforcing and administering
the building code. Such deputy Manager of Building and Inspection Services shall
give special attention to and render assistance in enforcing all provisions of the
building code pertaining to the sanitation of any building, structure or portion thereof
now existing or which may hereafter be constructed.
4-1-4. ADOPTION OF BUILDING CODES.
A. The following Codes are hereby adopted as the Building Code for the City of
Evanston in the State of Illinois; for the control of building and structures as
herein provided: and each and all of the regulations, provision, penalties,
conditions and terms of said referenced codes are hereby referred to, adopted
and made a part hereof as if fully set out in this Code, with the additions,
►M
Title 4, Chapter 1, Building and Inspection Services Division
Page 4 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit A
insertions, deletions and changes prescribed in the Chapters of Title 4 — Building
Regulations.
This Code contains basic minimum provisions considered necessary to provide
protection to life, health, safety and the public welfare. This code is intended to
produce installations essentially free from hazards and to promote quality
workmanship.
1. International Building Code/2021
2. International Residential Code/2021 and Appendices AA, AB, AC, AF,
G(2012), AH, AJ, AK, AO, AT
3. International Fire Code/2021
4. International Mechanical Code/2021
5. International Fuel Gas Code/2021
6. International Property Maintenance Code/2021
7. National Electrical Code — NFPA 70/2020
8. Illinois Plumbing Code/Illinois Administrative Code Title 77 Part 890
9. Illinois Energy Conservation Code/Illinois Administrative Code Title 71 Part
600
10. Illinois Accessibility Code/ Illinois Administrative Code Title 71 Part 400
B. Code Reference Clarifications.
1. All references to electrical code shall mean "National Electric Code".
2. All references to plumbing code shall mean "Illinois Plumbing Code".
3. All references to energy code shall mean "Illinois Energy Conservation Code".
4. All references to accessibility code shall mean the "Illinois Accessibility Code".
5. Conflicts. If there is found to be a conflict of requirements in this code, the
most stringent requirement shall apply. The Building and Fire Officials are
authorized to waive the more stringent requirement based upon a showing of
good cause, unusual or special circumstances and equivalent measures of
safety.
C. Workmanship. All work shall be conducted, installed and completed in a
professional and workmanlike manner consistent with current construction
practices so as to secure the results intended by this code.
Title 4, Chapter 1, Building and Inspection Services Division
Page 5 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
CHAPTER 2 BUILDING CODE
4-2-1. ADOPTION.
(A) Pursuant to the authority granted by 65 ILCS 5/1-2-4, and pursuant to its home rule
powers, the City of Evanston hereby adopts by reference the 2021 International
Building Code, with the additions, deletions, exceptions, and other amendments set
forth in this Chapter. All advisory or text notes, other than the rules and regulations
contained in the 2021 International Building Code adopted hereby, are expressly
excluded from this Chapter.
(B) Any reference in the 2021 International Building Code to "Building Official" shall
refer to the City's Manager of Building and Inspection Services. Any reference to
"municipality" shall mean the City of Evanston.
(C) In the event that any provision of the 2021 International Building Code adopted
hereby is in conflict with any provision(s) of the City Code, the more/most stringent
shall control.
(D) There shall be a copy of the 2021 International Building Code kept on file for public
inspection in the City Clerk's office.
4-2-2. AMENDMENTS.
The 2021 International Building Code adopted hereby shall read as follows with
respect to these Sections.
101.4.3 Plumbing. Revise this section to read as follows:
The provisions of the Illinois Plumbing Code as amended and adopted by the City shall
apply to the installation of plumbing systems, including alterations, repairs, replacement,
equipment, appliances, fixtures, fittings and appurtenances, and where connected to a
water or sewage system and all aspects of a medical gas system. With the exception of
Chapter 29, Plumbing Systems as amended, whenever a reference is made to the
International Plumbing Code, such reference shall be deemed to refer to the applicable
section of the Illinois Plumbing Code, as amended and adopted by the City of Evanston.
101.4.5 Fire Prevention. Revise this section to read as follows:
The provisions of the 2021 NFPA Life Safety Code 101 and 2021 International Fire
Code as amended and adopted by the City shall apply to matters affecting or relating to
structures, processes, and premises from the hazard of fire and explosion arising from
the storage, handling, or use of structures, materials, or devices; from conditions
hazardous to life, property or public welfare in the occupancy of structures or premises;
and from the construction, extension, repair, alteration, or removal of fire suppression
and alarm systems or fire hazards in the structure or on the premises from occupancy
or operation
101.4.6 Energy. Revise this section to read as follows:
The provisions of the Illinois Energy Conservation Code shall apply to all matters
governing the design and construction of buildings for energy efficiency. Whenever a
0
Page 6 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
reference is made to the International Energy Conservation Code, such reference shall
be deemed to refer to the applicable section of the Illinois Energy Conservation Code,
as adopted by the City of Evanston.
101.4.7 Existing Buildings. Delete this section in its entirety.
101.4.7.1 Existing Building Alteration (Bird -friendly). Where the alteration of an
existing building includes the replacement of fifty (50%) percent or more of the exterior
glazing, such alteration shall comply with Section 1403.15 of this code.
103.1: Creation of Enforcement Agency. The Division of Building and Inspection
Services is hereby made responsible for the enforcement of this Code.
103.2: Appointment. Any reference in the 2021 International Building Code to "Building
Official" shall refer to the City's Manager of Building and Inspection Services Division.
Any reference to "municipality" shall mean the City of Evanston.
103.3: Deputies. The Building Official shall have the authority to appoint such technical
officers, inspectors, plan examiners and other employees as he or she deems
necessary to effectuate the purposes of this Code. Such employees shall have powers
as delegated by the Building Official. For the maintenance of existing properties, see the
Property Maintenance Code adopted by the City.
104.6: Right of Entry. Revise this section to read as follows:
The Building Official and his/her authorized representatives are hereby authorized to
make inspections of all buildings, structures, and premises located within the City to
determine their compliance with the provisions of this Chapter. For the purpose of
making such inspections, the Building Official and his/her authorized representatives
are hereby authorized to examine and survey all buildings, structures, and premises
within the City. Such inspections shall be made between the hours of 7:00 A.M. and
7:00 P. M. unless circumstances dictate the need for earlier or later inspections, on any
day except Sunday, subject to the following standards and conditions:
1) Such inspections may take place only if:
a) a complaint respecting said premises has been received by the Building
Official and such complaint, in the opinion of said Building Official,
provides reasonable grounds for belief that a violation exists; or
b) if such inspection is undertaken as part of a regular inspection program
whereby certain areas of the City are being inspected in their entirety by
direction of the Building Official or the City Manager; or
c) if said official has other personal knowledge of conditions providing
reasonable grounds to believe that a violation exists;
2) Such inspections shall be made by the Building Official or the City Manager or
by any duly authorized representative upon direction of either of said officers;
3) Any person making such inspection shall furnish to the owner or occupant of
the structure sought to be inspected, sufficient identification and information to
enable the owner or occupant to determine that he/she is a representative of
the City of Evanston and to determine the purpose of said inspection.
B2
Title 4, Chapter 2, Building Code
Page 7 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
105.2: Work Exempt From Permit. Delete this section in its entirety. Contact the
Building and Inspection Services Division for information regarding work exempt from
permits.
R105.3.1.2: Issuance of a Building Permit. The Building Official may refuse to issue
a building permit if there is an outstanding sum of money due the City from the property
owner or if work done a separately issued building permit has not been satisfactorily
completed per the requirements of these provisions.
105.5: Expiration and Extension. Revise this section to read as follows:
1) Expiration:
a) A building permit shall, without further action by the City, automatically
expire and be rendered null, void, and of no further force or effect, if the
permit holder does not begin the work authorized by the permit within one
hundred eighty (180) calendar days of the date of permit issuance.
b) A building permit shall, without further action by the City, automatically
expire and be rendered null, void, and of no further force or effect, if, at
any time after the work is begun, the permit holder suspends and/or
abandons the work authorized by the building permit for a continuous
period of one hundred eighty (180) calendar days.
c) A building permit shall, without further action by the City, automatically
expire and be rendered null, void, and of no further force or effect, two (2)
years after the date of permit issuance, unless an extension is granted in
accordance with Subsection 2) below.
d) If the building or work authorized by a building permit does not receive
final inspection approval by the permit expiration date, all work shall stop
until the Building Official issues a new permit or grants an extension of
time in accordance with Subsection 2) below. All electrical, plumbing,
and/or mechanical permits associated with a building permit shall expire
concurrently with the building permit.
2) Extension:
a) Except for relocation of structures, a permit holder may submit, before the
expiration date of the building permit, an application to the Building Official
for an extension of time. The application shall be filed no later than one (1)
month in advance of the expiration date. The Building Official may extend
the building permit once, for a period not exceeding one hundred eighty
(180) calendar days, if he/she determines that circumstances beyond the
permit holder's control prevented completion of the work. All electrical,
plumbing, and/or mechanical permits associated with a building permit
shall be extended to expire concurrently with the building permit.
b) If a permit holder files application for an extension of time before expiration
and in accordance with this Subsection, the existing building permit shall
automatically be extended until the Building Official makes a decision on
the application for an extension.
B3
Title 4, Chapter 2, Building Code
Page 8 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
c) If the building permit expires before an application is submitted for an
extension of time, no extension shall be granted. If the previous permit
holder or any other applicant wants to proceed with the same
development, a new application is required and the application is treated
in all respects as a new application.
d) If the Building Official previously approved an extension of time in
accordance with Subsection a), the Building Official may extend the
expiration of the building permit one (1) additional time if he/she finds the
following:
i) There are no significant change(s) in the regulations applicable to the
site since the date the permit was issued;
ii) The additional extension is in the public interest; and
iii) Circumstances beyond the control of the applicant prevented the
authorized work from proceeding.
105.7: Placement of Permit. Revise this section to read as follows:
The building permit or a legible copy of the building permit shall be kept on the site of
operations, open to public inspection during the entire time of prosecution of the work
and until the completion of the same. Said permit must be posted within forty-eight (48)
hours of permit issuance, must remain posted until a certificate of occupancy is issued
or the permit expires, and must be visible from the public way. Failure to post and
maintain the permit as required by this Section may result in revocation of the building
permit and forfeiture of all permit fees.
105.8: Hours of Work Permitted for the Construction, Repair, and Demolition of
Buildings. The creation (including excavation), demolition, alteration or repair of any
building within the City, other than between the hours of seven o'clock (7:00) A.M. and
seven o'clock (7:00) P.M. on weekdays, and eight o'clock (8:00) A.M. and five o'clock
(5:00) P.M. on Saturdays, except in case of urgent necessity in the interest of public
health and safety, and then only with permission from the City Manager or his or her
designee, which permission may be granted while the emergency continues.
107.2 Construction Documents. Construction documents shall be in accordance with
Sections 107.2.1 through 107.2.9
107.2.1: Information on Construction Documents. Revise section to read as follows:
Construction documents shall be dimensioned and drawn upon suitable material.
Electronic media documents are permitted to be submitted when approved by the
Building Official. Construction documents shall be of sufficient clarity to indicate the
location, nature and extent of the work proposed and show in detail that it will conform
to the provisions of this Code and relevant laws, ordinances, rules, and regulations, as
determined by the Building Official. All floor plans, including mechanical, electrical,
plumbing and fire protection plans, shall indicate all required fire ratings and where they
occur by graphic means with a legend or key.
Title 4, Chapter 2, Building Code
B4
Page 9 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
107.2.9 Information for electric vehicle charging stations. Construction documents
shall include electric vehicle charging stations with system installation requirements set
forth in Section 406.2.7 of this code.
113: MEANS OF APPEALS. Delete this section in its entirety.
117: Digital Submission of Construction Documents Prior to Issuance of
Certificate of Occupancy.
1) In addition to the requirement of filing hard -copy construction documents,
submission of a series of construction/design documents in a computer digital
format is required as part of the permitting process prior to the issuance of any
final certificates of occupancy pursuant to the guidelines stated immediately
below if one or more of the following applies:
a) The valuation of the construction project is, in its entirety, greater than
$500,000.00 (five hundred thousand and no/100 dollars).
b) When the Director of Community Development, or his/her designee,
determines that there are significant changes to the physical
characteristics of the property or the structures on or around that property
to warrant the submission of electronic documents.
2) Digital data shall be submitted according to the following guidelines:
a) The digital data submission shall contain the following three (3) document
types:
i) Site Plan: A plan view, drawn to scale, depicting the project's location
and showing at a minimum: property lines, building footprints, building
elevation changes, sidewalks, driveways, proximate reference points
identifiable within the City, and any fire lanes.
ii) Floor Plan: Exterior plan view for each floor, drawn to scale, showing
at a minimum: interior walls, exterior walls, doors, and any stairs and
elevators.
iii) Elevation Views: Exterior profile views, drawn to scale, showing at a
minimum: height of building Sections, main entrance, and roofline.
b) Data shall be submitted via compact disc, FTP, e-mail or other media
deemed permissible by the Director of Community Development or his/her
designee.
c) All digital submissions shall be in a format approved by the City's
Information Technology Division.
d) The data must be a proportionally accurate representation of the
construction project, sufficient to fully explain and reproduce the project,
with the defined scale clearly represented.
e) The permit applicant shall resubmit newly updated information pursuant to
the above requirements whenever the applicant or his/her agent makes
Title 4, Chapter 2, Building Code
B5
Page 10 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
corrections or updates to the originally submitted information requiring the
resubmission of printer -paper documents.
3) Upon request by the person required to submit information in a digital format,
or if that party is unwilling or unable to digitally submit information, the City's
geographical information systems division will digitally convert paper -based
submitted documents. The fee for digital conversion shall be $100.00 (one
hundred and no/100 dollars) for each submitted page equal to or smaller than
ledger -sized (11" by 17") paper, and $200.00 (two hundred and no/100 dollars)
for each submitted page exceeding ledger -sized (11" by 17") paper.
4) Any person who fails to comply with all requirements of this Section shall be
subject to denial or revocation of any temporary or final certificates of
occupancy pertaining to the project for which the violation has occurred. Denial
or revocation of any temporary or final certificates of occupancy shall not
preclude the City from seeking fines, costs, and other relief against the violator
by filing a complaint or citation with the Circuit Court or Division of
Administrative Adjudication.
202: Definitions. Amend this section to include the following definition(s):
MULTIPLE OCCUPANCY RESTROOM. A room designed to be used as a
restroom by more than one person at a time, which shall contain, at least, more
than one toilet and more than one sink, which shall be suitable for use by disabled
persons in compliance with applicable local, state and federal laws. Toilets, for
privacy purposes, shall be separated by partitions and the stalls shall be equipped
with a locking mechanism to be operated by the user of the stall.
SINGLE OCCUPANCY RESTROOM. A fully enclosed room, with a locking
mechanism controlled by the user, containing a sink, toilet stall, and no more than
one (1) urinal. Every single occupancy restroom in a place of public accommodation
or public building shall be identified as all -gender and designated for use by no
more than one (1) person at a time or for family or assisted use.
GENDER IDENTITY. Shall have the meaning given in City Code Section 1-21-5.
GENDER NEUTRAL RESTROOM. A restroom that is designated for use by any
person, regardless of Gender Identity, as defined in City Code Section 1-21-5, as
amended.
ELECTRIC VEHICLE. An automotive -type vehicle for on -road use primarily
powered by an electric motor that draws current from an onboard battery charged
through a building electrical service, electric vehicle supply equipment (EVSE), or
another source of electric current.
ELECTRIC VEHICLE SUPPLY EQUIPMENT (EVSE). The apparatus installed
specifically for the purpose of transferring energy between the premises wiring and
the Electric Vehicle.
EV-CAPABLE SPACE. A dedicated parking space with electrical panel capacity
and space for a branch circuit dedicated to the EV parking space that is not less
Title 4, Chapter 2, Building Code
[3.
Page 11 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
than 40-ampere and 208/240-volt and equipped with raceways, both underground
and surface mounted, to enable the future installation of electric vehicle supply
equipment. For two adjacent EV-Capable spaces, a single branch circuit is
permitted.
EV-READY SPACE. A designated parking space which is provided with a
dedicated branch circuit that is not less than 40-ampere and 208/240-volt assigned
for electric vehicle supply equipment terminating in a receptacle or junction box
located in close proximity to the proposed location of the EV parking space. For two
adjacent EV-Ready spaces, a single branch circuit is permitted.
Section 406.2.7 Electric vehicle charging stations and systems.
Commentary: Definitions for Electric Vehicle, Electric Vehicle Supply Equipment
(EVSE), EV-Capable Space and EV-Ready Space have been added to Chapter 2.
Section 406.2.7.1 Electric vehicle parking. Where parking is provided, new
construction shall provide EVSE-Installed Spaces and facilitate future installation and
use of EVSE through the provision of EV-Ready Spaces and EV-Capable Spaces
provided in compliance with Sections 406.2.7.2 through 406.2.7.3. Where more than
one parking facility is provided on a site, EVSE-Installed, EV-Ready Spaces and EV-
Capable Spaces shall be calculated separately for each parking facility.
Section 406.2.7.2 New commercial and multifamily buildings. EVSE-installed
spaces, EV-Ready Spaces and EV-Capable Spaces shall be provided in accordance
with Table 406.2.7.2 for multifamily and commercial buildings. Where the calculation of
percent served results in a fractional parking space, it shall round up to the next whole
number. The circuit shall have no other outlets. The service panel shall include an
over -current protective device and provide sufficient capacity and space to
accommodate the circuit and over -current protective device and the termination point
shall be located in close proximity to the proposed location of the EV parking spaces.
Table 406.2.7.2: EVSE-Installed, EV-Ready and EV-Capable Space
Requirements
Multifamily
Commercial
10% EV-Installed, 20% EV-Ready, 70% EV- 10% EV-Installed, 40% EV-Capable
Capable
EV-Installed and EV-Capable to increase
EV-installed and EV-Ready to increase 10% 10% every 3 years
every 3 years with remainder of spaces being
EV-C;apable
a. Where EVSE-Installed Spaces installed exceed the required values in Table
1101.15.3, the additional spaces shall be deducted from the EV-Ready
Spaces requirement.
b. Where EV-Ready Spaces installed exceed the required values in Table
1101.15.3, the additional spaces shall be deducted from the EV-Capable
Spaces Requirement.
B7
Title 4, Chapter 2, Building Code
Page 12 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
406.2.7.3 Identification. Construction documents shall indicate the raceway termination
point and proposed location of future EV spaces and EVSE. Construction documents
shall also provide information on amperage of future EVSE, raceway methods, wiring
schematics and electrical load calculations to verify that the electrical panel service
capacity and electrical system, including any on -site distribution transformers, meet the
requirements of this code. Parking spaces equipped with EVSE shall be identified by
signage. A permanent and visible "EV-Capable" or "EV-Ready" label shall be posted in
a conspicuous place at the service panel to identify each panel space reserved to
support EV-Capable or EV-Ready Spaces, respectively and at the termination point of
the raceway or circuit termination point.
Commentary: Definitions for Electric Vehicle, Electric Vehicle Supply Equipment
(EVSE), EV-Ready Space and EV-Capable Space have been added to Chapter 2.
Reference Section 1107 Motor Vehicle -Related Facilities — Exception to 1107.2
Electrical Vehicle Charging Stations has been deleted.
Chapter 9 Fire Protection and Life Safety Systems.
Reference 2021 International Fire Code Chapter 9 as adopted and amended by the City
of Evanston. (Commentary: 2021 IBC Chapter 9 parallels and is substantially
duplicated in Chapter 9 of the International Fire Code).
Reference 2021 International Residential Code Section R313 Automatic Fire Sprinkler
Systems as amended for provisions for townhouses and one- and two-family dwellings
including those with accessory dwelling units.
1009.6.1.1: Area of Refuge. The floor of the area of refuge shall be designed with
striping or other such means and labeled with the International symbol of access, such
that this area is reserved at all times for the intended purpose.
1011.16: Stairway to Roof. Revise this section to read as follows:
In building four (4) or more stories above grade plane, all stairways shall extend to the
main roof surface, unless the roof has a slope steeper than four units vertical to twelve
units horizontal (33% slope). One stair shall terminate at a minimum four feet (4') deep
landing in a penthouse conforming to Section 1509.2 and shall have a three feet (3')
wide side -hinged door to the roof area. If the door is locked a key in an elevator box
shall be provided adjacent to the door. Access to the roof from all other stairs shall
comply with Section 1009.16.1.
1009.16.1: Access to penthouse roofs. All building penthouse roofs shall have access
to them by way of a stairwell or ships ladder. This may be interior or exterior to the
penthouse. An interior position shall have access to the roof through a roof hatch which
shall be sixteen square feet (16 ft2 ) minimum and have a minimum dimension of two
feet (2').
1107.2 Electrical Vehicle Charging Stations. Electric vehicle charging stations shall
comply with Sections 1107.2.1 and 1107.2.2.
(Delete) Exception. Electrical vehicle charging stations provided to serve R-2,
R-3 and R-4 occupancies are not required to comply with this section.
Title 4, Chapter 2, Building Code
M.;
Page 13 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
1202.1: General. Revise this section to read as follows:
Buildings shall be provided with natural ventilation in accordance with Section 1202.5,
or mechanical ventilation in accordance with the International Mechanical Code. All
sleeping rooms in new buildings shall be provided with natural ventilation in accordance
with Section 1202.5, which may be supplemented with mechanical ventilation in
accordance with the International Mechanical Code. The provisions of Section
1203.5.1.1 that allow use of adjoining spaces for ventilation shall not apply to sleeping
rooms in new buildings.
1204.1: General. Revise this section to read as follows:
Every space intended for human occupancy shall be provided with natural light by
means of exterior glazed openings in accordance with Section 1204.2 or shall be
provided with artificial light in accordance with Section 1204.3. Exterior glazed openings
shall open directly onto a public way or onto a yard or court in accordance with Section
1204.2.2. Notwithstanding the rest of this Section 1204.1, all sleeping rooms in new
buildings shall be provided with natural light by means of exterior glazed openings in
accordance with Section 1204.2, which may be supplemented with artificial light in
accordance with Section 1204.3. The provisions of Section 1204.2.1 that allow use of
adjoining spaces for light shall not apply to sleeping rooms in new buildings.
1502.2.1 Separate Systems Required. Secondary roof drain systems shall have the
end point of discharge separate from the primary system. Discharge shall be above
grade, in a location that would normally be observed by the building occupants or
maintenance personnel. Exception to the above grade discharge requirement shall be
by the city's Building Official or Civil Engineer.
Table 1607.1: Minimum Uniformly Distributed Live Loads and Minimum
Concentrated Live Loads. Revise this table to read as follows:
Occupancy or Use Uniform (psf) Concentrated
(lbs.)
Balconies and decks (including porches) 100 —
Chapter 29 Plumbing Systems. This Chapter shall be retained with the following
amendments:
Commentary: Definitions for Single Occupancy Restroom, Multiple Occupancy
Restroom, Gender Identity and Gender Neutral Restroom have been added to Chapter
2.
2901 General. Delete.
2902.1 Minimum Number of Fixtures. Delete.
Table 2902.1 Minimum Number of Required Plumbing Fixtures. Delete.
2902.1.1 Fixture Calculations. Delete.
2902.2: Separate Facilities. Revise this section to read as follows:
Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Title 4, Chapter 2, Building Code
Page 14 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
Exceptions:
1. Separate facilities shall not be required for dwelling units and sleeping units.
2. Separate facilities shall not be required to be designated by sex where single
occupancy restrooms are provided in accordance with Section 2902.1.2. Single
occupancy restrooms shall not have more than one water closet and one
lavatory and the option of one urinal.
3. Separate facilities shall not be required where rooms having both water closets
and lavatory fixtures are designed for use by both sexes and privacy for
water closets is provided. Each water closet utilized by the public or employees
shall occupy a separate compartment with walls or partitions and a door
enclosing the fixtures to ensure privacy.
Exceptions:
1. Water closet compartments shall not be required in a single -
occupant restroom with a lockable door.
2. Restrooms located in child day care facilities and containing two
or more water closets shall be permitted to have one water closet
without an enclosing compartment.
3. This provision is not applicable to toilet areas located within 1-3
housing areas.
Urinals shall be located in an area visually separated from the remainder of the
facility or each urinal that is provided shall be located in a stall.
Multiple occupancy, gender neutral facilities are not required but can be used as
an alternative to be determined by the property owner or the property owner's
agent.
2902.3 Employee and public toilet facilities. Delete.
2902.3.3 Location of toilet facilities in occupancies other than malls. Delete.
2902.3.4 Location of toilet facilities in malls. Delete.
2902.5 Drinking fountain locations: Delete.
2902.4 Signage. All public restroom facilities shall be designated by legible signs,
stating that the public facilities are for men, women, or are gender neutral, as
applicable. Single occupancy and family or assisted -use restrooms shall be outfitted
with exterior signage that marks the single -occupancy, family or assisted -use restroom
as a restroom and does not indicate any specific gender. Signs shall be readily visible
and located near the entrance to each toilet facility. Signs for accessible toilet facilities
shall comply with the Illinois Accessibility Code.
2902.4 Signage. All public restroom facilities shall be designated by legible signs,
stating that the public facilities are for men, women, or are gender neutral, as
applicable. For public facilities that have multiple occupancy restrooms, signs shall
indicate that the multiple occupancy restrooms are either designated for men, women or
gender neutral. For single occupancy restrooms each single -occupancy restroom shall
B10
Title 4, Chapter 2, Building Code
Page 15 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
be outfitted with exterior signage that marks the single -occupancy restroom as a
restroom and does not indicate any specific gender. Signs shall be readily visible and
located near the entrance to each toilet facility. Signs for accessible toilet facilities shall
comply with the Illinois Accessibility Code.
2902.4.2 Existing Facilities. All existing single occupancy restrooms and family or
assisted -use restrooms shall be provided with signage in accordance with Section
2902.4
3105.1: General. Revise this section to read as follows:
Awnings or canopies shall comply with the requirements of this Section and other
applicable Sections of this Code. No person shall erect, install, remove, re -hang, alter,
or maintain over public property any awning or canopy for which a permit is required
under the provisions of this Code until the requirements of the sign regulations
ordinance, Title 4, Chapter 10 of the City Code, are met. Awnings and canopies shall
only extend to a point 2 feet back from the curb line.
3106.1: General. Revise this section to read as follows:
Marquees shall comply with this Section and other applicable Sections of this Code. No
person shall erect, install, remove, re -hang, alter, or maintain over public property any
marquee for which a permit is required under the provisions of this Code until the
requirements of Title 4, Chapter 10 of the City Code, are met. Marquees shall only
extend to a point 2 feet back from the curb line.
3107.1: General. Revise this section to read as follows:
Signs shall be designed, constructed, and maintained in accordance with this Code. No
person shall erect, install, remove, re -hang, alter, or maintain over public property any
sign for which a permit is required under the provisions of this Code until the
requirements of the sign regulations ordinance, Title 4, Chapter 10 of the City Code, are
met.
3201.5: Building Deterioration. In the event that a piece or part of an existing building
dislodges and falls onto the public way evidencing movement of building components
that comprise imminent danger, the following shall be required:
1) Within forty-eight (48) hours of a written notice of the imminent danger or failed
condition by the City of Evanston, the property owner(s) shall install illuminated
sidewalk and/or street protection as required by the City of Evanston. If this is
not completed in accordance with all city Codes, the City may install such
protection at the expense of the property owner(s).
2) Within thirty (30) days of such notice, the property owner shall submit to the
City a written report of the conditions by a State of Illinois licensed engineer. If
this requirement is not fulfilled in accordance with all city Codes, the violator is
subject to a fine of a minimum of $150.00 (one hundred fifty and no/100
dollars) for each day until the report is submitted.
3) Within sixty (60) days of such notice, the property owner shall obtain permits
for all required repairs. If this requirement is not fulfilled in accordance with all
Title 4, Chapter 2, Building Code
B11
Page 16 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
city Codes, the violator is subject to a fine of a minimum of $150.00 (one
hundred fifty and no/100 dollars) per day until the report is submitted.
4) Within one hundred eighty (180) days of such notice, all work associated with
the repair of the deterioration must be completed and inspected. If the
requirement of completion is not fulfilled in accordance with all city Codes, the
violator is subject to a fine of a minimum of $150.00 (one hundred fifty and
no/100 dollars) per day until the work is completed, as verified by a city
inspector.
3301.2: Storage and Placement. Revise this section to read as follows:
Construction equipment and materials shall be stored and placed so as not to endanger
the public, the workers or adjoining property for the duration of the construction project.
In no case, shall construction equipment or materials be kept or stored on any public
way or property.
3303.4: Vacant Lot. Revise this section to read as follows:
Every vacant lot shall be filled, graded, seeded, and/or sodded in accord with 3303.4.1.
3303.4.1: Wrecking, Demolition, or Razing of Structures.
1) Prior to the issuance of any permit for the wrecking, demolishing, or razing of
any building or other structure, the owner of said structure shall deposit, in
escrow, funds in an amount deemed sufficient by the Director of Community
Development to secure the owner's obligations to grade, place topsoil, seed,
sod, and/or fence any unimproved surface. Should the owner and/or owner's
successor(s) in interest fail to perform said duties, the City may draw on said
funds to complete them.
2) Prior to the start of demolition work, the owner and/or owner's successor(s)
shall deliver all water meters on the property to the Utilities Department.
3) Demolition work shall not begin until site has been inspected by the City for
placement of temporary fencing and temporary tree protection, and any related
measures implemented.
4) Demolition work shall not begin until the owner and/or owner's successor(s)
has established, either by way of a hose connected to the public water hydrant
or by the use of a water truck on site, a source for wetting down the structure
and resulting debris during the demolition process to minimize the creation of
air -borne dust and debris.
5) Written notice stating the date on which work is to begin shall be given to the
Director of Community Development and to owners/occupants of adjoining
property at least forty-eight (48) hours before beginning the wrecking,
demolishing, or razing of any building or other structure.
6) During demolition, any temporary structure erected adjacent to or on any public
way, used as temporary storage for debris and wreckage, shall be outfitted
with reflective orange material outlining every top and bottom corner of said
temporary structure, which reflective material will be visible when struck by
Title 4, Chapter 2, Building Code
B12
Page 17 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
headlight beams three hundred feet (300') away at night. Said markings shall
be approved by the City Engineer.
7) All foundations and footings associated with the demolished structure shall be
removed in the course of demolition. The property owner and/or owner's
successor(s) in interest shall schedule and permit an inspection by the Building
Official or his/her designee to determine removal of all foundations and
footings prior to the backfill of any excavated area.
8) Debris caused from the demolition of a building or structure in excess of that
required to fill openings shall be removed from the site as wrecking
progresses. Salvaged material, if left on the premises, shall be stored neatly.
Debris shall be kept from adjacent properties and public ways at all times.
9) On completion of demolition, all debris, equipment and temporary protections
shall be removed from the site. In no case shall demolition debris be allowed to
remain on the site longer than seven (7) days after the structure has been
demolished.
10) On completion of demolition, owner and/or owner's successor(s) shall
immediately restore the public right-of-way to its original condition upon
completion of the work, including restoration of openings, broom sweeping
walks and streets and raking of grassy areas.
11) On completion of demolition, the property owner and/or owner's successor(s)
in interest shall fill with clean inorganic material with the upper eight inches (8")
filled in friable topsoil and graded to the level of sidewalks, alleys, or adjoining
property with allowance for settlement.
12) On completion of demolition, the property owner and/or owner's successor(s)
in interest shall schedule and permit an inspection by the Building Official or
his/her designee to determine compliance with the City Code.
13) Unless construction of a new structure on the site commences within sixty (60)
days of completion of demolition, the property owner and/or owner's
successor(s) shall seed the property with grass or place sod thereon no later
than fifteen (15) days after completion of demolition. The temporary
construction fence shall be removed no later than fifteen (15) days after such
seeding or sodding.
Table 3306.1: Protection of Pedestrians. Revise this table to read as follows:
Height of Construction
8 feet or less
8 feet or less
More than 8 feet
Title 4, Chapter 2, Building Code
Distance from Construction
to Lot Line
Less than 5 feet
5 feet or more
Less than 5 feet
Type of Protection
Required
Construction railings
Construction railings
Barrier and covered
walkway
B13
Page 18 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
More than 8 feet 5 feet or more, but not more
than one-fourth the height
of construction
More than 8 feet 5 feet or more, but between
one-fourth and one-half the
height of construction
More than 8 feet Less than 5 feet
More than 8 feet 5 feet or more, but
exceeding one-half of the
height of construction
Ordinance 29-0-22, Exhibit B
Barrier and covered
walkway
Barrier
Barrier and covered
walkway
8-foot high chain link fence,
firmly anchored into the
ground.
3307.1: Protection Required: Add the following sentence. "Required notice to Owner
shall also be required for building demolition."
Chapter 34 Existing Structures of the 2012 IBC will be retained with the following
changes:
3401.6: Alternative Compliance. Delete.
3406.1.3: New Fire Escape. Delete.
3406.1.4: Limitations. Delete.
3412: COMPLIANCE ALTERNATIVES. Delete.
Appendix A
BUILDING CODE REGULATIONS FOR FIREARM RANGES
(1) DEFINITIONS. For purposes of this Appendix, the following definitions apply:
ANCILLARY The uses associated with the operations of the firearm range
SPACES. outside of the practice area, which directly support the operations of
the practice area. "Ancillary spaces" may include, but are not limited
to, offices, classrooms, locker facilities, washroom facilities, and
spectator spaces.
FIREARM Any indoor establishment where the discharging of a firearm, as
RANGE. defined in Section 9-8-1 and Section 6-18-3, is allowed for a
sporting event or for practice, instruction, testing, or training in the
use of a firearm. A Firearm Range may also include rental of a
firearm for allowable uses within the establishment and a firearm
dealer as defined and regulated by Title 9 Chapter 9 — Weapon of
the City Code.
FIRING LINE. The point where a person stands or positions himself to discharge a
firearm.
REAR WALL. The wall located in a practice area that is parallel to and opposite
from, the wall where the bullet trap/backstop is located.
SHOOTING The space between fixed panels along the firing line designed to
B14
Title 4, Chapter 2, Building Code
Page 19 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
BOOTH. protect someone discharging a firearm from an adjacent person
discharging a firearm.
SHOOTING The space along the firing line designated for an individual practice
POSITION. area patron to use when discharging a firearm.
PRACTICE The section of the firearm range facility from the firing line to the
AREA. rear (exterior) wall of the structure behind the backstop.
(2) GENERAL REQUIREMENTS.
(a) Every firearm range erected, constructed within an existing building, or
substantially rehabilitated shall comply with all applicable special provisions of
this appendix.
(b) Every firearm range erected, constructed within an existing building, or
substantially rehabilitated shall comply with the requirements the applicable
code requirements for the specific use of the space as determined by Title 4,
Chapter 2 "Building Code" of the Evanston City Code of 2021, as amended.
(c) Where a more specific or restrictive requirement is provided in this section than
found elsewhere in the code, the requirements in this section shall govern.
(3) PERMITS REQUIRED.
(a) It shall be unlawful to proceed with the construction, installation, enlargement
or alteration of a firearm range without first obtaining a permit from the Division
Manager of Building and Inspection Services Division or his/her designee and
other required departments.
(b) The permit fee for the initial installation and inspection of the firearm range
shall be in the amount required by Ordinance 138-0-14, as amended.
(c) The permit application shall include drawings and documents that fully
describe all features of the firearm range, including but not limited to the
installed equipment and all required ballistic safety features, along with all
supporting documents to fully describe the building, all appurtenances and the
intended caliber of ballistics.
(4) ENCLOSURE REQUIREMENTS.
(a) A practice area must be totally enclosed with contiguous walls, a ceiling, and a
floor that separates the practice area from the remaining part of the firearm
range and any other uses located in the building. Except as provided in
subsection (b) of this section, the enclosure shall be penetration -proof for the
heaviest caliber of ammunition used in the practice area if fired point blank into
the enclosure at 90 degrees to the surface. Enclosure walls, floors, ceiling
assemblies, doors and opening protective assemblies for the practice area
shall be designed and constructed with materials and assemblies sufficient to
stop all bullets fired or projectiles from penetrating beyond the practice area
enclosure.
Title 4, Chapter 2, Building Code
B15
Page 20 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
(b) The rear wall shall be designed and constructed of materials, assemblies, and
opening protectives strong enough to be capable of stopping a ricochet of a
bullet, fragment or back splatter, from penetrating beyond the rear wall.
(c) All enclosure requirements shall comply with Range Design Criteria - U.S.
Department of Energy Section 5 - Indoor Range Design, as amended.
(5) ANCILLARY SPACES. Ancillary spaces shall be contiguous to the practice area
and directly support the operations of the practice area. These spaces shall be
separated from the practice area with appropriate means to diminish contamination
from the by-products of the practice area and be protected from any projectiles
straying from the practice area.
(6) OCCUPANCY REQUIREMENTS.
(a) A firearm range occupancy classification shall be an A-3 occupancy. All
ancillary spaces shall have an occupancy classification in accordance with all
of the requirements that are applicable to each of the purposes for which the
room or space will be occupied. Where a structure is proposed for a purpose
that is not specifically provided for in this code, such structure shall be
classified in the group that the occupancy most nearly resembles, according to
the fire safety and relative hazard involved. The most restrictive ancillary space
occupancy which is greater than 5% of the total firearm range area shall
govern the occupancy classification. A firearm range shall comply with the
applicable code requirements for the specific use of the space as determined
by Title 4, Chapter 2 and this section. The amount of area per person shall be
determined by 2021 International Building Code, Section 1004, as amended.
(b) The occupancy calculation to determine the occupancy count of the practice
area shall be determined by calculating the amount of area behind the firing
line between the firing line and the perimeter of the enclosure protecting the
remaining firearm range facility from projectiles and dividing that area by 20
square feet. All firing lines shall be stationary.
(c) The occupancy count shall be used to determine the required number and size
of the exits. The area between the firing line and the bullet trap/backstop shall
be unoccupied and shall not be counted in the occupancy load calculations or
be considered for exiting travel distance.
(7) HEIGHT AND AREA LIMITATIONS.
(a) The height and area limitations of a firearm range shall be as provided in Title
4, Chapter 2 and the 2021 International Building Code, Chapter 5. In
calculating the maximum allowable area of the firearm range, the total area in
the practice area, including the area from the firing line to the wall behind the
backstop/bullet trap, shall be included in such calculations.
(b) The maximum height of every practice area erected or constructed within a
new or existing building shall be one-story or 20 feet, whichever is less, and
the maximum area shall match the limitations for H-3 classification,
Title 4, Chapter 2, Building Code
Page 21 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
Construction Type I or II only per 2021 International Building Code, table
506.2.
(8) PRACTICE AREA FACILITY REQUIREMENTS.
(a) The firearm range must comply with all applicable code sections as determined
by the occupancy classification. Where the ancillary spaces are under the
direct control and management of the owner of the practice area, no mixed
occupancy separation is required between the practice area and the ancillary
spaces. Where the ancillary spaces are not under the direct control and
management of the owner of the practice area, or where the practice area is
constructed without ancillary spaces, the mixed occupancy separation shall be
as set forth in the 2021 International Building Code, Table 508.4.
(b) Exiting for the firearm range shall not be through the practice area.
(c) (1) The firearm range may include the following uses: office space, mercantile,
training, classroom or spectator space, general patron use space, locker rooms
including showers, range master booth, storage of ammunition, and storage of
firearms.
(2) The firearm range shall include the following uses:
(a) a practice area;
(b) security entrance;
(c) toilet facilities in compliance with current edition of the Illinois
Plumbing Code; and
(d) all occupancies within the firearm range must be protected from any
projectiles straying from the practice area.
(9) PRACTICE AREA REQUIREMENTS.
(a) Every practice area shall be separated from the rest of the firearm range facility
and/or other occupancies with a separation that prevents projectiles from
straying from the practice area.
(b) Every practice area shall comply with the following:
(1) Area Requirement. The shooting range shall have a minimum ceiling
height of 8 feet. The area between the firing line and the rear wall shall be
at a minimum adequate to accommodate a designated exit path beyond
the depth of the area occupied by the practice area patron and any
appurtenances. The exit path shall be in addition to the area required for
practice area patrons to easily and directly move from one shooting booth
or shooting position to another along the firing line without disturbing
another practice area patron, and in addition to the area required for the
range master to monitor operations;
(2) Sound Control: The noise emanating from the practice area to areas
outside of the firearm range is subject to City of Evanston Code, Title 6,
13-1-4, compliance with applicable regulations for noise and vibration
B17
Title 4, Chapter 2, Building Code
Page 22 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662felf15
Ordinance 29-0-22, Exhibit B
control. The maximum noise emanating from the firearm range shall not
be more than 55 dB when measured from a distance of 100 feet or more
from the source, or 70 dB when measured from a distance of 10 feet or
more from the source. The practice area shall conform to the requirements
of The Occupational Noise Exposure Standard Section 1910.95 of 29 CFR
Part 1910 and shall be designed and constructed to contain noise
generated from the discharge of firearms.
(3) Special Ballistic Protectives: The practice area shall have ceiling baffles,
deflector plates and floor guards of appropriate materials, such as steel
plate covered with wood or other materials, which are designed with
sufficient bullet resistive strength, thickness, and configuration to function
safely for the type and caliber of firearms and ammunition used within the
practice area. Such protectives shall be permanently located and
anchored to protect the building structure, lighting fixtures, HVAC ductwork
and appurtenances, plumbing hose bibbs, floor drains and cleaning
apparatus, ceilings, target carrier apparatus or other range appurtenances
or assemblies to protect against ricochets or back splatter and to re -direct
the projectiles to the backstop;
(4) Bullet Trap/Backstop: The practice area shall have a permanent, fixed,
manufactured bullet trap system capable of stopping and containing the
bullets or projectiles from any firearms discharged in the practice area.
The bullet trap shall be designed and constructed of appropriate bullet
resistive, durable materials, such as steel plate. The bullet trap shall be
capable of functioning safely for the type, amount and duration of firearm
usage at the practice area. The bullet trap shall cover the entire space
between the two side walls of the practice area and provide complete
coverage for all firing positions from floor to the underside of the structural
ceiling assembly. Bullet trap systems which utilize rubber chunks, blocks,
sheets, layered rubber, laminated carpeting or other materials potentially
subject to combustion, shall be fire -treated to be fire -resistive and meet
the flame spread requirements of Class 1, unless the building is equipped
with an approved automated sprinkler system, in which case Class 2
requirements shall apply. Mobile or temporary bullet traps/backstops are
prohibited;
(5) Exit Pathways. Exits and exit pathways serving the practice area shall not
require occupants to pass beyond the firing line and cross through the
practice area. The area from the firing line to the back of the
backstop/bullet trap shall not be included in the exiting travel distances. No
exits shall be located in this area;
(6) No Doors or Windows Downrange: No doors or windows shall be located
in the practice area in the space between the back face of the bullet trap to
a point five feet behind the firing line located the farthest distance from the
bullet trap/ backstop;
Title 4, Chapter 2, Building Code
Page 23 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
(7) Floors, Ceilings, and Walls. The floors, ceilings, and walls of every
practice area shall be constructed of smooth non -porous materials to
facilitate effective maintenance and cleaning and removal of lead
particulate.
(8) Shooting Booths. Where shooting booth separations are provided, the
shooting booth panels shall be constructed of permanently fixed,
cleanable, non -porous materials. The shooting booths shall be constructed
to provide an impenetrable protective barrier between people in the
shooting booths and to protect against the effects of ejected bullet casings
and muzzle blast;
(9) Range Master Booth. Where a range master booth is provided, the
practice area shall be limited in size to the area that can be directly visible
to the range master at all times. The range master booth shall be
constructed to provide:
(i) protection from any projectiles straying from the practice area;
(ii) clear visibility of all firing positions at the practice area;
(iii) ready access to the practice area;
(iv) acoustical protection and separation for the range master;
(v) protection from exposure to lead particulate from the practice area, as
provided for in rules and regulations promulgated by the department
of health; and
(vi) immediate access to and use of the practice area communication
system;
(10) Removal of Lead Particulate: The practice area shall be equipped with a
lead particulate removal system, such as a HEPA vacuum or other such
system approved by the commissioner of public health, or a lead
particulate removal system which removes the lead particulate using
water; and
(11) If the practice area uses a lead particulate removal system that removes
the lead particulate using water, the practice area shall have a floor drain
at the backstop/bullet trap that collects lead and other hazardous waste
material in a separate drainage system to an approved collection device or
treatment system that complies with all applicable local, state or federal
laws and standards.
(10) VENTILATION REQUIREMENTS. In addition to general building ventilation and
heat requirements applicable to a firearm range, the practice area shall be provided
with an engineered ventilation and exhaust system that complies with OSHA Lead
Standard for General Industry, 29 CFR 1910.1025 that limits lead exposure and
prevents the build-up of noxious gases caused by the discharge of firearms. The
practice area ventilation and exhaust system shall conform to the following
requirements:
Title 4, Chapter 2, Building Code
B19
Page 24 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
(a) The ventilation air supply system shall provide a horizontal laminar air flow
from floor to ceiling at the firing line of 75 fpm. The minimum allowable range
laminar air flow shall be 50 fpm from the firing line to the bullet trap. The
laminar flow of air shall be directed away from shooters at the firing line
downrange towards the backstop/bullet trap area.
(b) The entire practice area shall be maintained at a slightly negative pressure with
respect to adjacent areas to prevent the escape of contaminants from the
shooting range. Exhaust air shall exceed supplied air by a minimum of 10%.
(c) The practice area shall be designed and constructed with separation walls,
doors, windows and assemblies with related gaskets and sealing materials
sufficient to close off the practice area from the firearm range and adjacent
spaces to provide the air pressures required for the practice area ventilation
and exhaust system to operate correctly.
(d) Where a firearm range contains multiple practice areas, each practice area
shall be provided with a separate ventilation and exhaust system.
(e) The supply and exhaust systems shall be electrically interlocked to turn on
each system at the same time.
(f) The practice area ventilation and exhaust system shall be a totally separate
system isolated from any other ventilation and exhaust system which serves
the ancillary spaces of the firearm range facility.
(g) The ventilation and exhaust system shall be commissioned prior to initial
operation, and a regular schedule of maintenance and system adjustment shall
be included in the description of the ventilation and exhaust system as part of
the permit application. For purposes of this subsection (g), "commissioned" has
the same meaning ascribed to that term in American Society of Heating,
Refrigeration, and Air-conditioning Engineers Guideline 0-2005, as amended.
The practice area ventilation and exhaust system shall be operated and
maintained in conformity with the submitted schedules and procedures.
(h) The practice area ventilation and exhaust systems shall be either
(1) a 100% total exhaust/purge system utilizing 100% fresh make up air. All
air from the practice area shall be completely exhausted. The exhausted
air shall be filtered and cleaned to remove lead particulate before
exhausting to the open atmosphere. Twenty-five percent of the airflow
shall be exhausted 15 feet downrange from the firing line and the other
75% shall be exhausted at the apex of the backstop/bullet trap. The
ventilation system shall operate at one fan speed only and shall be
designed and provided with automatic sensors and controls, where
required, to monitor and ensure the performance and safety of the system;
or
(2) an air cleaning re -circulation system that re -circulates up to a maximum of
75% of the air and cleans and exhausts a minimum of 25% of the air in the
practice area. The air re -circulation system shall be designed and provided
Title 4, Chapter 2, Building Code
B20
Page 25 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
with primary and secondary filters, high efficiency particulate air (HEPA)
filters, electronic precipitators or other air filtering and cleaning technology,
as reviewed and approved by the Building Official, to remove lead
particulate from the re -circulated air before re -introduction into the practice
area. System exhaust fans may operate at variable speeds. The
ventilation system shall be designed and provided with automatic sensors
and controls, where required, to monitor and ensure the performance and
safety of the system.
(i) New technology or designs for practice area ventilation and exhaust systems
not authorized in this code shall be reviewed and approved by the Building
Official on standards and tests prior to installation.
(j) All other ventilation, refrigeration and heating systems for the firearm range
shall conform to the requirements of the 2021 International Mechanical Code,
as amended by the City of Evanston.
(k) The practice area shall be provided with heating and cooling for the comfort of
practice area patrons and staff. Where the heating or cooling system is not a
component of the ventilation and exhaust system, such as radiant heating or
geothermal sourcing, one heating or cooling system in the firearm range is
permitted.
(1) All ventilation and exhaust equipment, ducts and appurtenances shall be
located and installed to allow ready maintenance and inspection.
(11) PLUMBING REQUIREMENTS.
(a) Every firearm range shall meet all applicable plumbing code requirements of
the Illinois Plumbing Code as adopted and amended by the City of Evanston.
(b) The occupancy calculation to determine the required number of plumbing
fixtures for the firearm range shall be determined by this Appendix, Occupancy
requirements.
(c) The discharge of any waste from the firearm range shall be in compliance with
all applicable local, state or federal laws or standards, and shall comply with
the requirements of the City of Evanston Code, Title 4, Chapter 13 to prevent
the discharge of any prohibited waste from entering into any sewer,
watercourse, natural outlet or waters.
(d) Interceptors or separators shall be installed to recover solids from metal
particles, metal chips, shavings, plaster, stone, clay, sand, cinder, ashes,
glass, gravel, oily or greasy residual waste and similar materials in separating
lighter than water waste from heavier than water waste or waste from soiled
water to prevent such matter from entering the drain line. The size, type,
location and construction material of each interceptor and of each separator
shall be designed and installed in accordance with the manufacturer's
instructions. All interceptors and all separators shall be installed in an
accessible location to permit the convenient removal of the lid and internal
contents and to permit service and maintenance. Unless otherwise approved,
Title 4, Chapter 2, Building Code
B21
Page 26 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
all interceptors and separators shall have an inspection manhole located
outside on private property to permit observation, measurement and sampling
downstream of the interceptors or separators.
(e) Waste that does not require treatment or separation need not be discharged
into any interceptor or separator and may be in a separate line until after the
interceptor or separator but must connect to the building sewer before the
public way. Waste from the firearm range which does not have a lead
contamination level of more than 0.5 mg/L is not required to discharge into an
interceptor or separator.
(f) Grease traps approved by the department of buildings shall have the waste
retention capacity indicated in the Illinois Plumbing Code for the flow -through
rated indicated.
(12) ELECTRICAL REQUIREMENTS.
(a) Every firearm range shall be constructed with emergency lighting in
conformance with the requirements of 2020 National Electric Code, Article 700.
(b) The practice area shall be constructed to be free of excessive glare and major
differences in light levels. Floors and ceilings shall be designed to provide light
reflection.
(c) The lighting design and construction of every practice area shall include the
following:
(1) General lighting shall provide uniform light levels over the entire practice
area and adjoining spaces;
(2) Local lighting shall supplement general lighting along the firing line to
provide better visibility;
(3) Semi -direct lighting shall be provided to direct 60 to 90 percent of the
lighting on the target.
(13) GREEN BUILDING STANDARDS. All new buildings or spaces altered shall comply
with the City of Evanston, Title 4, Chapter 21, Green Building Ordinance.
4-2-3. BUILDING CONTRACTORS.
(A) Definition. The term "building contractor" means any person, individual, company,
or corporation engaged in the business of constructing, enlarging, altering,
removing, or remodeling any structure including constructing, maintaining, repairing
or installing landscape systems by furnishing of labor, material, and methods
necessary to accomplish a given result, and who retains for himself/herself the
control of the means, method, and manner of accomplishing this desired result.
(B) Registration Required. Any person engaged in the business of building contractor,
including general and trade contractors, within the City for which a building permit is
required must register with the Community Development Department. Any person
engaged in the business of constructing, maintaining, repairing or installing
landscape systems is required to register with the Community Development
B22
Title 4, Chapter 2, Building Code
Page 27 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
Department. Registration must be submitted on forms available from the City and
must include the following information:
1. Contractor's name;
2. Business name;
3. Business address;
4. Business telephone;
5. Business email address;
6. Federal Employer Identification Number (FEIN);
7. Whether the business is a sole proprietorship, partnership or corporation, and
registered agent, if applicable;
8. Whether the contractor is required to be licensed by the State of Illinois, a copy
of the current license number and an original certificate of insurance as
detailed in this Section;
9. Electrical contractors must be licensed by an accredited Iicensure commission,
a copy of the current license with the license number, and an original certificate
of insurance as detailed in this Section;
10. Cross Connection Control (C3) contractors shall submit a copy of their City of
Evanston C3 license issued in accordance with Section 7-12-16-3 of the City
Code.
11. Pavement Sealant contractors shall provide verification that coal tar, coal tar
derivatives or coal tar mixtures shall not be applied to any public or private
property in the City of Evanston in accordance with Title 7, Chapter 18 of the
City Code.
12. Landscape contractors shall submit the Office of Sustainability's Landscape
Company Survey and a vehicle list with photo documentation of company
vehicle(s) signage displaying the company name and company phone number.
Signage shall be 100 square inches (minimally).
13. An original certificate of insurance or policy declaration documenting that the
contractor carries general liability insurance with a minimum of three hundred
thousand dollars ($300,000.00) per occurrence, bodily injury insurance with a
minimum of one hundred thousand dollars ($100,000.00) per occurrence,
property damage insurance with a minimum of one hundred thousand dollars
($100,000.00) per occurrence and workers' compensation insurance at the
statutory minimum amounts. Exceptions:
a. Sole proprietorships and partnerships with no employees are exempt from
the workers' compensation insurance requirement with submission of an
affidavit.
b. Contractors required to maintain insurance as part of their State Iicensure
must provide proof of insurance in forms and amounts required by State
law.
B23
Title 4, Chapter 2, Building Code
Page 28 of 99 Doc ID: 89d95372ca2la88d7c7e45de8e6b363662felfl5
Ordinance 29-0-22, Exhibit B
c. Contractors who are engaged to perform work in the public right-of-way
must carry general liability insurance with a minimum of one million dollars
($1,000,000.00) per occurrence and name the City of Evanston as an
additional insured.
(C) Registration Fee. The amount of the annual registration fee for persons engaged in
the business of building contractor shall be established from time to time by action
of the City Council.
(D) Renewal of Registration. Registration is valid for one (1) year from the date of
issuance. Registration may be renewed based upon an application for renewal and
the payment of the annual registration fee. The City Manager or his/her designee is
authorized to review a renewal request in the same manner as the initial
application.
(E) Amended Registration. Registered individuals must notify the Community
Development Department within twenty (20) business days of any change in the
registration information by filing an amended registration statement on a form
provided by the Community Development Department for such purpose. There is
no additional fee for filing an amended registration.
(F) Suspension or Revocation of Registration.
1. If any person shall violate any of the provisions of this Chapter or the Code
adopted hereby, he/she shall be liable to be prosecuted against for any fine or
penalty imposed thereto and his/her registration may be suspended or revoked
by the City Manager.
2. No such registration shall be so revoked or suspended except after a hearing
by the City Manager or his/her designee with a three (3) business day notice to
the registered person affording the registered person an opportunity to appear
and defend. The notice shall specify the reason for the contemplated
suspension or revocation and shall give the date, time, and room number in the
civic center of the hearing. Notice shall be sufficient if sent to the address
stated on the registered person's application.
3. If the Building Official certifies to the City Manager that he/she has reason to
believe that immediate suspension of the registration is necessary to prevent
the threat of immediate harm to the community, the City Manager may, upon
the issuance of a written order stating the reason for such conclusion and
without notice or hearing, order the registration suspended for not more than
seven (7) days. The City Manager may extend the suspension during the
pendency of a hearing upon a written determination that doing so is necessary
to prevent the aforesaid harm to the community.
4. Hearings shall be conducted in accordance with procedures on file with the
City Clerk.
5. The City Manager shall issue his/her decision within ten (10) business days
after the close of the hearing. In reaching a decision, the City Manager may
consider any of the following:
Title 4, Chapter 2, Building Code
B24
Page 29 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit B
a. The nature of the violation.
b. The nature and extent of the harm caused by the licensee's action or
failure to act.
c. The factual situation and circumstances surrounding the violation.
d. Whether or not the action or failure to act was willful.
e. The record of the registered person with respect to violations.
6. The City Manager may suspend a registration for a period of up to ninety (90)
days. A registered person whose registration has been revoked shall not be
eligible to reapply for a registration until the expiration of one (1) year after the
effective date of the revocation.
4-2-4. PENALTY FOR VIOLATIONS.
Any person found to have violated any provision of the 2021 International Building
Code as adopted by the City, or who shall fail to comply with any of the requirements
thereof, or who shall erect, construct, alter or repair a building or structure in violation of
any approved plan or direction of the Building Official or of any permit or certificate
issued by the Building Official or his/her designee, shall be guilty of an offense and fined
as follows:
(A) 1. The fine for a first violation is one hundred fifty dollars ($150.00).
2. The fine for a second violation is four hundred dollars ($400.00).
3. The fine for a third or subsequent violation is seven hundred fifty dollars
($750.00).
(B) Each day a provision of this Chapter is found to have been violated constitutes
a separate violation subject to the fine schedule set forth in Subsection (A) of
this Section.
(C) The fines provided for herein shall not be construed as limiting the power of a
court of competent jurisdiction or an administrative hearing officer to impose
other penalties and remedies as provided for by applicable legislation.
4-2-5. SEVERABILITY.
It is the intention of the City Council that the provisions of this Chapter and the Code
adopted hereby are severable and the invalidity of any Section or any portion of any
such Section of either of them shall not affect any other Section.
4-2-6. — IDENTIFICATION OF ORDINANCE WITH THE ILLINOIS CAPITAL BOARD.
The adoption of this Ordinance and code, by title and edition, shall be reported to the
Illinois Capital Development Board Illinois or any successor agency of the State of
Illinois pursuant to Section 1-2-3.1 of the Illinois Municipal Code, 651LCS 5/1-2-3.1.
4-2-7. — EFFECTIVE DATE.
Title 4, Chapter 2, Building Code
B25
Page 30 of 99
Doc ID: 89d95372ca2la88d7c7e45de8e6b363662felfl5
Ordinance 29-0-22, Exhibit B
This Ordinance shall be in full force and effect thirty (30) days after its approval and
passage. For projects in design concurrent with the adoption of this ordinance, the
building official is authorized to accept construction documents designed in accordance
with the requirements of the 2012 International Building Code for up to one hundred and
eighty (180) days after this ordinance's approval and passage.
Title 4, Chapter 2, Building Code
B26
Page 31 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
CHAPTER 4 FIRE PREVENTION REGULATIONS
4-4-1. ADOPTION.
(A) Pursuant to the authority granted by 65 ILCS 5/1-2-4, and pursuant to its home rule
powers, the City of Evanston hereby adopts by reference the 2021 International
Fire Code and 2021 National Fire Protection Association 101, Life Safety Code,
which shall be used together with the below stated additions and amendments as
criteria for the control and regulation of conditions which would constitute fire
hazards to persons or property within the city or which would interfere with fire
suppression forces, excepting therefrom the sections which are modified or deleted
in Section 2 of this Chapter.
(B) Any reference in the 2021 International Fire Code or the 2021 National Fire
Protection Association 101, Life Safety Code to "Administrative Authority" or "Fire
Official" shall mean the Fire Chief of the City of Evanston or his/her designee. Any
reference to "municipality" shall mean the City of Evanston.
(C) In the event that any provision of the 2021 International Fire Code or the 2021
National Fire Protection Association 101, Life Safety Code adopted hereby is in
conflict with any provision(s) of the City Code, the more/most stringent shall control.
(D) There shall be a copy of the 2021 International Residential Code and the 2021
National Fire Protection Association 101, Life Safety Code kept on file for public
inspection in the City Clerk's office.
4-4-2. AMENDMENTS.
2021 International Fire Code: The 2021 International Fire Code adopted hereby shall
read as follows with respect to the indicated Sections.
101.1: Title: These regulations shall be known as the Fire Code of the City of Evanston,
hereinafter referred to as "this Code."
111.1: Appeals: Any person, firm or corporation affected by any decision, interpretation
or order of the Fire Official made under any provision of these Codes or the standards
adopted herein, may appeal such decision, interpretation, or order to the Fire Chief by
filing a written notice of such intent to the office of the Fire Chief within fifteen (15) days
after the day the decision, interpretation, or order was served. For purposes of this
Section, a decision, interpretation, or order is served upon delivery, in the case of
personal delivery, and in the case of mailing, five (5) days after deposit in the U.S. mail
with first-class postage prepaid. The Fire Chief, or his/her designee, shall convene a
hearing upon such appeal within ten (10) days of receipt thereof and may, when no
immediate hazard exists, continue such hearing from time to time for cause. The Fire
Chief shall establish reasonable rules for such hearings and shall make a record of
proceedings. The rules shall be on file with the Fire Chiefs office. The decision of the
Fire Chief shall be deemed final as to the order or interpretation appealed from. The
decision shall be in writing and shall be issued within two (2) business days of its
rendering. Where there are practical difficulties in the implementation of the strict
provisions of these Codes, the Fire Chief may modify such provision provided that such
C1
Title 4, Chapter 4, Fire Prevention Regulations
Page 32 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
modification shall effect substantial conformance with the provisions hereof, provide for
the public safety.
A person is "affected" for the purposes of an appeal pursuant to this Section when the
person has a material or definitive interest in the decision, interpretation, or order of the
official. An application for appeal shall be based on a claim that the true intent of a Code
adopted by the City or the rules legally adopted thereunder, have been incorrectly
interpreted, or the provision of these Codes are adequately satisfied by other means.
307.4.3 Fire Pit Regulations: The use of fire pits will be allowed provided the following
regulations are complied with:
1) For clarity, a fire pit includes a permanent below ground fire pit, a permanent
grade level outdoor fireplace or a portable outdoor fireplace, all intended to
contain and control outdoor wood fires.
2) Portable fire pits, constructed of steel, brick, or masonry, shall be used in
accordance with the manufacturers specifications and safety guidelines and
must be placed upon a non-combustible surface.
3) Only natural seasoned firewood or commercial logs may be burned.
4) The fires in fire pits shall be kept manageable.
5) The use of the fire pit must be attended and supervised by a competent adult
property owner until the fire has been completely extinguished. A legal
resident/tenant of a property may use a fire pit in accordance to this ordinance
as long as the property owner or assigned management company grants
written permission to the legal resident/tenant. The use of the fire pit must be
attended and supervised by the legal resident/tenant until the fire has been
completely extinguished.
6) A portable ten pound (10 lb.) ABC type fire extinguisher or other approved
extinguishing equipment, such as a garden hose, bucket of sand, or dirt, must
be readily available.
7) The use of a fire pit which creates a hazardous or objectionable condition shall
be prohibited. The code official is authorized to order the extinguishment of a
fire in a fire pit creating a hazardous or objectionable condition.
8) The use of the fire pit shall not be located within ten feet (10') of a structure or
any combustible material. In no case shall the appliance be located directly
under overhead combustible construction.
9) The use of the fire pit shall not cause any building fire alarm system to activate.
10) Guidelines when using fire pit shall include common sense, respect for
neighbors and neighborhoods.
308.1.4: Open -Flame Cooking Grills: Barbecue grills shall not be used on any stairs
or porches that serve as a means of egress. The use of barbecues will be allowed on
balconies or at ground level provided the following regulations are complied with:
Title 4, Chapter 4, Fire Prevention Regulations
C2
Page 33 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
1) The use of a cooking grill which creates or adds to a hazardous or
objectionable situation shall be prohibited.
2) Read the owner's manual for safety guidelines.
3) The use of the barbecue shall not cause the building's fire alarm system to
activate.
4) A portable fire extinguisher shall be located in close proximity to the barbecue,
but not affixed to the grill. The fire extinguisher shall be at least a 10 pound
ABC type extinguisher.
5) Extreme caution shall be exercised when lighting the barbecue to prevent
flames from elevating to an excessive height.
6) Hot ashes or cinders shall be deposited into noncombustible receptacles free
of all combustible material and away from combustible construction.
404.4.1: Emergency guide: Fire safety evacuation plans in accordance with Section
404.2.1 shall be provided to each living unit on an annual basis. Living units include
apartments, condominiums, dormitories, hotels, and any other type of residential or
commercial living unit.
505.1.1: Address on Rear and Side Doors: Signage with the address, including the
name of the street and business name or building name, shall be installed at all other
entrance and exit doors. The sign shall be installed at a height of approximately five feet
(5) above the standing surface. The sign shall be installed immediately to the latch side
of the door so it is visible with the door in the open or closed position. All other
installation locations shall be approved by the Fire Official.
505.3: Truss (Wood) Construction Signage: Identification signage as designated by
the Fire Official shall be installed by the property owner on all structures in which the
roof is of a truss construction design. The signage shall be approved by the Fire Official
and installed so that it is visible from the street for the Fire Department use.
508.1.1.1: Fire Command Center: All fire command centers shall be equipped with a
five (5)-button combination keypad for entry into the room or other entry device
approved by the Fire Official.
509.1.2: Room Identification: Signage shall be placed at all doors identifying the room.
The signage shall be installed at a height of approximately five feet (5) above the
standing surface. The signage shall be installed immediately to the latch side of the
door so it is visible with the door in the open or closed position.
603.2.3: Electrical Equipment: The Fire Official may require remote power
disconnects for specialized electrical equipment such as solar panels, wind turbines,
etc.
604.3.1: Manual Transfer: Standby power shall be manually transferable to all
elevators in each bank. This transfer switch shall be located in the fire command room
or location designated by the Fire Official.
Title 4, Chapter 4, Fire Prevention Regulations
C3
Page 34 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
901.7: Systems Out of Service: Any required fire protection/detection system placed
out of service for more than six (6) hours in a day and/or for a cumulative total of twenty
(20) hours a week shall require the approval of the Fire Official or his designee. Any fire
protection/detection system placed out of service for periods equal to or greater than
those stated without the approval of the Fire Official, will be subject to the following
fines:
■ First warning: No charge
■ Second warning: $200.00
■ Third warning: $300.00
■ Fourth and subsequent warnings: $500.00
903.2: Where Required: Approved automatic sprinkler systems in new buildings and
structures shall be provided in the locations described in Sections 903.2.1 through
903.2.12. In any Group, where the condition requiring an automatic sprinkler system
states a fire area greater than 5,000 square feet, that square footage shall be changed
to 5,000. All other conditions for the Group shall apply. The building area shall be
defined in accordance with Section 202 and include each story.
Reference the 2021 International Residential Code Section R313 Automatic Fire
Sprinkler Systems as amended for provisions for townhouses and one- and two-family
dwellings including those with accessory dwelling units.
903.3.1: Standards: Sprinkler systems shall be designed and installed in accordance
with Section 903.3.1.1, Section 903.3.1.2, or Section 903.3.1.3 and other chapters of
this Code, as applicable. A minimum of five (5) psi safety factor in the fire protection
system hydraulic calculations shall be provided for all systems, except in one- and two-
family dwellings. The system demand shall be five (5) psi below the seasonal low-water
test supply. Sprinklers shall be required in all clothes closets, linen closets, pantries,
and bathrooms, regardless of size, except in one- and two-family dwellings.
903.3.7.1: Number of Fire Department Connections: The Fire Official shall determine
the number of Fire Department connections appropriate for the building.
903.3.7.2 Access to Fire Department Connections: Any Fire Department connection
located behind or within landscaping or vegetation shall have a concrete path from the
sidewalk or closest public way to the connection. A concrete pad with minimum
dimensions of forty-eight inch (48") x forty-eight inch (48") shall also be provided at the
Fire Department connection.
903.3.7.3: Type of Fire Department Connections: Unless otherwise approved by the
Fire Code Official, a five (5) inch Storz type connection with a thirty (30) degree down
turn shall be required. The fire department connection shall be installed between
twenty-four (24) inches and forty-two (42) inches above the standing surface.
903.3.7.4: Fire Department Connection Locator: Provide a white strobe light above
all Fire Department connections to flash upon activation of the fire alarm system. All
strobes shall be installed at a height that will make it visible from the street. Exception:
Existing systems, unless the system is altered, modified, or upgraded.
Title 4, Chapter 4, Fire Prevention Regulations
C4
Page 35 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
903.4.3.1: Sprinkler Control Valves: Approved supervised indicating control valves
shall be provided at the point of connection to the riser on each floor in all buildings.
Control valves shall also be provided for each individual unit (commercial, residential, or
business) where the units share a common water supply and have individual entrances.
904.3.5.1 Alternate Systems Monitoring: All new alternate automatic fire
extinguishing systems shall be monitored by a fire alarm signaling system in
accordance with NFPA 72 remote or central supervision station.
905.3.1: Required Locations. Class I standpipe systems shall be installed throughout
buildings where the floor level of the highest story is located more than thirty feet (30',
9.144 m) above the lowest level of the Fire Department vehicle access, or where the
floor level of the lowest story is located more than thirty feet (30', 9.144 m) below the
highest level of Fire Department vehicle access.
Class I standpipe systems shall be installed throughout buildings where the floor level of
the highest story is less than thirty feet (30', 9.144 m) above the lowest level of the Fire
Department vehicle access, but the length of hose laid by the Fire Department is greater
than one hundred fifty feet (150') from the point of the Fire Department vehicle's access
to the furthest point in the building.
905.4.3: Standpipe Hose Connections: All standpipe hose connections shall include a
two and one-half inch connection with a cap attached to a chain. The hose connections
shall be installed on a forty-five degree (451) angle towards the floor level unless
otherwise approved by the Fire Official.
906.3 Size and distribution. The size and distribution of portable fire extinguishers
shall be in accordance with Section 906.3.1 through 906.3.4. In new structures or
occupancies, the minimum size fire extinguishers installed shall be 4A:60B:C (Ten (10)
Pound).
906.6.1: Fire Extinguisher Signage: Projection style signage shall be installed above
each extinguisher to identify the location. The sign shall be installed at a height of
approximately six to seven feet (6' to 7') above the standing surface where the
extinguisher is mounted. Style of that sign must be approved by the Fire Official.
907.4.3.1: Smoke Detectors, Where Required: Smoke detectors, installed as part of
an approved automatic fire alarm system, shall be installed at the top of all interior
stairways and elevator shafts unless otherwise directed by the Fire Official.
914.3.1.2: Water supply to required fire pumps: Required fire pumps for high-rise
buildings shall be supplied by connections to at least two (2) water supplies. The two (2)
connections shall be made to the same main and valved in such that an interruption can
be isolated so that the water supply will continue without interruption through at least
one (1) of the connections. Each connection and the supply piping between the
connection and the pumps shall be sized to supply the flow and pressure required for
the pumps to operate and be provided with its own backflow prevention device.
Exceptions: Any water supply arrangement that is approved by the Fire Official and
Utilities Department.
Title 4, Chapter 4, Fire Prevention Regulations
C5
Page 36 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
1023.9: Stairway Identification Signs: An interior exit stairway and ramp shall not
continue below its level of exit discharge unless an approved barrier is provided at the
level of exit discharge to prevent persons from unintentionally continuing into levels
below. Directional exit signs shall be provided as specified in Section 1011. The top of
the approved barrier shall not be less than thirty-six inches (36") from the finished floor
of the landing. The barrier shall be self -closing. The only approved method of holding
the barrier in the open position shall be a magnetic 'hold open' connected to the building
fire alarm system. The barrier shall be a contrasting color from the colors in the
immediate area.
1023.9.1.1: Signage Requirement: A sign shall be provided at each floor landing in an
interior exit stairway and ramp connecting more than two (2) stories designating the
floor level, the terminus of the top and bottom of the interior exit stairway and ramp and
the identification of the stair or ramp. The signage shall also state the story of, and the
direction to, the exit discharge and the availability of roof access from the interior exit
stairway and ramp for the Fire Department. The sign shall be located five (5) feet above
the floor landing in a position that is readily visible when the doors are in the open and
closed positions. In addition to the stairway identification sign, a floor -level sign in raised
characters and Braille complying with ICC A117.1 shall be located at each floor -level
landing adjacent to the door leading from the interior exit stairway and ramp into the
corridor to identify the floor level.
1101.2.1 Rehabilitation Work Area: That portion of a building affected by any
renovation, modification, or reconstruction work as initially intended by the owner, and
indicated as such in the permit, but excluding other portions of the building where
incidental work entailed by the intended work must be performed, and excluding
portions of the building where work not initially intended by the owner is specifically
required.
1103.1.2 Rehabilitation Work Area: In a building with rehabilitation work areas
involving over 50 percent of the aggregate building area, automatic sprinkler and
detection, alarm, and communications systems shall be provided throughout the
building with the requirements of other sections of this Code applicable to new
construction for the occupancy. Exception: One- and Two -Family Dwellings.
1103.1.3 Change of Occupancy: Where a change of occupancy classification occurs,
automatic sprinkler and detection, alarm, and communications systems shall be
provided throughout the building with the requirements of other sections of this Code
applicable to new construction for the occupancy created by the change.
In a change of occupancy where the fire area is less than 5,000 square feet, a fire alarm
signaling system in accordance with NFPA 72 remote or central supervision station will
be required.
In a change of occupancy where the fire area is 5,000 or greater, an automatic sprinkler
system and detection alarm will be required.
1103.7.5.2 Group R-1 boarding and rooming houses manual fire alarm system. A
manual fire alarm system that activates the occupant notification system in accordance
Title 4, Chapter 4, Fire Prevention Regulations
C6
Page 37 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
with Section 907.6 shall be installed in existing Group R-1 boarding and rooming
houses.
Exception: Buildings less than two (2) stories in height where all sleeping units, attics,
and crawl spaces are separated by one (1)-hour fire -resistance -rated construction and
each sleeping unit has direct access to a public way, egress court or yard. Buildings
equipped with an approved automatic sprinkler system that is monitored in accordance
with Section 903.4.1.
5601.1.3: Fireworks and Explosives: The possession, manufacture, storage, sale,
handling and use of fireworks and explosives are prohibited except as approved by the
Fire Official.
5602.1: The following terms are defined in Chapter 2:
5602.1: Fireworks: Fireworks include any combustible or explosive composition, and
any substance and combination of substances and articles prepared for the purpose of
producing a visible or an audible effect by combustion, explosion, deflagration or
detonation. Fireworks shall include blank cartridges, toy pistols, toy cannons, toy canes
and toy guns in which explosives are utilized; balloons requiring fire underneath to
propel the balloon; firecrackers, torpedoes, skyrockets, Roman candles, sparklers and
other devices of similar construction; any device containing any explosive or flammable
compound; and any tablets and other devices containing any explosive substance.
The term "fireworks" shall not include automobile flares or paper caps containing not
more than an average of 0.25 grain (16 mg) of explosive content per cap, and toy
pistols, toy canes, toy guns, and other devices utilizing such caps. The sale and
utilization of types of explosive devices listed herein which are not considered fireworks
shall be permitted at all times.
5608.2 Permit application. Prior to issuing permits for a fireworks display, plans for the
display, inspections of the display site, and demonstrations of the display operations
shall be approved. All requests for permits must be made at least fifteen (15) days in
advance of the event unless otherwise approved by the Fire Official. A plan establishing
procedures to follow and actions to be taken in the event that a shell fails to ignite in, or
discharge from, a mortar so fails to function over the fallout area or other malfunctions
shall be provided to the Fire Official.
4-4-3. AUTOMATIC SPRINKLER SYSTEMS.
Automatic sprinkler systems shall be installed as required by this Section, which is
hereby in addition to Section 903 of the International Fire Code.
(A) Definitions. -
AUTOMATIC An engineered system to automatically detect and contain or
SPRINKLER suppress a fire through fixed piping and nozzles. The system
SYSTEMS: shall be designed in accordance with the fire protection system
requirements of the 2021 International Building Code, 2021
International Fire Code and referenced NFPA standards as
Title 4, Chapter 4, Fire Prevention Regulations
C7
Page 38 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
adopted by the City, and good fire protection practices. The City
must approve in writing all systems prior to their installation.
DORMITORIES:
A space in a structure associated with or serving an educational
institution, the primary use of which is group sleeping
accommodations provided in one room, or in a series of closely
associated rooms, for persons not members of the same family
group including structures used for dormitories, sororities,
fraternities and similar uses, but excluding rooming and lodging
houses.
FULLY
A sprinkler system that provides protection to the entire
SPRINKLERED:
structure.
HOSPITAL:
A structure under the 1-2 use group as defined by the 2021
International Fire Code.
IBC:
2021 International Building Code, as adopted by the City.
ICC.
International Code Council (which publishes the adopted
International Building and Fire Codes).
IFC:
2021 International Fire Code, as adopted by the City.
NFPA:
National Fire Protection Association edition as adopted by the
City.
NFPA 13.
National Fire Protection Association standard 13. Provides the
minimum requirements for the design and installation of
automatic fire sprinkler systems.
NONOWNER
A rooming/lodging house which the owner of the property does
OCCUPIED
not occupy as his/her primary residence.
ROOMING/LODGING
HOUSE:
NURSING HOME
Any facility that is licensed or subject to licensure under Title 8,
FACILITY.
Chapter 12 of this Code regulating long term care facilities or
under similar provisions in Illinois law.
RETROFIT:
To install in, within, or on an existing structure.
ROOMING/LODGING
Any facility that is licensed or subject to licensure under Title 5,
HOUSE:
Chapter 2 of this Code regulating lodging establishments.
STRUCTURE:
That which is built or constructed.
(B) Systems Provided In Structures: Automatic sprinkler systems shall be provided
in the following structures:
Dormitories
Hospitals
Non -owner occupied rooming/lodging houses
Nursing homes
(C) System Requirements: Any structure required to be retrofitted with a sprinkler
system under this Chapter shall have such a system designed and installed in
Title 4, Chapter 4, Fire Prevention Regulations
M:
Page 39 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
accordance with the fire protection system requirements of the 2021 International
Building Code, 2021 International Fire Code and referenced NFPA standards as
adopted by this Code.
(D) Penalties: Failure to comply with the installation provisions of this Section and any
extensions thereof approved in writing by the Fire Chief or his/her designee shall
subject the violator to a penalty of $500.00 per month. The City may, in addition to
monetary penalties, avail itself of any legal or equitable remedy provided for by law.
Occupancies for which a City license is required are not eligible to obtain or retain said
license if they fail to comply with this Section, subject to any extension approved in
writing by the Fire Chief or his/her designee.
4-4-4. SIGNAL BOOSTING.
(A) Emergency Responder Radio Coverage in Buildings: All buildings shall have
approved radio coverage for emergency responders within the building, based
upon the existing coverage levels of the public safety communication systems of
the City of Evanston at the exterior of the building. This Section shall not require
improvement of the existing public safety communication system. Existing buildings
that do not have approved radio coverage for emergency responders within the
building shall be equipped with such coverage according to one of the following:
1. Wherever existing wired communication system cannot be repaired or is being
replaced.
2. Within a time frame established by the Fire Official
(B) Radio Signal Strength: A building shall be considered to have acceptable
emergency responder radio coverage when signal strength measurements in
ninety-five percent (95%) of all areas on each floor of the building meet the
following requirements-
1 . A minimum signal strength of -95 dBm.
2. A minimum signal strength of -100 dBm received at the closest City of
Evanston Radio Communications site.
3. The frequency range which must be supported shall be 151-159 MHz and 450-
476 MHz.
4. Starcom 21 frequencies. They have control channels between the 850-860
MHz ranges.
When measuring the performance of a bi-directional amplifier, signal strength
measurements shall be based on one (1) input signal adequate to obtain a maximum
continuous operating output level.
(C) Amplification Systems Allowed: Buildings and structures that do not support the
required level of radio coverage shall be equipped with either a radiating cable
system or an internal multiple antenna system, with or without FCC type accepted
bi-directional required MHz amplifiers, as needed. If any part of the installed system
Title 4, Chapter 4, Fire Prevention Regulations
W
Page 40 of 99
Doc ID: 89d95372ca2la88d7c7e45de8e6b363662felfl5
Ordinance 29-0-22, Exhibit C
or systems contains an electrically -powered component, the system shall be
capable of operating on an independent battery and/or generator system for a
period of at least twelve (12) hours without external power input. The battery
system shall automatically charge in the presence of an external power input. If
used, bi-directional amplifiers shall include filters to reduce adjacent frequency
interference to at least 35 dB below the COE P/S band. The filters shall be tuned to
154 MHz and to 470 MHz so that they will be 35 dB below the COE P/S
frequencies of 154 MHz and 470 MHz respectively. Other settings may be used
provided they do not attenuate the COE- P/S frequencies and are not more than
one (1) MHz from the COE-P/S frequencies.
(D) Testing Procedures:
1. Acceptance Test Procedure: When an in -building radio system is required, and
upon completion of installation, it shall be the building owner's responsibility to
have the radio system tested to ensure that two-way coverage on each floor of
the building is a minimum of ninety-five percent (95%). Each floor of the
building shall be divided into a grid of approximately twenty (20) equal areas.
No more than one (1) such area shall be allowed to fail the test. In the event
that two (2) or more of the areas fail the test, in order to be more statistically
accurate, the floor may be divided into forty (40) equal areas. In such event, no
more than two (2) nonadjacent areas will be allowed to fail the test. If, after the
forty (40)-area test, the system continues to fail, the building owner shall have
the system altered to meet the ninety-five percent (95%) coverage
requirement. The test shall be conducted using a Motorola HT1250, or
equivalent, portable radio, talking through the City of Evanston Radio
Communications System (COE-911) as specified by the authority having
jurisdiction. A spot located approximately in the center of a grid area shall be
selected for the test, then the radio shall be keyed to verify two-way
communications to and from the outside of the building through the City of
Evanston 911 center. Once the spot has been selected, prospecting for a
better spot within the grid area shall not be permitted.
The building owner shall keep the gain values of all amplifiers and the test
measurement results on file so that the measurements may be verified each year
during annual tests. In the event that the measurement results are lost, the building
owner shall repeat the acceptance test to reestablish the gain values.
2. Annual Tests: When an in -building radio system is required, the building
owner shall test, at once every twelve (12) months, all active components of
the system, including, but not limited to, amplifiers, power supplies and backup
batteries. Amplifiers shall be tested to ensure that the gain is the same as it
was upon initial installation and acceptance. Backup batteries and power
supplies shall be tested under load for a period of one (1) hour to verify that,
they will properly operate during an actual power outage. If, within the one (1)
hour test period, the battery exhibits symptoms of failure in the opinion of the
testing technician, the test shall be extended for additional one (1) hour periods
until the testing technician confirms the integrity of the battery. All other active
Title 4, Chapter 4, Fire Prevention Regulations
C10
Page 41 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
components shall be checked to determine that they are operating within the
manufacturer's specifications for the intended purpose.
3. Five Year Tests: In addition to the annual test, the building owner shall
perform a radio coverage test at least once every five (5) years to ensure that
the radio system continues to meet the requirements of the original acceptance
test. The procedure set forth above shall apply to such tests.
4. Qualifications of Testing Personnel: All tests shall be conducted,
documented and signed by a person in possession of a current FCC license, or
a current technician certification issued by the Associated Public -Safety
Communications Officials International (APCO) or the Personal
Communications Industry Association (PCIA). All test records shall be retained
on the inspected premises by the building owner and a copy submitted to the
Fire Official.
(E) Field Testing: Police and fire personnel, after providing reasonable notice to the
owner or his representative, shall have the right to enter onto the property to
conduct field testing to be certain that the required level of radio coverage is
present.
(F) Maintenance: The public radio coverage system shall be maintained operational at
all times.
4-4-5. PENALTIES.
Except for the penalties specifically relating to automatic sprinkler installation set
forth in Section 3 of this Chapter, any person found to have violated any provision of the
2021 International Fire Code or the 2021 National Fire Protection Association 101, Life
Safety Code as adopted by the City, or who shall fail to comply with any of the
requirements thereof, or who shall erect, construct, alter or repair a building or structure
in violation of any approved plan or direction of the Fire Official or of any permit or
certificate issued by the Fire Official or his/her designee, shall be guilty of an offense,
punishable as follows:
(A) 1. The fine for a first violation is one hundred fifty dollars ($150.00).
2. The fine for a second violation is four hundred dollars ($400.00).
3. The fine for a third or subsequent violation is seven hundred fifty dollars
($750.00).
(B) Each day a provision of this Chapter is found to have been violated constitutes
a separate violation subject to the fine schedule set forth in Subsection (A) of
this Section.
(C) The fines provided for herein shall not be construed as limiting the power of a
court of competent jurisdiction or an administrative hearing officer to impose
other penalties and remedies as provided for by applicable legislation.
Title 4, Chapter 4, Fire Prevention Regulations
C11
Page 42 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit C
4-4-6. SEVERABILITY.
It is the intention of the City Council that the provisions of this Chapter and the Code
adopted hereby are severable and the invalidity of any Section or any portion of any
such Section of either of them shall not affect any other Section.
4-4-7. — IDENTIFICATION OF ORDINANCE WITH THE ILLINOIS CAPITAL BOARD.
The adoption of this Ordinance and code, by title and edition, shall be reported to the
Illinois Capital Development Board Illinois or any successor agency of the State of
Illinois pursuant to Section 1-2-3.1 of the Illinois Municipal Code, 651LCS 5/1-2-3.1.
4-4-8. — EFFECTIVE DATE.
This Ordinance shall be in full force and effect thirty (30) days after its approval and
passage.
Title 4, Chapter 4, Fire Prevention Regulations
C12
Page 43 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit D
CHAPTER 5 PLUMBING CODE
4-5-1. ADOPTION.
(A) Pursuant to the authority granted by 65 ILCS 5/1-2-4, and pursuant to its home rule
powers, the City of Evanston hereby adopts by reference the 2014 Illinois Plumbing
Code, III. Admin. Code tit. 77 § 890 (2014), with the additions, deletions,
exceptions, and other amendments set forth in this Chapter.
(B) Any reference in the 2014 Illinois Plumbing Code to "Authorities Having
Jurisdiction" shall refer to the City's Manager of Building and Inspection Services.
Any reference to "municipality" shall mean the City of Evanston.
4-5-2. AMENDMENTS.
The 2014 Illinois Plumbing Code adopted hereby shall read as follows with respect
to these Sections.
Subsection 890.340(f):
f) Copper Water Tube. Joints in copper tubing shall be made with case bronze or
wrought copper pressure fittings, properly soldered or brazed, or by means of
compression or flared joints as provided in Sections 890.320(d), (e), (h) and
(p)(2). Flared joints and compression fittings shall not be installed underground
except for water services, water meter yokes, and stop box connections.
Soldered and braised fittings shall not be installed below grade.
Section 890.610 General Requirements —Material and Design:
a) Quality of Fixtures: Plumbing fixtures shall comply with approved designs, be
constructed from approved materials, have smooth, impervious surfaces and
be free of defects and concealed fouling surfaces. (See Appendix A: table A
"Approved Materials and Standards for Plumbing Fixtures" and "Approved
Standards for Plumbing Appliances/Appurtenances/Devices.")
b) Used plumbing material, equipment and fixtures for plumbing installations shall
comply with this Part.
c) Any plumbing equipment condemned by the Department because of wear,
damage, defects or sanitary hazards shall not be used in a plumbing system.
d) All new and replacement plumbing fixtures and irrigation controllers installed
after the effective date of this ordinance shall bear the Watersense label as
designated by the U.S. Environmental Protection Agency Watersense Program
when such labeled fixtures are available.
Section 890.680 Lavatories:
a) Waste Outlets. Wastes shall have a strainer or stopper and have a waste outlet
at least 1'/4 inches in diameter.
b) Lavatory Faucets. All lavatory faucets shall have air gaps as specified in
Appendix A, table C.
D1
Title 4, Chapter 5, Plumbing Code
Page 44 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit D
c) When metering faucets are located on lavatories in public restrooms, they shall
be adjusted to remain open for a minimum of 10 seconds and shall comply with
the water consumption requirements of ASME/ANSI 112.18.1. Metering
faucets shall be designed for hot and cold, tempered and cold, or tempered
water only.
d) Fixture Calculation. Eighteen lineal inches of wash sink or 18 inches of a
circular basin, when provided with water outlets for the space, shall be
considered equivalent to one lavatory. (See Appendix F, Illustration B.)
e) Water Temperature. All lavatory faucets for public use shall be provided with
an automatic safety water mixing device to prevent sudden unanticipated
changes in water temperature or excessive water temperatures. The automatic
safety water mixing device shall comply with ASSE 1070 or 1017 in
accordance with Section 890.210, and shall be adjusted to a maximum setting
of 110 degrees Fahrenheit, at the time of installation. Exception: Units
constructed in accordance with Section 890.1220(a)(9)(B) may be used in lieu
of an automatic safety water mixing device to provide hot or tempered water to
public lavatories.
f) All lavatories for public use in new construction or remodeling shall be
equipped with metering or self -closing faucets.
Subsection 890.810(a)(2)(C):
C) Restroom Location, Designation, and Requirements. The required number of
plumbing fixtures for a restroom shall be located within the restroom area and
not in the hallways or vestibule. Lavatories required by Appendix A: Table B
shall be installed in restrooms at a ratio of not less than one lavatory per two
water closets or urinals. (See Footnote 2, Appendix A: Table B.) All restroom
facilities must comply with designation requirements set forth in Section 2902.2
of the 2021 International Building Code, adopted by City Code Section 4-2-2 of
the City of Evanston.
Subsection 890.1130(g):
g) Installation of Devices or Assemblies
1) Devices of All Types. Backflow preventer assemblies and devices shall be
installed to be accessible for observation, maintenance and replacement
services. Backflow preventer devices or assemblies shall not be installed
where they would be subject to freezing conditions, except as allowed in
Section 890.1140(d).
2) All in -line backflow/back siphonage preventer assemblies shall have a full
port type valve with a resilient seated shut-off valve on each side of the
preventer. Relocation of the valves is not permitted.
3) A protective strainer shall be located upstream of the first check valve on
all backflow/back siphonage preventers unless the device contains a built-
in strainer. Fire safety systems are exempt from the strainer requirement.
Title 4, Chapter 5, Plumbing Code
V
Page 45 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit D
4) Atmospheric vacuum breakers shall be installed with the critical level
above the flooded level rim of the fixture they serve, and on the discharge
side of the last control valve of the fixture. No shut-off valve or faucet shall
be installed beyond the vacuum breaker.
5) No in -line double check valve backflow preventer assembly (DCV) or
reduced pressure principled backflow preventer assembly (RPZ) shall be
located more than 5 feet above a floor, or be installed where it [is] subject
to freezing or flooding conditions. After installation, each DCV and RPZ
shall be field tested in -line in accordance with the manufacturer's
instructions by a cross -connection control device inspector before initial
operation. (See subsection (b)).
6) A dual check backflow preventer with atmospheric vent assembly shall not
be installed where it is subject to freezing or flooding conditions.
7) Closed water systems with hot water storage shall have a properly sized
thermal expansion tank located in the cold water supply as near to the
water heater as possible and with no shut-off valve or other device
between the heater and the expansion tank. Exception: In existing
buildings with a closed water system, a properly sized pressure relief valve
may be substitute in place of a thermal expansion tank. For closed water
systems created by backflow protection in manufactured housing, as
required in Section 890.1140(i), a ballcock with a relief valve may be
substituted for the thermal expansion tank.
8) A backflow prevention device shall be installed on each water service
pipe/line to a business, commercial, or industrial facility in accordance with
the Illinois Plumbing Code. This requirement applies whenever there is an
installation of a water service pipe/line, or alteration, renovation, or
replacement of an existing pipe/line, and for new construction. A reduced
pressure principle backflow, prevention assembly (RPZ) shall be installed
in the water service supplying food service, manufacturing, or production
establishments.
Subsection 890.1150(a)(3):
a) 3) The minimum depth for any water service pipe shall be at least 60" deep or
the maximum frost penetration of the local area, whichever is greater.
Subsection 890.1190(b):
b) The water meter shall be installed within the building within 60" of the water
service entrance. The meter shall have unions on the inlet and outlet openings.
A full -port valve with an open area at least that of the water service shall be
provided for all meters and shall be provided with a drain valve installed on the
discharge side of the meter valve when located inside of a building. (See
Appendix I, Illustrations H and I.)
Subsection 890.1200(a):
Title 4, Chapter 5, Plumbing Code
D3
Page 46 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit D
a) Water Service Piping Sizing. The water service pipe from the street main
(including the tap) to the water distribution system for the building shall be
sized in accordance with Appendix A, Tables M, N, O, P, and Q. Water service
pipe and fittings shall be at least one inch in diameter. If flushometers or other
devices requiring a high rate of water flow are used, the water service pipe
shall be designed and installed to provide this additional flow.
890 Appendix A, Table A
Approved Materials for Building Sewer
1) Cast Iron Soil Pipe/Fittings ASTM A 74-2009
CSA B70-2012
Rubber Gaskets ASTM C 564-2012
ASTM D 4161-2010
CSA B70-2012
CSA B602-2010
2) High -Density Polyethylene (HDPE) Pipe ASTM D 3350-2010
3) Polyvinyl Chloride (PVC) Pipe
ASTM F 1866-2007
ASTM D 2665-2012
ASTM D 2949-2010
CSA B 182.1-2011 in 81800
CSA 13182.2-2011 in 81800
CSA B182.4-2011 in 81800
CSA B181.2-2011 in 81800
ASTM D 2855-2010
ASTM D 3212-2013
CSA B602-2010
ASTM F 656-2010
ASTM D 2564-2012
ASTM D 3138-2011
CSA B181.2-2011 in B1800
4) Polypropylene Pipet ASTM 2389-2010
AWWA C901-2008
AWWA C906-2012
(Material Code PE3408)3
(Material Codes PE2406 and PE3406)4
5) Identification of Piping Systems
ASME A13.1-2007
Agency Notes:
1 Solvent cement must be handled in accordance with STM F 402-1988.
2 PVC pipe with cellular core and vitrified clay pipe are approved only for gravity
drainage.
Title 4, Chapter 5, Plumbing Code
D4
Page 47 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit D
3 Dimension Ratio (DR) 17 or less.
4 Dimension Ratio (DR) 13.5 or less.
Approved Materials for Water Service Pipe
1) Cast Iron (ductile iron)2 ASTM A 377-2008e1
Water Pipe CSA B70-2012
2) Copper/Copper Alloy Tubing2,3 ASTM B 88-2009
3) Polyethylene (PE) Pipet,' ASTM D 2239-2012a
AWWA C901-2008
AWWA C906-2012
(Material Code PE3408)4
Material Codes PE2406, PE3406)
Agency Notes:
1 Solvent cement must be handled in accordance with ASTM F 402-1988.
2 Water service pipe must meet the appropriate NSF standard for potable water.
3 Minimum Type K copper shall be installed underground.
4 Dimension Ratio (DR) 17 or less.
5 Dimension Ratio (DR) 13.5 or less.
6 ASME B.1.20.1-1983
Up to a developed distance of twenty-four (24) inches to be used only in the transition
between similar types of service pipe.
Approved Materials for Water Distribution Pipe
1) Brass Pipe2,6 ASTM B 43-2009
2) Copper/Copper Alloy Pipet ASTM B 42-2010
ASTM B 302-2012
3) Galvanized Steel Pipet,' ASTM A 53-2012
AWWA C606-2011
Agency Notes-
1 Solvent cement must be handled in accordance with ASTM F 402-1988.
2 Water distribution pipe must meet the appropriate NSF standard for potable water,
minimum Type L copper shall be installed above grade.
3 Use for cold or tempered water only.
4 ASME B.1.20.1-1983
5 Safety color.
6 For repairs only.
For repairs only, except for the distribution and conveyance of distilled or deionized
water.
D5
Title 4, Chapter 5, Plumbing Code
Page 48 of 99 Doc ID: 89d95372ca2la88d7c7e45de8e6b363662felfl5
Ordinance 29-0-22, Exhibit D
4-5-3. ADDITIONAL REQUIREMENTS.
The following are requirements additional to the 2014 Illinois Plumbing Code. In the
event that any provision of City Code Section 4-5-3 is in conflict with the 2014 Illinois
Plumbing Code, as amended, the 2014 Illinois Plumbing Code shall prevail.
(A) Existing Plumbing: Plumbing fixtures not maintained shall be disconnected,
removed, and sealed.
(B) Safety: Any part of a structure or premises which is changed, altered, or for
which replacement is required as a result of the installation, alteration,
renovation, or replacement of a plumbing system, or any part thereof, shall be
left in a safe, nonhazardous condition. All penetrations through fire rated
construction shall be fire stopped with a through penetration protection system
approved by the Building Official.
(C) Installation: All plumbing installed within the City of Evanston shall be installed
in accordance with the 2014 Illinois Plumbing Code. If required by the Code
Official, an approved backflow prevention device is necessary for the safety of
the public water supply system, the Public Works Agency Director or his/her
designee will give notice to the property owner or person in charge (collectively,
"property owner") of the building structure or premises to install such an
approved device immediately. The property owner shall, at his/her own
expense, immediately install such an approved device at a location and in a
manner in accordance with the 2014 Illinois Plumbing Code; Illinois
Environmental Agency Rules and Regulations, Title 35: Environmental
Protection, Subtitle F: Public Water Supply, Chapter I: Pollution Control Board,
Part 604 Subpart O: Cross Connections and Chapter II: Environmental
Protection Agency, Part 653 subpart H Cross Connections; and all applicable
local regulations, and shall have inspections and tests made of such approved
devices upon installation and annually thereafter, at a minimum. The property
owner shall maintain records to document that testing, servicing, and repairs
are conducted as required.
(D) Right of Entry. A City inspector, who shall be a licensed plumber, shall have
the right to enter at any reasonable time any property served by a connection to
the public water supply or distribution system of the City for the purpose of
verifying information submitted by the property owner or person in charge of the
building, structure, or premises regarding the required cross connection control
inspection. On demand, the property owner or person in charge of the building,
structure, or premises so served shall furnish to the Code Official, his/her
authorized agent, or approved cross connection control device inspector any
information which these individuals may request regarding the piping system or
systems or water use on such property. The Code Official or his/her authorized
agents shall have a right to enter at any reasonable time any property served by
a connection to the public water supply or distribution system of the City for the
purpose of verifying information submitted by the property owner or person in
Title 4, Chapter 5, Plumbing Code
Page 49 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit D
charge of the building, structure, or premises regarding the required cross
connection inspection.
(E) Contamination: The occupant or property owner of the building, structure, or
premises responsible for back siphoned material or contamination of the
potable water supply system which occurs through an illegal cross connection
or an improperly installed, maintained, or repaired device, or a device which has
been bypassed, must bear the cost of cleanup of the potable water supply
system. Said costs to include, but not be limited to, overhead and administrative
costs of the City and any other costs reasonably incurred by the City in the
cleanup.
(F) Discharge to Sanitary Drainage System: Every plumbing fixture, drain,
appliance, or appurtenance thereof which is to receive water or waste, or
discharge any liquid wastes or sewage, shall discharge to the sanitary drainage
system of the structure in accordance with the requirements of this Chapter.
Building Drains shall be constructed of either service weight cast iron or
schedule 40 PVC pipe and fittings or a material approved by the city Plumbing
Inspector. Building Sewers shall be constructed of either service weight cast-
iron, schedule 40 PVC pipe and fittings, SDR 26 or SDR 35 or a material
approved by the city Plumbing Inspector. Underground piping shall be laid on a
firm bed of sand or gravel for its entire length, except where support is
otherwise provided and approved by a City Plumbing Inspector. Six (6) inches
of compacted stone, sand, or other approved material shall be provided under
pipe and minimum of twelve (12) inches of stone or sand shall be provided
above the crown of the pipe. The remaining soil fill shall be compacted in
compliance with Metropolitan Water Reclamation District bedding regulations.
(G) Automatic Clothes Washing Machine/Water Heater Floor Drains: For all new
construction, a pan or receptor with a drain to an approved floor drain, or an
impervious floor with a floor drain, shall be required for all automatic clothes
washing machines and water heaters in multi -family and commercial
occupancies. For existing multi -family and commercial buildings, a pan and
automatic shut-off valve shall be required for all automatic clothes washing
machines and water heaters where installation of a floor drain is not feasible.
(H) Underground Piping. Piping installed in underground plumbing systems shall
be protected from structural damage by an approved method of installation
which accounts for the conditions of the installation and application and the type
of piping material. In new construction, all plumbing shall be overhead. All
fixtures below grade shall be directed to an ejector pit and lifted to an overhead
system. Footings, grade beams and/or foundation walls shall be properly
sleeved or cored in compliance with a design from a licensed design
professional to accommodate for the proper installation of the buildings
plumbing system.
(1) Sillcocks: All buildings have a minimum of two (2) frost -proof, anti -siphon type
sillcocks.
Title 4, Chapter 5, Plumbing Code
D7
Page 50 of 99
Doc ID: 89d95372ca2la88d7c7e45de8e6b363662felfl5
Ordinance 29-0-22, Exhibit D
(J) Public Toilet Room Drains: All public toilet rooms, including employee
facilities, shall be graded into floor drains.
(K) Unmaintained Plumbing Fixtures. All plumbing fixtures not maintained shall be
disconnected, removed, and sealed.
(L) Sewer Depth. Building sewers shall be installed below frost line depth per IRC
Table R301.2(1). Current frost line depth is forty-two inches (42").
(M) Subsoil Drain Pipe: Subsoil drains shall be open jointed, horizontally split or
perforated pipe. Footing drains to be connected to the sump pump as discharge
shall terminate water discharge to grade a minimum of three feet (3') away from
any portion of the structure and not within ten feet (10') of any property line or
as approved by the Civil Reviewer. Water discharge shall not be directed
toward adjacent properties or discharge in a manner that will disturb adjacent
properties. Discharge to storm or combination sewer will be upon approval the
Public Works Director, Civil Engineer Reviewer or his/her designee. Discharge
to sanitary sewer shall not be allowed. All windows wells require drains. The
drains shall be connected to drain tile and drain into the sump.
(N) Roof Drains. Roof drains shall conform to ASME Al 12.21.2. Buildings in R1,
R2 and R3 zoning districts, and all one- and two-family dwelling units shall drain
roof stormwater by gutters and downspouts to the front and rear of the property,
Water discharge shall terminate to grade a minimum of three feet (Y) away
from any portion of the structure and not within ten feet (10') of any property line
or as approved by the Civil Reviewer. Water discharge shall not be directed
toward adjacent properties or discharge in a manner that will disturb adjacent
properties. No connections to the combined or sanitary sewer shall be made in
the above zoning districts. All roofs of buildings not mentioned above may drain
directly in the storm sewer system.
(0) Car Wash Facilities. Unless designed to use thirty (30) gallons or less of
water per wash, new car wash facilities or replacement of existing facilities shall
be equipped with water recycling systems.
(P) Reduced Pressure Principle Backflow Preventers: A reduced pressure
principle backflow prevention assembly (RPZ) shall be installed in the water
service supplying food service, manufacturing or production establishments.
RPZs shall conform to ASSE 1013, 1047 AWWA C511 or CSA CAN/CSA-
B64.4. These devices shall be allowed where subject to continuous pressure
conditions. The relief opening shall discharge by air gap and shall be prevented
from being submerged.
4-5-4. PENALTIES.
Any persons who violates any provision of this Chapter or fails to comply with any of the
requirements thereof, or erects, installs, alters, or repairs work in violation of the
approved construction documents or directives of the Code Official, or of a permit or
certificate issued under the provisions of this Chapter, shall be fined as set forth in this
Section:
Title 4, Chapter 5, Plumbing Code
M:
Page 51 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit D
(A) 1. The fine for a first violation is one hundred fifty dollars ($150.00).
2. The fine for a second violation is four hundred dollars ($400.00).
3. The fine for a third or subsequent violation is seven hundred fifty dollars
($750.00).
(B) Each day a provision of this Chapter is found to have been violated constitutes
a separate violation subject to the fine schedule set forth in Subsection (A) of
this Section.
(C) The fines provided for herein shall not be construed as limiting the power of a
court of competent jurisdiction or an administrative hearing officer to impose
other penalties and remedies as provided for by applicable legislation.
4-5-5. SEVERABILITY.
It is the intention of the City Council that the provisions of this Chapter and the Code
adopted hereby are severable and the invalidity of any Section or any portion of any
such Section of either of them shall not affect any other Section.
4-5-6. IDENTIFICATION OF ORDINANCE WITH THE ILLINOIS CAPITAL BOARD.
The adoption of this Ordinance and code, by title and edition, shall be reported to the
Illinois Capital Development Board Illinois or any successor agency of the State of
Illinois pursuant to Section 1-2-3.1 of the Illinois Municipal Code, 651LCS 5/1-2-3.1.
4-5-7. EFFECTIVE DATE.
This Ordinance shall be in full force and effect thirty (30) days after its approval and
passage.
Title 4, Chapter 5, Plumbing Code
Page 52 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit E
CHAPTER 6 ELECTRICAL CODE
4-6-1. ADOPTION.
(A) Pursuant to the authority granted by 65 ILCS 5/1-2-4, and pursuant to its home rule
powers, the City of Evanston hereby adopts by reference the 2020 National
Electrical Code, with the additions, deletions, exceptions, and other amendments
set forth in this Chapter. All advisory or text notes, other than the rules and
regulations contained in the 2020 National Electrical Code adopted hereby, are
expressly excluded from this Chapter.
(B) Any reference in the 2020 National Electrical Code to "Administrative Authority,"
"Building Official" or "Code Official" shall refer to the City's Manager of Building and
Inspection Services Division. Any reference to "municipality" shall mean the City of
Evanston.
(C) In the event that any provision of the 2020 National Electrical Code adopted hereby
is in conflict with any provision(s) of the City Code, the more/most stringent shall
control.
(D) There shall be a copy of the 2020 National Electrical Code kept on file for public
inspection in the City Clerk's office.
4-6-2. Application of Regulations.
The regulations of said 2020 National Electrical Code shall apply to all matters
concerning the construction, reconstruction, alteration, or installation of all electrical
wiring apparatus, fixtures, machinery, or devices, and their service equipment, and shall
apply to all existing or proposed buildings and structures in the City.
4-6-3. AMENDMENTS.
The 2020 National Electrical Code adopted hereby shall read as follows with
respect to the indicated Sections.
Article 210.8 (A)(5), Ground -Fault Circuit -Interrupter Protection for Personnel
Exception to (5): Add sump pumps and ejector pumps
Article 210.11(3) Bathroom Branch Circuits: Delete the Exception.
Article 210.12 Arc -Fault Circuit -Interrupter Protection. (Revised to read as follows)
Arc- fault circuit -interrupter protection shall be provided as required in 210.12(A), (B),
(C) and (D). The arc -fault circuit interrupter shall be installed in a readily accessible
location.
(A) Dwelling Units. All 120-volt, single phase, 15- and 20-ampere branch circuits
supplying outlets and devices installed in dwelling units shall be protected by a listed
arc -fault circuit interrupter, combination -type, installed to provide protection of the
branch circuit.
Title 4, Chapter 6, Electrical Code
E1
Page 53 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit E
(B) Dormitory Units. All 120-volt, single phase, 15- and 20-ampere branch circuits
supplying outlets and devices installed in dormitory units shall be protected as
described in 210.12(A).
(C) Guest Rooms, Guest Suites and Patient Sleeping Rooms in Nursing Homes
and Limited -Care Facilities. All 120-volt, single-phase, 15- and 20-ampere branch
circuits supplying outlets and devices installed in guest suites, guest rooms of hotels
and motels and patient sleeping rooms in nursing homes and limited -care facilities shall
be protected as described in 210.12(A).
(D) Branch Circuit Extensions or Modifications — Dwelling Units, Dormitory
Units, and Guest Rooms and Guest Suites. In any of the areas specified in
210.12(A), (B) or (C), where branch- circuit wiring is modified, replaced or extended, the
branch -circuit shall be protected by one of the following:
(1) A listed combination -type AFCI located at the origin or the branch circuit.
(2) A listed outlet branch -circuit type AFCI located at the first outlet of the existing
branch circuit.
Exception No. 1 to 210.12(A), (B), and (C): It shall be permitted to omit AFCI
protection for that portion of the branch circuit enclosed in rigid metal conduit (RMC),
flexible metal conduit (FMC), intermediate metal conduit (IMC), electrical metal tubing
(EMT), or Type MI cable sheath meeting the requirements of 250.118 along with metal
outlet and junction boxes.
Exception No. 2 to 210.12(D): It shall be permitted to omit AFCI protection for that
portion of the branch circuit installed in rigid metal conduit (RMC), flexible metal conduit
(FMC), intermediate metal conduit (IMC), electrical metal tubing (EMT), or steel
sheathed cable, Type AC, Type MC, or Type MI cable sheath, meeting the
requirements of 250.118, with metal outlet and junction boxes.
Exception No. 3 to 210.12(A), (B), (C) and (D): Where an individual branch circuit to
a fire alarm system is installed in accordance with 760.41(B) or 760.121(B) is installed
in rigid metal conduit (RMC), intermediate metal conduit (IMC), electrical metal tubing
(EMT), or Type MI Cable sheath meeting the requirements of 250.118, with metal outlet
and junction boxes, AFCI protection shall be permitted to be omitted.
Informational Note No. 1: For information on types of arc -fault circuit interrupters,
see UL 1699, Standard for Arc -Fault Circuit Interrupters.
Informational Note No. 2: See 11.6.3(5) of NFPA 72, National Fire Alarm and
Signaling Code, f
Article 210-70 Lighting Outlets Required (A)(2): (Add the following)
(4) All exterior lighting shall be designed, shielded and directed so that direct light
from the lamp does not cause light trespass and protects adjacent properties and
public ways from glare and excessive lighting. Light level at any property line is
limited to one-half (0.5) foot-candle unless otherwise regulated by city code.
E2
Title 4, Chapter 6, Electrical Code
Page 54 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit E
Exception:
1. Security lighting: Exterior lighting installed primarily for safety or
emergency shall be permitted provided that said lighting is solely for
security and activated by a motion or a controlled system and shall be
extinguished within 5 minutes of cessation of actual or perceived
emergency.
2. Holiday lighting: Subject to NFPA 70 National Electric Code
regulations as adopted and amended by the City of Evanston.
Article 230 Services: Add the following: "The maximum number of branch circuits
allowed for a 100-amp, 120/240 volt, single phase service is thirty (30). The maximum
number of branch circuits allowed for a 200-amp, 120/240 volt, single phase service is
sixty (60)."
Article 230 Services: Add the following: "No additional fuse or breaker boxes shall be
installed without the prior written approval of the city's Electrical Inspector."
Article 250.62: Grounding Electrode Conductor Material: Delete the words
"Aluminum" and "Copper Clad Aluminum."
Article 334 Nonmetallic Sheathed Cable: Types NM, NMC, and NMS: Delete.
Article 338 Service Entrance Cable: Types SE and USE: Delete.
Article 352 Polyvinyl Chloride Conduit: Type PVC 352.12(A) Concealed: PVC
conduit shall only be concealed in the following manner: direct buried below grade, in
slab below grade, in slab at and above grade. PVC conduit stub ups where subject to
physical damage shall be RMC, IMC, or EMT.
Article 362 Electrical Nonmetallic Tubing: Types ENT: Add the following:
1) Shall not be used for Electrical Power and Lighting Circuits.
2) When not concealed inside walls and ceilings, only Plenum Rated ENT shall
be installed.
Appeals: Delete.
4-6-4. PERMIT FEES.
Fees for electrical constructions, reconstructions, alterations or installations as
required by the 2020 National Electrical Code adopted hereby, shall be those
established from time to time by ordinance of the City Council. The fee for the
installation of standby generators shall be the same as the fee for that size of service.
4-6-5. PERMITS; INVALIDITY.
Reference 2021 International Building Code Section 105 Permits as amended.
E3
Title 4, Chapter 6, Electrical Code
Page 55 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit E
4-6-6. ADDITIONAL REGULATIONS.
(A) Treatment of Aluminum Wire: All aluminum wire installed in any installation shall be
wire brushed and treated with a compound according to manufacturers'
recommendations.
(C) Luminaires: Luminaires two square feet (2 ft2 ) and larger located in framing
members of a suspended ceiling shall be supported to the structure by a minimum
of two (2) pencil rods or other approved means.
(D) Receptacle Outlets: Receptacle outlets connected to small appliance branch
circuits, as required by Art. 210.52(B)(1), shall be 20 amp rated devices.
4-6-7. ELECTRICAL CONTRACTORS.
(A) Definition: The term "electrical contractor", as used in this section, means any
person, firm, or corporation engaged in the business of installing or altering by
contract electrical equipment for the utilization of electricity for light, heat, or power.
But the term "electrical contractor" shall not include:
1. The installing or altering of radio apparatus or equipment for wireless reception
of sounds and signals; or
2. The installing or altering of apparatus, conductors, or other equipment installed
for or by public utilities, including common carriers, which are under the
jurisdiction of the Illinois commerce commission, for use in their operation as
public utilities; or
3. Employees employed by an electrical contractor to do or supervise his work.
(B) Registration Required: No person shall engage in the business of electrical
contracting within the City without first having registered with the Building Official.
Reference 4-2-3 Building Contractors of City Code Title 4 — Building Regulations.
Exceptions:
1. Nothing contained in this section shall prohibit the owner -occupant of a single-
family residence from planning, installing, altering, or repairing the electrical
system of such residence, provided that said owner -occupant complies with all
ordinances, rules and regulations of the City, and provided further, that any
such owner -occupant may not employ any person other than an electrical
contractor registered with the City to assist him in such work. An affidavit
certifying installation by owner and familiarity with the provisions of the 2020
National Electrical Code is required prior to permit issuance.
4-6-8. PENALTIES.
Reference 4-2-4 Penalty for Violations of City Code Title 4 — Building Regulations.
Title 4, Chapter 6, Electrical Code
E4
Page 56 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit E
4-6-9. - SEVERABILITY.
It is the intention of the City Council that the provisions of this Chapter and the Code
adopted hereby are severable and the invalidity of any Section or any portion of any
such Section of either of them shall not affect any other Section.
4-6-10. — IDENTIFICATION OF ORDINANCE WITH THE ILLINOIS CAPITAL BOARD.
The adoption of this Ordinance and code, by title and edition, shall be reported to the
Illinois Capital Development Board Illinois or any successor agency of the State of
Illinois pursuant to Section 1-2-3.1 of the Illinois Municipal Code, 651LCS 5/1-2-3.1.
4-6-11. — EFFECTIVE DATE.
This Ordinance shall be in full force and effect thirty (30) days after its approval and
passage.
Title 4, Chapter 6, Electrical Code
E5
Page 57 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit F
CHAPTER 7 - MECHANICAL CODE
4-7-1. - ADOPTION.
(A) Pursuant to the authority granted by 65 ILCS 5/1-2-4, and pursuant to its home rule
powers, the City of Evanston hereby adopts by reference the 2021 International
Mechanical Code, with the additions, deletions, exceptions, and other amendments
set forth in this Chapter. All advisory or text notes, other than the rules and
regulations contained in the 2021 International Mechanical Code adopted hereby,
are expressly excluded from this Chapter.
(B) Any reference in the 2021 International Mechanical Code to "Administrative
Authority" or "Building Official" shall refer to the City's Manager of Building and
Inspection Services Division. Any reference to "municipality" shall mean the City of
Evanston.
(C) In the event that any provision of the 2021 International Mechanical Code adopted
hereby is in conflict with any provision(s) of the City Code, the more/most stringent
shall control.
(D) There shall be a copy of the 2021 International Mechanical Code kept on file for
public inspection in the City Clerk's office.
4-7-2. - AMENDMENTS.
The 2021 International Mechanical Code adopted hereby shall read as follows with
respect to the indicated Sections.
101.1 Title. (Insert) City of Evanston
103.1 Creation of Agency. Delete and reference 2021 International Building Code
Section 103.1 as amended.
103.2 Appointment. Delete and reference 2021 International Building Code Section
103.2 as amended.
103.3 Deputies. Delete and reference 2021 International Building Code Section 103.3
as amended.
104.4 Right of Entry. Delete and reference 2021 International Building Code Section
104.6 as amended.
106.4.7 Posting of permit. Delete and reference 2021 International Building Code
Section 105.7 as amended.
106.4.8 Hours of Work Permitted for the Construction, Repair and Demolition of
Buildings. Reference 2021 International Building Code Section 105.8.
106.2 Permits not required. Delete section in its entirety. Contact the Building &
Inspection Services Division for information regarding work exempt from permit.
E1
Title 4, Chapter 6, Mechanical Code
Page 58 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit F
106.4.3 Expiration. Delete and reference 2021 International Building Code Section
105.5 as amended.
106.4.4 Extensions. Delete and reference 2021 International Building Code Section
105.5 as amended.
110.1: Construction Documents: Construction documents, engineering calculations,
diagrams and other data shall be submitted in digital format with each application for a
permit. The Code Official shall require construction documents, computations and
specifications to be prepared and designed by a registered design professional when
required by state law. Where special conditions exist, the Code Official is authorized to
require additional construction documents to be prepared by registered design
professional. Construction documents shall be drawn to scale it shall be of sufficient
clarity to indicate the location, nature and extent of the work proposed and show in
detail that the work conforms to the provisions of this Code. Construction documents for
buildings or than two stories in height shall indicate where penetrations will be made for
mechanical systems, and the materials and methods for maintaining required structural
safety, fire resistance rating and fire blocking. Permit drawing shall include a HVAC
plan showing location of supply, return, and exhausts and shall include a heat load
itemizing CFM delivered or exhausted throughout the system
Exception: The Code Official shall have the authority to waive the submission of
construction documents, calculations or other data if the nature of the work applied for is
such that reviewing of construction documents is not necessary to determine
compliance with this Code.
109.2: Schedule of permit fees. The permit fee for inspection, construction,
reconstruction, alteration, and installation shall be those established from time to time
by the City Council of the City of Evanston.
Section 114. Means of Appeal: Delete section in its entirety.
115.4 Violation penalties. Delete and reference 4-2-4 Penalty for Violations of City
Code Title 4 — Building Regulations.
Section 313
Noise Limitations
313.1 Noise Limitations: Noise levels for equipment and appliances shall not exceed
55 dBA SPL (Decibels, A -weighted, Sound Pressure Level) as averaged over any 15
minute period, and as measured at the property line between the said adjacent
structures if a property line separates the parcels.
Exception: Emergency Back -Up Generators.
501.3.1.1 Exhaust Discharge: Exhaust air shall not be directed onto public sidewalks.
504.9.3: Transition Ducts: Transition ducts used to connect the dryer to the exhaust
duct system shall be a single length that is listed and labeled in accordance with UL
2158A. Transition ducts shall be a maximum of eight feet (8', 2.438 m) in length and
E2
Title 4, Chapter 6, Mechanical Code
Page 59 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit F
shall not be concealed within construction. Flexible air ducts used as a connecter
between clothes dryer and its concealed duct shall be semi ridged aluminum/metal.
602.3 Stud Cavity and Joist Space Plenums: Stud spaces, building cavities, shafts
spaces shall not be used as supply or return air provisions for any portion within a
residential structure.
603.6.1.1 Duct Length: Flexible air ducts shall be limited to eight feet (8', 2.438 m) in
length.
801.18.5: Reuse: Abandoned masonry chimney liners may be used as a chase for high
efficiency appliances adjacent to an active solid fuel chimney under the following
conditions:
1) Chimney or liner thereof serving the still -active solid fuel fireplace shall extend
at least two feet (2', 609 mm) above the point of termination of the high
efficiency appliance vent at all points where the separation is less than eighteen
inches (18", 457 mm) between center lines;
2) The abandoned liner which is used as the chase shall be sealed on top with
non-combustible materials and shall make the chase weather -tight; and
3) Annular space between the two (2) said liners is of masonry construction and
is at least four inches (4", 102 mm).
4-7-3. - HEATING, VENTILATION AND AIR CONDITIONING CONTRACTORS.
(A) Registration Required: Reference 4-2-3 Building Contractors of City Code Title
4 — Building Regulations.
Exception: Nothing contained in 4-2-3 Building Contractors shall prohibit the
owner -occupant of a single-family residence from planning, installing,
altering, or repairing the mechanical system of such residence, provided
that said owner -occupant complies with all ordinances, rules and
regulations of the City, and provided further, that any such owner -occupant
may not employ any person other than a mechanical contractor registered
with the City to assist him in such work. An affidavit certifying installation by
owner and familiarity with the provisions of the 2021 International
Residential Code, International Mechanical Code and International Fuel
Gas Code, as applicable, is required prior to permit issuance.
C 11raN*1 ATJ 4:7_1:1I I I Will!
It is the intention of the City Council that the provisions of this Chapter and the Code
adopted hereby are severable and the invalidity of any Section or any portion of any
such Section of either of them shall not affect any other Section.
4-7-5. — IDENTIFICATION OF ORDINANCE WITH THE ILLINOIS CAPITAL BOARD.
The adoption of this Ordinance and code, by title and edition, shall be reported to the
Illinois Capital Development Board Illinois or any successor agency of the State of
Illinois pursuant to Section 1-2-3.1 of the Illinois Municipal Code, 651LCS 5/1-2-3.1.
E3
Title 4, Chapter 6, Mechanical Code
Page 60 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit F
4-7-6. — EFFECTIVE DATE.
This Ordinance shall be in full force and effect thirty (30) days after its approval and
passage.
E4
Title 4, Chapter 6, Mechanical Code
Page 61 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
CHAPTER 9 RESIDENTIAL CODE
4-9-1. ADOPTION.
(A) Pursuant to the authority granted by 65 ILCS 5/1-2-4, and pursuant to its home rule
powers, the City of Evanston hereby adopts by reference the 2021 International
Residential Code with the additions, deletions, exceptions, and other amendments
set forth in this Chapter. Said Code shall govern the design, construction,
prefabrication, alteration, repair, use occupancy, and maintenance of all detached
one- and two-family dwellings and townhouses not more than three (3) stories
above grade plane in height, with separate means of egress and their accessory
structures. All advisory or text notes, other than the rules and regulations contained
in the 2021 International Residential Code adopted hereby, are expressly excluded
from this Chapter.
(B) Any reference in the 2021 International Residential Code to "Administrative
Authority," "Building Official" or "Code Official" shall refer to the City's Manager of
Building and Inspection Services. Any reference to "municipality" shall mean the
City of Evanston.
(C) In the event that any provision of the 2021 International Residential Code adopted
hereby is in conflict with any provision(s) of the City Code, the more/most stringent
shall control.
(D) There shall be a copy of the 2021 International Residential Code kept on file for
public inspection in the City Clerk's office.
4-9-2. AMENDMENTS.
The following sections of the International Residential Code are hereby amended to
read as follows:
R101. 1 Title.
Insert "the City of Evanston, Cook County, Illinois" for "[name of jurisdiction]
R101.2 Scope. Delete Exceptions 1, 2, and combine Exceptions 3, 4, and 5 to read as
follows:
3. Residential Care Homes and Transitional Treatment Facilities of up to 8
occupants, as regulated in 6-4-4 of the City Zoning Code, within a dwelling unit.
R102.4.3 State Plumbing Code. Add a new subsection to read as follows:
R102.4.3 Illinois Plumbing Code. Whenever a reference is made to the International
Plumbing Code or Chapters 25 through 33 of this Code, such reference shall be
deemed to refer to the applicable section of the Illinois State Plumbing Code, as
adopted by the City of Evanston.
R102.4.4 Electrical Code. Add a new subsection to read as follows:
G1
Title 4, Chapter 9, Residential Code
Page 62 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
R102.4.4 Electrical Code. Whenever a reference is made to Chapters 34 through 43
of this Code, such reference shall be deemed to refer to the applicable section of the
National Electrical Code, as adopted by the City of Evanston.
R102.5 Appendices. Provisions in the appendices shall not apply unless specifically
referenced in the adopting ordinance. The following appendices are hereby adopted:
Appendix AA. Sizing and Capacities of Gas Piping
Appendix AB. Sizing of Venting Systems Serving Appliances Equipped
with Draft Hood, Category I Appliances and Appliances Listed for Use with
Type B Vents
Appendix AC. Exit Terminals of Mechanical Draft and Direct -Vent Venting
Systems
Appendix AF. Radon Control Methods
Commentary: 420 ILCS 52 "The Illinois Radon Resistant Construction Act", requires that
all new residential construction in the State of Illinois shall include passive radon
resistant construction.
Appendix G. (2012 International Residential Code) Swimming Pools, Spas
and Hot Tubs
Commentary: Appendix G was not included in the 2021 IRC as it is now a separate,
stand-alone code. The provisions of the 2012 IRC Appendix G will be retained.
Appendix AH. Patio Covers
Appendix AJ. Existing Buildings and Structures as amended.
Appendix AK. Sound Transmission as amended.
Appendix AO. Automatic Vehicular Gates
Appendix AT. [RE] Solar Ready Provisions -Detached One- and Two -Family
Dwellings and Townhouses
R102.7.1 Additions, alterations or repairs. This section shall be revised to read as
follows:
Additions, alterations or repairs to any structure shall conform to the requirements for a
new structure without requiring the existing structure to comply with the requirements of
this code unless otherwise stated. Additions, alterations, repairs and relocations shall
not cause an existing structure to become less compliant with the provisions of this
code than the existing building or structure was prior to the addition, alteration or repair.
Where an Accessory Dwelling Unit is created within a legally existing two-family
dwelling, bringing the total dwelling unit count to three, the provisions of this code and
Appendix AJ Existing Buildings and Structures shall apply.
R102.7.2 Additions, alteration or repairs following demolition. Additions,
alterations or repairs to any structure that follows the removal or deconstruction of a
structure or building in whole or in part to the extent of 50% or more of such structure or
building as it existed prior to the commencement of such act or process (demolition)
shall comply with the requirements of this code for new construction.
G2
Title 4, Chapter 9, Residential Code
Page 63 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
Exception: Removal or deconstruction of interior building elements without
removal or deconstruction of foundation, exterior walls and/or roofs.
R103.1: Creation of an enforcement agency. This section shall be revised to read as
follows:
The Division of Building and Inspection Services is hereby made responsible for the
enforcement of this Code.
R103.2: Appointment. This section shall be revised to read as follows:
Any reference in the 2021 International Residential Code to "Building Official" shall refer
to the Manager of Building and Inspection Services. Any reference to "municipality"
shall mean the City of Evanston.
R103.3: Deputies. This section shall be revised to read as follows:
The Building Official shall have the authority to appoint such technical officers,
inspectors, plan examiners, and other employees as he or she deems necessary to
effectuate the purposes of this code.
R105.2: Work exempt from permit. This section is deleted in its entirety. Contact the
City's Building and Inspection Services Division for information regarding work exempt
from permits.
R105.3.1.2: Issuance of a building permit. The Building Official may refuse to issue a
building permit if there is an outstanding sum of money due the City from the property
owner or if work done a separately issued building permit has not been satisfactorily
completed per the requirements of these provisions.
R105.5: Expiration. This section shall be revised to read as follows:
1) Expiration. -
a) A building permit shall, without further action by the City, automatically
expire and be rendered null, void, and of no further force or effect, if the
permit holder does not begin the work authorized by the permit within one
hundred eighty (180) calendar days of the date of permit issuance.
b) A building permit shall, without further action by the City, automatically
expire and be rendered null, void, and of no further force or effect, if, at
any time after the work is begun, the permit holder suspends and/or
abandons the work authorized by the building permit for a continuous
period of one hundred eighty (180) calendar days.
c) A building permit shall, without further action by the City, automatically
expire and be rendered null, void, and of no further force or effect, two (2)
years after the date of permit issuance, unless an extension is granted in
accordance with Subsection 2) below.
d) If the building or work authorized by a building permit does not receive
final inspection approval by the permit expiration date, all work shall stop
until the Building Official issues a new permit or grants an extension of
time in accordance with Subsection 2) below. All electrical, plumbing,
G3
Title 4, Chapter 9, Residential Code
Page 64 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
and/or mechanical permits associated with a building permit shall expire
concurrently with the building permit.
2) Extension:
a) Except for relocation of structures, a permit holder may submit, before the
expiration date of the building permit, an application to the Building Official
for an extension of time. The application shall be filed in advance of the
expiration date. The Building Official may extend the building permit once,
for a period not exceeding one hundred eighty (180) calendar days, if
he/she determines that circumstances beyond the permit holder's control
prevented completion of the work. All permits associated with a building
permit shall be extended to expire concurrently with the building permit.
b) If a permit holder files application for an extension of time before expiration
and in accordance with this Subsection, the existing building permit shall
automatically be extended until the Building Official makes a decision on
the application for an extension.
c) If the building permit expires before an application is submitted for an
extension of time, no extension shall be granted. If the previous permit
holder or any other applicant wants to proceed with the same
development, a new application is required and the application is treated
in all respects as a new application.
d) If the Building Official previously approved an extension of time in
accordance with Subsection a), the Building Official may extend the
expiration of the building permit one (1) additional time if he/she finds the
following:
i) There are no significant change(s) in the regulations applicable to the
site since the date the permit was issued;
ii) The additional extension is in the public interest; and
iii) Circumstances beyond the control of the applicant prevented the
authorized work from proceeding.
R105.7: Placement of permit. This section shall be revised to read as follows:
The building permit or a legible copy of the building permit shall be kept on the site of
operations, open to public inspection during the entire time of prosecution of the work
and until the completion of the same. Said permit must be posted within forty-eight (48)
hours of permit issuance and must be visible from the public way. Failure to post the
permit as required by this section may result in revocation of the building permit and
forfeiture of all permit fees.
R105.10: Hours of work permitted for the construction, repair, and demolition of
buildings. The creation (including excavation), demolition, alteration or repair of any
building within the City, other than between the hours of seven o'clock (7:00) A.M. and
seven o'clock (7:00) P.M. on weekdays, and eight o'clock (8:00) A.M. and five o'clock
(5:00) P.M. on Saturdays, except in case of urgent necessity in the interest of public
G4
Title 4, Chapter 9, Residential Code
Page 65 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
health and safety, and then only with permission from the City Manager or his or her
designee, which permission may be granted while the emergency continues.
R106.1: Submittal documents. This section shall be revised to read as follows:
Submittal documents consisting of construction documents, and other data shall be
submitted in two or more sets, or in a digital format where allowed by the building
official, with each application for a permit. Construction documents for all new one- and
two-family dwellings, additions and alterations involving structural work or where the
construction cost exceeds $25,000 shall be prepared by a design professional licensed
with the State of Illinois. Where special conditions exist, the building official is authorized
to require additional construction documents to be prepared by a registered design
professional.
Exception: The Building Official is authorized to waive the submission of construction
documents and other data not required to be prepared by a design professional
licensed with the State of Illinois if it is found that the nature of the work applied for is
such that reviewing of construction documents is not necessary to obtain compliance
with this Code. Projects not requiring preparation by a registered design professional
include single -level decks, single -level exterior stairs, single -story, detached garages
and accessory buildings and unheated porches. Contact the City's Building and
Inspection Services Division for information regarding waiver of preparation by a design
professional licensed with the State of Illinois requirement.
R106.2.1 Compliance with site plan. It shall be the responsibility of the
builder/developer to submit to the Building & Inspection Services Division, a spot survey
prepared by a Registered Land Surveyor within five (5) days of the foundation
installation. No construction will be allowed to proceed until the spot survey is approved
by the City's Zoning Division. This section applies to new one- and two-family
dwellings, townhouses, additions, detached accessory dwelling units and detached
garages.
Exception: The Building Official or Zoning Administrator is authorized to waive the spot
survey requirement if it is found that the nature of the work is such that review of a spot
survey is not necessary to obtain compliance with this code.
R112: BOARD OF APPEALS. Delete this section in its entirety.
R113.4 Violation Penalties. This section shall be revised to read as follows:
Any person who violates a provision of this code or fails to comply with any of the
requirements thereof or who erects, constructs, alters or repairs a building or structure
in violation of the approved construction documents or directive of the building official,
or of a permit or certificate issued under the provisions of this code, shall be subject to
penalties as prescribed under Section 4-9-3 Penalties of the City of Evanston Municipal
Code.
R202: Definitions.
DEMOLITION. The removal or destruction of a structure or building in whole or in part
to the extent of fifty percent (50%) or more of such structure or building as it existed
prior to the commencement of such act or process.
G5
Title 4, Chapter 9, Residential Code
Page 66 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
Table R301.2 CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA. Insert the
following values into the table:
Climatic and Geographic Design
Criteria
Ground Snow Load
30 psf
Wind Speed (mph)
117 mph
Topographic Effects
No
Special Wind Region
Not Applicable
Windborne Debris Zone
Not Applicable
Seismic Design Category
A
Subject to Damage from
Weathering
Severe
Subject to Damage From Frost Line
Depth
42 inches
Subject to Damage From Termite
Slight to Moderate
Ice Barrier Underlayment Required
Yes
Flood Hazards
2008
Air Freezing Index
2000
Mean Annual Temperature
47.6F
Manual J Design Criteria
Elevation
653
Latitude
42 degrees North
Winter Heating
4 degrees
Summer Cooling
89 degrees
Altitude Correction Factor
None
Indoor Design Temperature
70 degrees
Design Temperature Cooling
75 degrees
Heating Temperature Difference
66 degrees
Cooling Temperature Difference
14 degrees
Wind Velocity Heating
None
Wind Velocity Cooling
None
Coincident Wet Bulb
73 degrees
Daily Range
Medium
Winter Humidity
30%
Summer Humidity
50%
Table R301.5 MINIMUM UNIFORMILY DISTRIBUTED LIVE LOADS (in pounds per square foot)
Revise the table to read as follows:
Use
I Balconies (exterior) and deckse
e. See Section R507.1 for decks attached to exterior walls.
Uniform Load (psf) Concentrated
Load (lbs.)
60 —
G6
Title 4, Chapter 9, Residential Code
Page 67 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
R309.1.1 Spill containment. The sills of all door openings between the garage and
residence must be raised at least four inches (4") above the garage floor slab.
Section R309 — Garages and Carports
R309.5 Fire sprinklers. Delete this section in its entirety.
R310.1 Emergency escape and rescue opening required. Delete exception No. 2 in
its entirety.
R313.1.1 Design and Installation. This section shall be revised to read as follows:
Automatic residential sprinkler systems for townhouses shall be designed and installed
in accordance with NFPA 13D.
R313.2 One- and two-family dwellings automatic sprinkler systems. An automatic
sprinkler system shall be installed in one- and two-family dwellings.
Exception: This exception has been revised to read as follows:
An automatic system shall not be required for additions, alterations or when
adding a detached accessory dwelling unit to existing buildings that are not
already provided with a sprinkler system. The following conditions shall exist for
the accessory dwelling unit exception:
1) The unit meets the definition and conditions of an Accessory Dwelling Unit per
6-4-6-10 Special Regulations Applicable to Accessory Dwelling Units (ADUs) of
the City Zoning Code.
2) The existing primary residence is not required to have an automatic residential
sprinkler system
3) The accessory detached dwelling unit does not exceed 1,000 square feet in
size.
4) The unit is on the same lot as the primary residence.
R313.2.1: Design and installation. This section has been revised to read as follows:
Automatic residential sprinkler systems shall be designed and installed in accordance
with NFPA 13D.
R327 Swimming Pools, Spas and Hot Tubs. Delete this section in its entirety.
R331 Wrecking, Demolition, or Razing of Structures.
1) Prior to the issuance of any permit for the wrecking, demolishing, or razing of
any building or other structure, the owner of said structure shall deposit, in
escrow, funds in an amount deemed sufficient by the Director of Community
Development to secure the owner's obligations to grade, place topsoil, seed,
sod, and/or fence any unimproved surface. Should the owner and/or owner's
successor(s) in interest fail to perform said duties, the City may draw on said
funds to complete them.
2) Prior to the start of demolition work, the owner and/or owner's successor(s)
shall deliver all water meters on the property to the Utilities Department.
G7
Title 4, Chapter 9, Residential Code
Page 68 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
3) Demolition work shall not begin until site has been inspected by the City for
placement of temporary fencing and temporary tree protection, and any related
measures implemented.
4) Demolition work shall not begin until the owner and/or owner's successor(s)
has established, either by way of a hose connected to the public water hydrant
or by the use of a water truck on site, a source for wetting down the structure
and resulting debris during the demolition process to minimize the creation of
air -borne dust and debris.
5) Written notice stating the date on which work is to begin shall be given to the
Director of Community Development and to owners/occupants of adjoining
property at least forty-eight (48) hours before beginning the wrecking,
demolishing, or razing of any building or other structure.
6) During demolition, any temporary structure erected adjacent to or on any public
way, used as temporary storage for debris and wreckage, shall be outfitted
with reflective orange material outlining every top and bottom corner of said
temporary structure, which reflective material will be visible when struck by
headlight beams three hundred feet (300') away at night. Said markings shall
be approved by the City Engineer.
7) All foundations and footings associated with the demolished structure shall be
removed in the course of demolition. The property owner and/or owner's
successor(s) in interest shall schedule and permit an inspection by the Building
Official or his/her designee to determine removal of all foundations and
footings prior to the backfill of any excavated area.
8) Debris caused from the demolition of a building or structure in excess of that
required to fill openings shall be removed from the site as wrecking
progresses. Salvaged material, if left on the premises, shall be stored neatly.
Debris shall be kept from adjacent properties and public ways at all times.
9) On completion of demolition, all debris, equipment and temporary protections
shall be removed from the site. In no case shall demolition debris be allowed to
remain on the site longer than seven (7) days after the structure has been
demolished.
10) On completion of demolition, owner and/or owner's successor(s) shall
immediately restore the public right-of-way to its original condition upon
completion of the work, including restoration of openings, broom sweeping
walks and streets and raking of grassy areas.
11) On completion of demolition, the property owner and/or owner's successor(s)
in interest shall fill with clean inorganic material with the upper eight inches (8")
filled in friable topsoil and graded to the level of sidewalks, alleys, or adjoining
property with allowance for settlement.
12) On completion of demolition, the property owner and/or owner's successor(s)
in interest shall schedule and permit an inspection by the Building Official or
his/her designee to determine compliance with the City Code.
G8
Title 4, Chapter 9, Residential Code
Page 69 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
13) Unless construction of a new structure on the site commences within sixty (60)
days of completion of demolition, the property owner and/or owner's
successor(s) shall seed the property with grass or place sod thereon no later
than fifteen (15) days after completion of demolition. The temporary
construction fence shall be removed no later than fifteen (15) days after such
seeding or sodding.
R403.1.1.1: Trench foundations. Trench foundations incorporating a monolithically -
poured footing and foundation wall shall be permitted for one story wood frame and
wood frame with masonry veneer room additions provided the following are met-
1 ) Trench foundations are to be designed in accordance with accepted
engineering practice based on a minimum allowable soil pressure of 3000 psf
and a minimum concrete compressive strength of 3000 psf at twenty-eight (28)
days.
2) The foundation wall shall be a minimum of eight inches (8") wide and be belled
at the bottom to a minimum width of twice the wall width for a depth of at least
one foot (1').
3) Trench foundations shall be permitted only in those soils which exhibit
cohesive characteristics so as to prevent collapse of the adjacent soil mass
before, during and after placement of the concrete.
4) Trench foundations shall extend a minimum of forty-two inches (42") below
adjacent grade.
5) Trench foundations shall comply with all applicable sections of the 2021
International Residential Code, adopted by the City, except as previously
mentioned.
R502.1. 2: Prefabricated wood I -joists. This section is revised to read as follows:
Structural capacities and design provisions for prefabricated wood I -joists shall be
established and monitored in accordance with ASTM D 5055. Where prefabricated
wood I -joists are used for floor and ceiling joist framing members in finished or
unfinished spaces in one or two-family dwellings, the prefabricated wood I -joists shall be
separated from adjacent spaces by a minimum five -eighths inch (5/8") thick, type "X"
gypsum wall board, taped. Such separation shall not be required for structures fully
equipped with an automatic sprinkler system designed and installed in accordance with
N.F.P.A. 13R.
R506.2.3 Vapor retarder. Exception No. 1 is revised to read as follows.
Detached garages, utility buildings and other unheated accessory structures.
R602.3: Design and construction. This section is revised to read as follows:
Exterior walls of wood frame construction shall be designed and constructed in
accordance with the provisions of this chapter and figures R602.3(1) and R602.3(2) or
in accordance with AWC NDS. Components of exterior walls shall be fastened in
accordance with table R602.3(1) through R602.3(4). Wall sheathing shall be fastened
directly to framing members and, where placed on the exterior side of an exterior wall,
G9
Title 4, Chapter 9, Residential Code
Page 70 of 99
Doc ID: 89d95372ca2la88d7c7e45de8e6b363662felfl5
Ordinance 29-0-22, Exhibit G
shall be capable of resisting wind pressures listed in Table R301.2.1(1) adjusted for
height and exposure using Table R301.2.1(2) and shall conform to the requirements of
Table R602.3(3). Wall sheathing used only for exterior wall covering purposes shall
comply with Section R703. Exterior walls covered with foam plastic sheathing shall be
braced in accordance with section R602.10. Structural sheathing shall be fastened
directly to structural framing members. Any wall which contains any plumbing or
mechanical piping, and/or ductwork must have a minimum depth of the structural
members of five and one-half inches (5'/2"). Studs shall be continuous from support at
the sole plate to a support at the top plat to resist loads perpendicular to the wall. The
support shall be a foundation or floor, ceiling or roof diaphragm or shall be designed in
accordance with accepted engineering practice.
Chapter 11 — Energy Efficiency. This Chapter is retained for references purposes
only. For purposes of compliance, the design and construction of building is regulated
by Title 71, Part 600 of the Illinois Administrative Code — Illinois Energy Conservation
Code.
k15111411-v i 3tl'iLTe l f-Ti 10
ELECTRIC VEHICLE. An automotive -type vehicle for on -road use primarily powered by
an electric motor that draws current from an onboard battery charged through a building
electrical service, electric vehicle supply equipment (EVSE), or another source of
electric current.
ELECTRIC VEHICLE SUPPLY EQUIPMENT (EVSE). The apparatus installed
specifically for the purpose of transferring energy between the premises wiring and the
Electric Vehicle.
EV-CAPABLE SPACE. A dedicated parking space with electrical panel capacity and
space for a branch circuit dedicated to the EV parking space that is not less than 40-
ampere and 208/240-volt and equipped with raceways, both underground and surface
mounted, to enable the future installation of electric vehicle supply equipment. For two
adjacent EV-Capable spaces, a single branch circuit is permitted.
EV-READY SPACE. A designated parking space which is provided with a dedicated
branch circuit that is not less than 40-ampere and 208/240-volt assigned for electric
vehicle supply equipment terminating in a receptacle or junction box located in close
proximity to the proposed location of the EV parking space. For two adjacent EV-Ready
spaces, a single branch circuit is permitted.
Section N1101.15 ELECTRIC VEHICLE CHARGING. Where parking is provided, new
construction shall provide electric vehicle spaces in compliance with Sections
N1101.15.1 through N1101.15.4. Where more than one parking facility is provided on a
site, electric vehicle parking spaces shall be calculated separately for each parking
facility.
Exception: This section does not apply to parking spaces used exclusively for
trucks or delivery vehicles.
N1101.15.1 Electric vehicle ready circuit. The service panel shall provide
sufficient capacity and space to accommodate the circuit and over -current protective
device for each EV-Ready Space.
G10
Title 4, Chapter 9, Residential Code
Page 71 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
N1101.15.2 New detached one- and two-family dwelling units and
townhouses. New detached one- and two-family dwelling units and townhouses shall
provide not less than one EV-Ready Space per dwelling unit.
N1101.15.3 New multifamily dwellings. EVSE-Installed, EV-Ready and EV-
Capable Spaces for Group R-2, R-3 and R-4 buildings three stories or less in height
above grade shall be provided in accordance with Table N1101.15.3. Where the
calculation of percent served results in a fractional parking space, it shall round up to
the next whole number.
Table N1101.15.3: EVSE Installed, EV-Ready and EV-Capable Space
Requirements
One- and Two -Family Dwelling Units and Multifamily
Townhouses
One (1) EV-Ready Space per Dwelling Unit
a. Where EVSE-Installed Spaces
1101.15.3, the additional spaces
requirement.
10% EV-Installed, 20% EV-Ready, 70% EV-
Capable
EV-installed and EV-Ready to increase 10%
ever 3 years with remainder of spaces being
EV-Capable
installed exceed the required values in Table
shall be deducted from the EV-Ready Spaces
b. Where EV-Ready Spaces installed exceed the required values in Table
1101.15.3, the additional spaces shall be deducted from the EV-Capable Spaces
requirement.
N1101.15.4 Identification. Construction documents shall indicate the raceway
termination point and proposed location of future EV spaces and EVSE. Construction
documents shall also provide information on amperage of future EVSE, raceway
methods, wiring schematics and electrical load calculations to verify that the electrical
panel service capacity and electrical system, including any on -site distribution
transformers, meet the requirements of this code. Parking spaces equipped with EVSE
shall be identified by signage. A permanent and visible "EV-Capable" or "EV-Ready"
label shall be posted in a conspicuous place at the service panel to identify each panel
space reserved to support EV-Capable or EV-Ready Spaces, respectively and at the
termination point of the raceway or circuit termination point.
Section M1309
Noise Limitations
M1309.1 Noise limitations. Noise levels for equipment and appliances shall not
exceed 55 dBA SPL (Decibels, A -weighted, Sound Pressure Level) as averaged over
any 15 minute period, and as measured at the property line between the said adjacent
structures if a property line separates the parcels.
Exception: Emergency Back -Up Generators.
Chapters 25 through 32. Delete these Chapters in their entirety. Whenever a
reference is made to the International Plumbing Code or Chapters 25 through 33 of this
Code, such references shall be deemed to refer to the applicable section of the Illinois
Plumbing Code, as adopted by the City of Evanston.
G11
Title 4, Chapter 9, Residential Code
Page 72 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
P2904 Dwelling unit fire sprinkler systems. Whenever a reference is made to
Section P2904 of this Code, such reference shall be deemed to refer the NFPA 13D
Standard for the Installation of Sprinkler Systems in One- and Two -Family Homes and
Manufactured Homes.
Chapters 34 through 42. Delete these Chapters in their entirety. Whenever a
reference is made to Chapters 34 through 43 of this Code, such reference shall be
deemed to refer to the applicable section of the National Electrical Code, as adopted by
the City of Evanston.
Appendix AJ — Existing Buildings and Structures. Appendix adopted with the
following revisions:
1. Delete Subsection AJ107.1.2 Plumbing materials and supplies.
2. Delete Subsection AJ107.2 Water closets
3. Delete Subsection AJ107.3 Electrical
4. Delete Subsection AJ109.5 Electrical equipment and wiring
Appendix AK - Sound Transmission. Appendix adopted with the following revisions:
AK102.1: General. This section has been revised to read as follows:
Airborne sound insulation for wall and floor -ceiling assemblies shall meet a sound
transmission class (STC) rating of fifty (50) when tested in accordance with ASTM E 90.
AK103.1: General. This section has been revised to read as follows:
Floor/ceiling assemblies between dwelling units or between a dwelling unit and a public
or service area within a structure shall have an impact insulation class (IIC) rating of not
less than fifty (50) when tested in accordance with ASTM E 492.
4-9-3. PENALTIES.
Any person who violates any provision of the 2021International Residential Code
as adopted by the City, who fails to comply with any of the requirements thereof, or who
erects, installs, alters, or repairs work in violation of any approved plan or direction of
the Building Official or of any permit or certificate issued by the Building Official or
his/her designee, shall be guilty of an offense and fined as follows:
(A) 1. The fine for a first violation is one hundred fifty dollars ($150.00).
2. The fine for a second violation is four hundred dollars ($400.00).
3. The fine for a third or subsequent violation is seven hundred fifty dollars
($750.00).
(B) Each day a provision of this Chapter is found to have been violated constitutes
a separate violation subject to the fine schedule set forth in Subsection (A) of
this Section.
(C) The fines provided for herein shall not be construed as limiting the power of a
court of competent jurisdiction or an administrative hearing officer to impose
other penalties and remedies as provided for by applicable legislation.
G12
Title 4, Chapter 9, Residential Code
Page 73 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit G
4-9-4. SEVERABILITY.
It is the intention of the City Council that the provisions of this Chapter and the Code
adopted hereby are severable and the invalidity of any Section or any portion of any
such Section of either of them shall not affect any other Section.
4-9-5. — IDENTIFICATION OF ORDINANCE WITH THE ILLINOIS CAPITAL BOARD.
The adoption of this Ordinance and code, by title and edition, shall be reported to the
Illinois Capital Development Board Illinois or any successor agency of the State of
Illinois pursuant to Section 1-2-3.1 of the Illinois Municipal Code, 651LCS 5/1-2-3.1.
4-9-6. — EFFECTIVE DATE.
This Ordinance shall be in full force and effect thirty (30) days after its approval and
passage.
G13
Title 4, Chapter 9, Residential Code
Page 74 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit H
CHAPTER 17 - FUEL GAS CODE
4-17-1. - ADOPTION.
(A) Pursuant to the authority granted by 65 ILCS 5/1-2-4, and pursuant to its home rule
powers, the City of Evanston hereby adopts by reference the 2021 International
Fuel Gas Code, with the additions, deletions, exceptions, and other amendments
set forth in this Chapter. All advisory or text notes, other than the rules and
regulations contained in the 2021 International Fuel Gas Code adopted hereby, are
expressly excluded from this Chapter.
(B) Any reference in the 2021 International Fuel Gas Code to "Administrative Authority,"
"Building Official" or "Code Official" shall refer to the City's Manager of Building and
Inspection Services Division. Any reference to "municipality" shall mean the City of
Evanston.
(C) In the event that any provision of the 2021 International Fuel Gas Code adopted
hereby is in conflict with any provision(s) of the City Code, the more/most stringent
shall control.
(D) There shall be a copy of the 2021 International Fuel Gas Code kept on file for public
inspection in the City Clerk's office.
4-17-2. - AMENDMENTS.
The 2021 International Fuel Gas Code adopted hereby shall read as follows with
respect to these Sections.
101.1 Title. City of Evanston
103.1 Creation of Agency. Delete and reference 2021 International Building Code
Section 103.1 as amended.
103.2 Appointment. Delete and reference 2021 International Building Code Section
103.2 as amended.
103.3 Deputies. Delete and reference 2021 International Building Code Section 103.3
as amended.
104.4 Right of Entry. Delete and reference 2021 International Building Code Section
104.6 as amended.
106.2 Permits not required. Delete section in its entirety. Contact the Building &
Inspection Services Division for information regarding work exempt from permit.
106.5.3 Expiration. Delete and reference 2021 International Building Code Section
105.5 as amended.
106.5.4 Extensions. Delete and reference 2021 International Building Code Section
105.5 as amended.
H1
Title 4, Chapter 17, Fuel Gas Code
Page 75 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit H
106.5.7 Posting of permit. Delete and reference 2021 International Building Code
Section 105.7 as amended.
106.5.8 Hours of Work Permitted for the Construction, Repair and Demolition of
Buildings. Reference 2021 International Building Code Section 105.8.
107.1: Construction Documents: Construction documents, engineering calculations,
diagrams and other data shall be submitted in digital format with each application for a
permit. The Code Official shall require construction documents, computations and
specifications to be prepared and designed by a registered design professional when
required by state law. Where special conditions exist, the Code Official is authorized to
require additional construction documents to be prepared by registered design
professional. Construction documents shall be drawn to scale it shall be of sufficient
clarity to indicate the location, nature and extent of the work proposed and show in
detail that the work conforms to the provisions of this Code. Construction documents for
buildings or than two stories in height shall indicate where penetrations will be made for
installations and indicate the materials and methods for maintaining required structural
safety, fire resistance rating and fire blocking. Permit drawing shall include a HVAC
plan showing location of supply, return, and exhausts and shall include a heat load
itemizing CFM delivered or exhausted throughout the system
Exception: The Code Official shall have the authority to waive the submission of
construction documents, calculations or other data if the nature of the work applied for is
such that reviewing of construction documents is not necessary to determine
compliance with this Code.
109.2: Schedule of permit fees. The permit fee for inspection, construction,
reconstruction, alteration, and installation shall be those established from time to time
by the City Council of the City of Evanston.
Section 113: Means of Appeal: Delete section in its entirety.
Section 114: Board of Appeals: Delete section in its entirety.
115.4: Violation Penalties: Delete and reference 4-2-4 Penalty for Violations of City
Code Title 4 — Building Regulations.
Section 311
Noise Limitations
311 Noise Limitations: Noise levels for equipment and appliances shall not exceed 55
dBA SPL (Decibels, A -weighted, Sound Pressure Level) as averaged over any 15
minute period, and as measured at the property line between the said adjacent
structures if a property line separates the parcels.
503.3.4.1 Exhaust discharge: Exhaust air shall not be directed onto public sidewalks.
4-17-3. - HEATING, VENTILATION AND AIR CONDITIONING CONTRACTORS.
H2
Title 4, Chapter 17, Fuel Gas Code
Page 76 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit H
Registration Required. Reference 4-2-3 Building Contractors of City Code Title 4—
Building Regulations.
Exception: Nothing contained in 4-2-3 Building Contractors shall prohibit the owner -
occupant of a single-family residence from planning, installing, altering, or repairing
the fuel gas system of such residence, provided that said owner -occupant complies
with all ordinances, rules and regulations of the City, and provided further, that any
such owner -occupant may not employ any person other than a mechanical
contractor registered with the City to assist him in such work. An affidavit certifying
installation by owner and familiarity with the provisions of the 2021 International
Residential Code, International Mechanical Code and International Fuel Gas Code,
as applicable, is required prior to permit issuance.
4-17-4. — SEVERABILITY.
It is the intention of the City Council that the provisions of this Chapter and the Code
adopted hereby are severable and the invalidity of any Section or any portion of any
such Section of either of them shall not affect any other Section.
4-17-5. — IDENTIFICATION OF ORDINANCE WITH THE ILLINOIS CAPITAL BOARD.
The adoption of this Ordinance and code, by title and edition, shall be reported to the
Illinois Capital Development Board Illinois or any successor agency of the State of
Illinois pursuant to Section 1-2-3.1 of the Illinois Municipal Code, 651LCS 5/1-2-3.1.
4-17-6. — EFFECTIVE DATE.
This Ordinance shall be in full force and effect thirty (30) days after its approval and
passage.
H3
Title 4, Chapter 17, Fuel Gas Code
Page 77 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
CHAPTER 1 PROPERTY MAINTENANCE CODE
5-1-1. ADOPTION.
(A) Pursuant to the authority granted by 65 ILCS 5/1-2-4, and pursuant to its home rule
powers, the City of Evanston hereby adopts by reference as its standard for the
maintenance of existing buildings, the International Code Council, International
Property Maintenance Code of 2021 ("International Property Maintenance Code"),
with the amendments below stated. All advisory or text notes, other than the rules
and regulations contained in the ICC, International Property Maintenance code, be
and the same are hereby expressly excluded from this chapter.
(B) Any reference in the Property Maintenance Code to "code official" shall refer to the
Manager of the Building & Inspection Services Division or his/her designee. Any
reference to "municipality" shall mean the City of Evanston.
(C) In the event that any provision of the 2021 International Property Maintenance
Code adopted hereby is in conflict with any provision(s) of the City Code, the
more/most stringent shall control.
(D) There shall be a copy of the 2021 International Property Maintenance Code kept on
file for public inspection in the City Clerk's office.
5-1-2. APPLICATION.
The International Property Maintenance Code shall apply to all matters concerning
the protection of public health, safety and welfare in all existing structures, residential
and nonresidential, and on all existing premises in the City as provided in the code.
5-1-3. AMENDMENTS.
The following sections of the International Property Maintenance Code are deleted,
amended or added to read as follows:
Chapter 1. Administration.
Section 101 General
101.1 Title. These regulations shall be known as the Property Maintenance Code
of the City of Evanston, hereinafter referred to as "this code."
101.2.1 Appendices. Adopted as part of this code is Appendix A: Boarding
Standard.
Section 102 Applicability
102.3 Application of Other Codes. Repairs, additions or alterations to a structure,
or changes of occupancy, shall be done in accordance with the procedures and
provisions of the International Building Code, International Residential Code,
International Fire Code, International Mechanical Code, International Fuel Gas
Code, NFPA 70 National Electrical Code, State of Illinois Plumbing Code, and any
11
Title 5, Chapter 1, Property Maintenance Code
Page 78 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit
other applicable code or ordinance adopted by the City of Evanston and any other
applicable legislation or regulation. Nothing in this code shall be construed to
cancel, modify or set aside any provision of the Evanston Zoning Ordinance, Title 6
of the Evanston City Code, as amended.
102.5 Workmanship. Repairs, maintenance work, alterations or installations which
are caused directly or indirectly by the enforcement of this code shall be executed
and installed in a workmanlike manner. Work not meeting the definition of
workmanlike may be rejected by the code official or their designee.
Section 103 Code Compliance Agency
103.1 General. The Building & Inspection Services Division is hereby assigned to
enforce this code and the official in charge thereof, the Building & Inspection
Services Division Manager, shall be known as the Code Official. The function of
the agency shall be the implementation, administration and enforcement of the
provisions of this code.
Section 105 Duties and Powers of the Code Official
105.3 Right of Entry. The code official is authorized to enter the structure or
premises at reasonable times to inspect subject to constitutional restrictions on
unreasonable searches and seizures. If entry is refused or not obtained, the code
official is authorized to pursue recourse as provided by law. If the premises owner
does not grant the code official entry to the entire premises during an initial
inspection, cure code violations discovered and cited during an initial inspection
before the compliance re -inspection, or grant the code official access to the entire
premises to re -inspect for every such cited violation, thereby requiring the code
official to perform multiple re -inspections, the premises owner shall owe the city a
fee of one hundred fifty dollars ($150.00) for the second and any subsequent re -
inspection. If the premises owner does not grant the code official entry for a
scheduled inspection without canceling said inspection on a city business day and
at least twenty-four (24) hours in advance of the appointed inspection time, or fails
to give his or her tenants forty-eight (48) hours notice of the inspection date, the
premises owner shall owe the city a fee of.one hundred fifty dollars ($150.00) for
the first such failure; two hundred fifty dollars ($250.00) for the second such failure;
and five hundred dollars ($500.00) for the third and any subsequent such failure.
Any fees assessed pursuant to this section shall be debts due and owing to the city
that the city may collect by any means allowed by law, including, but not limited to:
refusing to issue any permit, license, or zoning relief related to the structure or
premises; employing a collection agency; and filing a lien against the premises.
105.8 Documentation. The code official may require written submittal of estimates,
executed contracts, invoices, receipts, proof of payment or other documentation
regarding the completion or proposed completion of work for which a notice of
violation has been issued. Submittal of leases may be required to establish the
occupancy of any leased or rented space.
Title 5, Chapter 1, Property Maintenance Code
A
Page 79 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
105.9 Engineering Reports. The code official may require submittal of written
reports by a licensed design professional regarding violations for which a notice of
violation has been issued.
105.11 Permits Required. Any owner or authorized agent who intends to
construct, enlarge, alter, repair, move, demolish, or change the occupancy of a
building or structure, or to erect, install, enlarge, alter, repair, remove, convert or
replace any electrical, gas, mechanical or plumbing system, the installation of which
is regulated by the International Building Code, International Residential Code,
International Fire Code, International Mechanical Code, International Fuel Gas
Code, NFPA 70 National Electrical Code, State of Illinois Plumbing Code or any
other applicable code or ordinance adopted by the City of Evanston and any other
applicable legislation or regulation or to cause any such work to be done, shall first
make application to the building official and obtain the required permit. Nothing in
this code shall be construed to cancel, modify or set aside any provision of the
Evanston Zoning Ordinance, Title 6 of the Evanston City Code, as amended.
Section 107 Means of Appeal. Delete section in its entirety.
Section 108 Board of Appeals. Delete section in its entirety.
Section 109 Violations
109.3 Prosecution of Violations. Any person failing to comply with a notice of
violation or order served in accordance with section 111.4 shall be deemed guilty of
a violation of this code, and the violation shall be deemed a strict liability offense. If
the notice of violation is not complied with, the code official shall institute the
appropriate proceeding at law or in equity to restrain, correct or abate such
violation, or to require the removal or termination of the unlawful occupancy of the
structure in violation of the provisions of this code or of the order of direction made
pursuant thereto. Any action taken by the authority having jurisdiction on such
premises shall be charged against the real estate upon which the structure is
located and shall be a lien upon such real estate.
109.4 Violation Penalties. Any person found to have violated any provision of this
code, the International Property Maintenance Code, adopted hereby, shall be guilty
of an offense punishable as follows.
1. The fine for a first violation is $150.00
2. The fine for a second violation is $400.00
3. The fine for a third and any subsequent violation is $750.00
A separate offense shall be deemed to have been committed upon each such day
such violation shall occur or continue.
109.6 Criminal Housing Management. A person commits the offense of criminal
housing management when, having personal management or control of residential
or commercial real estate, whether as a legal or equitable owner or as a managing
agent or otherwise, he/she recklessly permits the physical condition or facilities of
the residential or commercial real estate to become or remain in any condition
which endangers the health or safety of any person. A person acts "recklessly"
13
Title 5, Chapter 1, Property Maintenance Code
Page 80 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
within the meaning of this section if he/she recklessly performs the acts which
cause bodily harm or which endanger bodily safety of a person, or if he/she
recklessly fails to perform and said failure causes the harm or endangers the safety
of a person.
109.6.1 Criminal Housing Management Penalty. A person who commits the
offense of criminal housing management as prohibited by 109.6 shall be guilty of a
misdemeanor and shall be subject to a term of incarceration not to exceed six (6)
months and a fine not to exceed one thousand five hundred dollars ($1,500.00).
Each day that a violation continues after due notice has been served shall be
deemed a separate offense. The court, may as part of any sentence, requires the
defendant to remedy the violation(s).
109.7 Fines. The fines and penalties provided for herein shall not be construed as
limiting the power of a court of competent jurisdiction or an administrative hearing
officer to impose other penalties and remedies as provided for by applicable
legislation.
Section 110 Stop Work Order
110.4 Failure to comply. Any person who shall continue any work after having been
served with a stop work order, except such work as that person is directed to perform to
remove a violation or unsafe condition, shall be subject to the penalties provided for in
Section 109.4.
Section 111 Unsafe Structures and Equipment
111.4.1 Form. Such notice prescribed in section 111.4 shall be in accordance with
all of the following-
1 . Be in writing.
2. Include a description of the real estate sufficient for identification.
3. Include a statement of the violation or violations and why the notice is
being issued.
4. Include a correction order allowing a reasonable time to make the repairs
and improvements required to bring the dwelling unit, structure or
premises into compliance with the provision of this code.
5. Include a statement that the city may file a lien in accordance with section
109.3
6. Include a statement that the city may initiate immediate legal action upon
certain violations of this code subsequent to a first notice of violation
issued by property standards.
7. Notwithstanding the foregoing, any violation found subsequent to issuance
of a violation notice or legal action within the previous 365 days relating to
litter, garbage, rubbish, inoperable motor vehicles, weeds and other similar
exterior violations, a violation notice may be posted on or about the
structure or premises affected by the violation. Such violation notice shall
Title 5, Chapter 1, Property Maintenance Code
14
Page 81 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
not identify a date for correction but shall state that legal action may be
initiated without any further notice.
111.4.2 Method of Service. Such notice shall be deemed to be properly served if a
copy thereof is:
1. Delivered personally which shall include service upon an employee; or
2. Sent by first-class mail, express mail, overnight carrier or certified mail
addressed to the last known address, or
3. Sent by electronic mail (email); or
4. Posted in a conspicuous place in or about the structure affected by such
notice
111.6 Transfer of ownership. It shall be unlawful for the owner of any dwelling unit
or structure who has received a compliance order or upon whom a notice of
violation has been served to sell, transfer, mortgage, lease or otherwise dispose of
such dwelling unit or structure to another until the provisions of the compliance
order or notice of violation have been complied with, or until such owner or the
owner's authorized agent shall first furnish the grantee, transferee, mortgagee or
lessee a true copy of any compliance order or notice of violation issued by the code
official and shall furnish to the code official a signed and notarized statement from
the grantee, transferee, mortgagee or lessee, acknowledging the receipt of such
compliance order or notice of violation and fully accepting the responsibility without
condition for making the corrections or repairs required by such compliance order or
notice of violation. When applicable, building permits and inspection approvals are
required for transfer of ownership.
111.9 Restoration or abatement. The structure or equipment determined to be
unsafe by the code official is permitted to be restored to a safe condition. The
owner, owner's authorized agent, operator or occupant of a structure, premises or
equipment deemed unsafe by the code official shall abate or cause to be abated or
corrected such unsafe conditions either by repair, rehabilitation, demolition or other
approved corrective action.
Section 112 Emergency Measures
112.6 Hearing. Delete.
Chapter 2. Definitions.
Section 201 General
201.3 Terms Defined In Other Codes. Where terms are not defined in this code
and are defined in the International Building Code, International Fire Code,
International Fuel Gas Code, International Mechanical Code, State of Illinois
Plumbing Code, International Residential Code, NFPA 70 National Electrical Code
and any other applicable code or ordinance adopted by the City of Evanston and
any other applicable legislation or regulation such terms shall have the meanings
ascribed to them as in those codes.
Section 202 General Definitions
Title 5, Chapter 1, Property Maintenance Code
15
Page 82 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
Add the following definitions:
Burglary -Resistant Glazing Material. Glazing materials shall meet or exceed
Underwriters Laboratories standard #UL 972 for burglary -resistant glazing material.
Combination Dead Latch and Dead Bolt. A device combining a dead latch
operable by knob from inside and outside by a key, both of which can be retracted
from the inside by turning the knob and from the outside by a key.
Cylinder Guard. A hardened steel ring or plate surrounding the otherwise exposed
portion of a cylinder lock to protect the cylinder from cutting, prying, pulling or
wrenching with common tools.
Dead Bolt. A lock bolt which has no automatic spring action and which is operated
by a key, thumb -turn, lever or knob and is positively held fast in the protected
position against return, by end pressure.
Dead Latch. A latch which is positively held in latched position with a strike, by an
added integral bolt -type mechanism and is again released by a key from the
outside and a knob or similar actuator from the inside.
Door Scope. A system of lenses encased for convenient installation in entrance
doors permitting an inside viewer to observe a one hundred eighty degree (180°)
area of the outside with the door closed.
Double -Cylinder Dead Bolt. A dead bolt lock actuated by a key from the inside
and outside.
Dwelling Unit. As defined in Section 6-18-3 of the Evanston City Code, as
amended.
Escutcheon Plate. A protective shield or enclosure that encompasses the
circumference of a pipe that typically penetrates a floor, and covers the open area
surrounding the pipe or penetration.
Foot-candle. A unit of illumination, equivalent to the illumination produced by a
source of one candle at a distance of one foot and equal to one lumen incident per
square foot. Abbreviation: FC.
Graffiti. Any and every name, identification, description, announcement,
declaration, demonstration, display, illustration or insignia, other than advertising
which is otherwise provided for in this code or other ordinances of the city, which,
without authorization, is marked, written, drawn, painted, scratched, inscribed, or
affixed directly to or upon any of the following objects or structures: public or private
curbstone, flagstone, or any portion or part of any sidewalk or street or upon any
tree, lamppost, utility pole, postal mail receptacle, sign, hydrant, gate, fence, door,
wall, window, garage, enclosure, vehicle, bridge, pier or upon or within any other
public or private structure, building or premises.
Inoperable Motor Vehicle. A vehicle, including any auto, bus, truck, van,
motorcycle, trailer or boat, which cannot be lawfully driven or used upon the public
streets for reasons including but not limited to being unlicensed, unregistered,
wrecked, abandoned, in a state of disrepair, or incapable of being moved under its
Title 5, Chapter 1, Property Maintenance Code
Ef
Page 83 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662felf15
Ordinance 29-0-22, Exhibit I
own power for motor vehicles, or in the case of a boat, if incapable of being used as
a means of transportation on water and/or if not currently registered in accordance
with the boat registration and safety act, 625 ILCS 45/1 et seq., as amended.
Insert. A hardened steel roller inside unhardened bolts to prevent bolt cutting or
sawing with common tools.
Latch. A spring -loaded device which automatically holds a swinging door shut upon
closing by engaging a strike and which is released by turning a knob, lever, or
similar actuator from inside or outside.
Light Trespass. Light emitted by a luminaire that shines beyond the boundaries of
the property on which the luminaire is located.
Litter. Any papers, newspapers, packaging, bags, plastics, cups, containers, cans
and other similar materials lying scattered about that are subject to movement by
any wind or breeze.
Mortise -Type Lock. A lock placed into an opening, groove or slot, cut in the edge
of a door.
Multi -Unit Rental Dwelling. A building or portion thereof, operating under a rental
agreement, including renter -occupied cooperatives and condominium units.
Multiple Point Locks. A system of lever -operated bolts that engages a door
opening, at the head and sill as a minimum, operated by a single knob or handle
from the inside, and, optionally, a cylinder -locked handle from the outside.
Owner -Occupied Unit. A dwelling unit occupied by an owner of the building and or
unit titleholder of the property including "those who have any undivided, joint, or
survivorship interest by specific devise or by any recorded document whether that
interest is an entire ownership interest or less than an entire ownership interest."
Rabbeted Jamb. The wooden sides and head of a door cut in such a way so that a
notch is created against which the door may be closed.
Rim -Type Cylinder Lock. A lock made for mounting on the face of a door.
Rooming house. As defined in Title 5, Chapter 2 of the Evanston City Code, as
amended.
Sash Fasteners. Locking devices which prevent a window from being moved.
Sign. A name, identification, description, display, message or illustration which is
affixed to, or represented directly or indirectly upon, a building, structure, or piece of
land so as to be principally seen from out-of-doors and which directs attention to an
object, product, place, activity, concept, thought, person, institution, organization, or
business.
Sign, Abandoned. Any sign advertising a business, commodity, service,
entertainment or activity which has been discontinued.
Single Cylinder Dead Bolt. A dead bolt lock activated from the outside by a key
and from the inside by a knob, thumb -turn, lever, or similar actuator.
Title 5, Chapter 1, Property Maintenance Code
17
Page 84 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
Single -Unit Dwelling. A building containing one owner -occupied dwelling unit; an
owner -occupied condominium unit or cooperative.
Single -Family Rental. A unit operating under a rental agreement.
Strike. A metal plate designed to receive and hold a projected bolt or latch.
Window Area. Any transparent area on a facade through which the interior of a
premises may be viewed from outside.
Chapter 3. General Requirements.
Section 301 General
301.3 Vacant Structures and land. Vacant structures and premises thereof or
vacant land shall be maintained in a clean, safe, secure and sanitary condition as
provided herein so as not to cause a blighting problem or adversely affect the
public health or safety. All vacant structures shall be regulated further according to
Title 4, Chapter 16 of the City Code as amended, "Vacant Buildings. "
301.4 Emergency Phone Contact. The owner shall provide each tenant with the
name and telephone number of a responsible person who, in emergency situations,
will be available on a 24-hour basis and who has the authority to make repairs to
the building and premises as needed. The owner shall also cause said information
to be posted with alphabet letters and Arabic numerals at least 1'/2 inches (37 mm)
high and 1/4-inch (6 mm) stroke and maintained on the exterior of the building near
the main entryway at least five feet (5) above grade of every rental residential
structure, except that two unit buildings where the owner resides in at least one unit
shall be exempt from posting.
Section 302 Exterior Property Areas
302.2 Grading And Drainage. Premises shall be graded and maintained to
prevent the erosion of soil and to prevent the accumulation of stagnant water
thereon, or within any structures located thereon, or on any surrounding premises
or structures. The grade of premises shall not be altered by the storage of any type
of soil, stone, chips or any other type of fill or material. Water shall not be allowed to
accumulate and remain stagnant in any equipment, storage, debris or containers
that may be present on the property.
302.3 Sidewalks and Walkways. All private sidewalks, walkways, stairs,
driveways, parking spaces, parking lots and similar areas on private property shall
be kept in a proper state of repair, and maintained free from hazardous conditions
including, but not limited to, snow and/or ice.
302.4 Weeds and Turf Grass. All premises and exterior property shall be managed
and maintained to prevent plant growth of weeds and turf grass in excess of eight
(8") inches. All noxious weeds shall be prohibited. Weeds shall be defined as plants
that may be injurious to public health, wildlife, land and/or other property, including
plants demonstrating an excessively and/or aggressively competitive propagation
pattern.
Exceptions:
Title 5, Chapter 1, Property Maintenance Code
H
Page 85 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit
Plants, including grasses other than turf, flowers, landscaping, and gardens,
shall not be restricted to eight (8") inches in growth if they are managed and
maintained and do not demonstrate excessive, aggressive, and/or unruly
propagation. Managed and maintained plant growth in excess of eight (8")
inches shall not obstruct visibility of and accessibility to sidewalks, alleys,
streets, intersections, crosswalks, or other public right of ways. Reference City
Code 7-8-1-3 — Duty to Maintain Vegetation; 7-8-1-1 — Projections Over Right
of Way & 7-2-9 (A) — Encumbrances, Encroachments and Obstructions.
It shall be unlawful to plant, install or maintain any shrub, perennial, ornamental
grass or annual in the parkway of any street that matures at a height over three
(3) feet. Reference City Code 7-8-4-1 — Restricted Parkway Plantings.
The owner or agent having charge of a property that fails to cut plant growth, as
described and defined above, within the time frame provided in the notice of
violation, shall be subject to prosecution in accordance with Section 109 of this
code.
Upon failure by the owner or agent to comply with the notice of violation, any duly
authorized agent of the city or contractor hired by the city shall be authorized to
enter upon the property in violation and cut and destroy the plant growth thereon
and the costs for such removal shall be paid by the owner or agent responsible for
the property.
If the city cuts any plant growth, as described and defined above, on any vacant lot
or premises with a vacant structure as provided in this section, the city may impose
a lien on the property in violation. Upon being recorded in the manner required by
article XII of the code of civil procedure, as amended, or by the uniform commercial
code, as amended, the lien shall be imposed on said property as a debt due and
owing the city in an amount including, but not limited to: any city costs or
contractor's fees for cutting the plant growth; inspections; correspondence; title
searches; preparation of lien; and recording fees.
302.5 Rodent Harborage. All structures and exterior property shall be kept free
from rodent harborage and infestation. Where rodents are found, they shall be
promptly exterminated by approved integrated pest management processes which
will utilize engineering controls to build out pests, pesticides will be used only when
no other alternative has proven viable. After extermination, property precautions
shall be taken to eliminate rodent harborage and prevent reinfestation. There shall
be no accumulation of rubbish, boxes, firewood, lumber, scrap metal or any other
materials so that rodent harborage exists. Stored materials shall be stacked neatly
in piles elevated at least twelve (12) inches above the ground or grade.
302.7 Accessory Structures. All accessory structures, including detached
garages, sheds, fences, gates and walls, shall be maintained structurally sound
and in good repair.
302.7.1 Doors. All accessory structures shall be provided with doors which are
maintained and operational. For carports and similar structures which by intent,
design and construction do not have doors, doors shall not be required.
Title 5, Chapter 1, Property Maintenance Code
N
Page 86 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
302.8 Motor Vehicles, Boats and Trailers. No inoperative, unlicensed, and or
unregistered, motor vehicle, boat or trailer, shall be parked, kept or stored, on any
premises, and no vehicle shall at any time be in a state of major disassembly,
disrepair or in the process of being stripped or dismantled. Painting of vehicles is
prohibited unless conducted inside an approved spray booth.
302.8.1. Parking of Motor Vehicles. No vehicle, regardless of status of licensing,
registration or operability, shall be parked within any public sidewalk area, parkway
area (unless there is an approved substrate/surface, the vehicle fits fully between
the sidewalk, street and concrete curbing inner edges where it meets the parkway,
is registered with the State of Illinois with a current license plate, and can be moved
with proper notice if required), private sidewalk, or upon any unimproved surface
including any vegetation, grass, soil, rock, stone or surface other than concrete,
asphalt, pavers or similar surface.
302.10 Graffiti Removal. All exterior and interior structure surfaces must be kept
clean and free of graffiti, as graffiti is defined in section 202.0. Surfaces which have
been exposed to graffiti must be cleaned, painted or in some manner covered, so
as to effect the complete removal of the graffiti from that surface and to return the
surface to a clean condition.
302.11 Landscape. All premises shall be maintained in the following manner
regarding grass, shrubs, trees and other plant growth.
302.11.1 Grass. All premises, including vacant land and parkways, shall have
grass, or other forms of approved ground cover provided and maintained. Any
requirement for grass installation either sod or seed, shall be completed in
accordance with city specifications.
A property owner who fails to establish seed or sod in conformance with a violation
notice shall provide the code official with an executed contract for the sodding or
seeding of the site with a landscape contractor who possesses a valid business
license issued by the municipality in which the landscape business is based. In the
instance a municipality does not issue such a license, the contractor must provide
evidence satisfactory to the code official that it is in the business of landscape
contracting. Installation of sod or seed shall be completed when the soil
temperature is at least 55 degrees Fahrenheit.
302.11.2 Trees. All premises and exterior property shall be maintained free of
fallen trees, limbs and branches. Trees with dead limbs or branches which are or
may become hazardous to persons or property in the vicinity shall have such limbs
or branches removed. Trees which are dead, diseased, infected, infested or are
otherwise determined to be hazardous shall be removed. Tree boughs or limbs that
project over any private means of egress from a structure shall not project over
such means of egress at a height of less than eight feet (8') above such means of
egress.
302.11.3 Encroachment. Any plant growth which shall encroach on the public way
or affect movement or vision of pedestrians or vehicles on the public way, shall be
Title 5, Chapter 1, Property Maintenance Code
110
Page 87 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
trimmed to allow for unobstructed vision and passage of persons, pedestrians and
vehicles.
302.12 Furniture. Any furniture placed exterior of a building shall have been
constructed for such exterior use and shall be constructed of materials that are
water and weather-proof and resistant to rot, mildew, mold, decay and insect
infestation. Exterior type furniture shall not be required in spaces which are
completely enclosed and protected from the exterior elements.
302.13 Tarpaulin (Tarp) Use Restrictions. Tarps or other similar temporary
coverings may be used to provide temporary weatherization of a structure for a time
period not to exceed 30 days, except during times of a natural disaster as declared
by any local, state or federal government or during an emergency as declared by
the Code Official. A tarp that is used after a declared natural disaster or emergency
shall be allowed to remain in place for a period not to exceed 180 days if such tarp
is maintained in good condition. The Code Official may approve one 180-day
extension for use after a natural disaster or declared emergency or one 30-day
extension for non -emergency uses upon a showing of good cause.
Tarps and other similar materials are prohibited as follows
(a) The use of a tarp as a roof covering, excluding declared emergencies as
mentioned above
(b) The use of a tarp as fencing material, or as part of a privacy fence or screen
(c) The use of a tarp as a cover or screen for porches, carports or garages
(d) The use of a tarp to cover cars, boats or other personal property is
prohibited. Only fitted covers manufactured specifically to cover cars, boats, pools,
ATVs, BBQ grills, or other similar personal property, are permitted and must be
used for their intended purpose. Covers shall not be faded and shall be in good
condition, without tears, rips or holes. Any motor vehicle that is lawfully parked
and is covered in a manner consistent with this section shall allow at least the
bottom six inches of each tire to be visible.
Section 304 Exterior Structure
304.3.1 Alley Frontage Identification. Buildings shall have approved address
numbers placed in a position to be plainly legible and visible from the alley when a
premises abuts an alley. Premises shall have the address placed on garages when
present or on the principal structure. These numbers shall contrast with their
background. Address numbers shall be Arabic numerals or alphabet letters.
Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke
width of 0.5 inch (12.6 mm).
304.7 Roof. The roof and flashing shall be sound, tight, and not have defects that
admit rain. All roof components, including, but not limited to, roofs over stairs,
soffits, fascia and flashing, shall be adequate to prevent dampness or deterioration
in the walls or interior portion of the structure. The roof shall not have any animal
entry points due to deterioration or damage. Roof drains, gutters and downspouts
shall be maintained in good repair, free from obstructions, vegetation, rust, peeling
paint, cracks and holes.
Title 5, Chapter 1, Property Maintenance Code
111
Page 88 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
304.7.1 Gutters, Sump Pump or Other Discharge. Where gutters are provided,
downspouts shall be required and shall terminate water discharge to grade a
minimum of three feet (3') away from any portion of the structure and not within ten
feet (10') of any property line or as approved by a Civil Reviewer or his/her
designee. Sump pumps and discharge from other sources including downspouts
shall not discharge upon a public way nor be directed towards adjacent properties
and shall be drained upon the premises without causing retention of stagnant water
thereon. Footing drains to be connected to the sump pump as discharge shall
terminate water discharge to grade a minimum of three feet (3') away from any
portion of the structure and not within ten feet (10') of any property line or as
approved by the Civil Reviewer or his/her designee. Water discharge shall not
discharge upon a public way nor be directed toward adjacent properties or
discharge in a manner that will disturb adjacent properties and shall be drained
upon the premises without causing retention of stagnant water thereon. Gutters,
downspouts and sump pump discharge lines shall not retain stagnant water.
304.13.1 Glazing. All glazing materials shall be maintained free from cracks and
holes. Open cracks and/or unstable glazing shall be corrected by replacement of
the windowpane.
304.14 Insect Screens. (Dates removed). Every door, window and other outside
opening utilized or required for ventilation purposes serving any structure
containing habitable rooms, food preparation areas, food service areas, or any
areas where products to be included or utilized in food for human consumption are
processed, manufactured, packaged or stored, shall be supplied with approved
tightly fitting screens of not less than 16 mesh per inch and every swinging door
shall have a self -closing device in good working condition.
Exception: Screens shall not be required where other approved means, such as
air curtains or insect -repellent fans, are employed.
304.18 Building Security. Delete
304.20 Burglar Bars, Grilles, Grates, Shutters. Any type of burglar bars,
including but not limited to bars, grilles, grates or shutters shall be prohibited from
placement on the exterior of any building, structure or premises, which fronts or is
visible from a street or thoroughfare, except that such security measures are
allowed when used on openings that are adjacent to an alley or similar area. Any
such security measures shall only be permitted to be placed on the interior of a
building when fronting or visible from a street or thoroughfare, shall remain in the
open position, thereby not visible and not impeding egress during any hours of
operation for non-residential occupancies and in compliance with egress
requirements for all occupancies and use groups. This section shall not prohibit the
placement of fencing on a premises, or security doors that are installed on the
exterior stairways of buildings where approved by permit. Property shall be in
compliance with this section within one year of the adoption of this code.
304.21 Masking Of Windows. Any building space located at grade where the
interior of such space is visible from the public way or private property intended for
public use and is vacant or undergoing construction, renovation, alterations or a
112
Title 5, Chapter 1, Property Maintenance Code
Page 89 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit
change of use, and such space is not in conformance with this code, such space
shall have the window area masked so that the interior of the space is not visible
from the public way. Masking of windows shall adhere to 4-10-13 Storefront
Maintenance and Window Covering During Vacancy or Renovation of City Code.
304.22 Sign Maintenance and Repair. Every sign including but not limited to
those signs for which permits are required, shall be maintained in a safe,
presentable, and good structural condition at all times, including replacement of
defective parts, painting, cleaning and other acts required to maintain the sign,
advertising structure, marquee, canopy or awning in its originally permitted and
installed condition in accordance with Title 4, Chapter 10 of the City Code, Sign
Regulations. Required repair or maintenance of any sign shall in no manner be
constituted as approval of any sign whether such sign is permitted, prohibited or
unlawful.
304.23 Obsolete Or Abandoned Signs. Any sign or advertising structure now or
hereafter existing, which advertises a business, commodity, service, entertainment,
activity, or event which has been discontinued, or is located on property which has
been vacant and unoccupied, shall have such sign removed in accordance with
Title 4, Chapter 10 of the City Code, Sign Regulations.. Any portion of the building
or surface that is uncovered due to removal of a sign shall be restored to a
condition free from holes, breaks and loose or rotting materials and maintained
weatherproof and properly surface -coated where required to prevent deterioration.
304.24 Window Glass Maintained. All windows and window areas shall be
maintained in a clean and sanitary condition, free and clear of all dirt, filth, grease,
adhesive, paint and any other similar materials or substances that mar the window
surface.
Section 305 Interior Structure
305.4 Stairs and Walking Surfaces. Every stair, ramp and landing, balcony,
porch, deck or other walking surface shall be maintained in sound condition and
good repair. Any components, including but not limited to treads and risers, that
evidence excessive wear, rot, deterioration or are broken, warped or loose shall be
replaced. Treads and risers shall be uniform. Building Permits shall be required for
the following: porch/deck replacement, stringer/stair replacement, and/or
replacement of any structural member including posts and posts that support roof
overhangs.
305.7 Bathrooms, Toilet Rooms, And Kitchen Floors. Every bathroom, toilet
room, kitchen and similar rooms equipped with running water, shall be maintained
to be a smooth, hard, nonabsorbent surface to permit such floor to be easily kept in
a clean and sanitary condition.
305.8 Walls. Every room containing a shower shall have walls surrounding the
shower covered by a smooth, hard, nonabsorbent surface and easily cleanable, to
a height of at least sixty inches (60") above the surrounding floor. Such walls shall
form a watertight joint with each other and with the bathtub, shower, and or floor.
Title 5, Chapter 1, Property Maintenance Code
113
Page 90 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit
305.9 Unit Identification. Each dormitory, dwelling, hotel and rooming unit, except
for buildings containing two or fewer units, shall have each unit -number or
designation, displayed in a position easily observed and readable from outside of
the unit. The unit -number shall be posted on or adjacent to the front or main egress
door of the unit. Units which are located in hallways, stairways or similar areas,
where such units have differing street addresses, such units shall have the street
address posted in addition to the unit number on the front and rear unit doors.
Identification shall be in Arabic numerals and alphabet letters at least 1'/2 inches
(37 mm) high and '/4-inch (6 mm) stroke.
Section 308 Rubbish And Garbage
Section 308 Rubbish and garbage is hereby deleted in its entirety and this section 308
substituted therefor.
308.1 Accumulation of Rubbish or Garbage. All exterior property and premises,
and the interior of every structure shall be free from any accumulation of rubbish or
garbage.
308.2 Disposal of Rubbish or Garbage. Every occupant of a structure shall
dispose of all rubbish and/or garbage in a clean and sanitary manner by placing
such rubbish or garbage in approved leak -proof containers with tightfitting covers
and closing such covers.
308.2.1 Rubbish and Garbage Containers. The owner of every occupied
premises and the operator or occupant of every establishment or building
producing garbage and or rubbish, shall be responsible for supplying and utilizing
approved covered leak -proof containers with tight fitting covers for the temporary
storage of rubbish and garbage until such materials are permanently removed from
the premises. The owner, operator, and building occupant shall be responsible for
the removal of rubbish and garbage.
The owner or agent having charge of a property who fails to remove rubbish and
garbage within time prescribed in the notice of violation, shall be subject to
prosecution in accordance with Section 106 of this code.
Upon failure by the owner or agent to comply with the notice of violation, any duly
authorized agent of the city or contractor hired by the city shall be authorized to
enter upon the property in violation and remove any and all rubbish and garbage
located thereon and the costs for such removal shall be paid by the owner or agent
responsible for the property.
308.2.2 Container Labeling. All containers servicing business, commercial, or
multi -residential premises shall display the name and address of the premises they
serve in conspicuous lettering. Said lettering is to be maintained in a clean and
legible condition. Containers shall be situated so that the required lettering is visible
from the public way.
308.2.3 Container Locks. If located in the downtown zoning districts, as defined in
section 6-18-3 of the Evanston zoning ordinance as amended, containers shall be
maintained with their lids shut and locked, except when depositing or removing
waste.
114
Title 5, Chapter 1, Property Maintenance Code
Page 91 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
308.3 Garbage and Rubbish Services for Multi -Unit Residential Buildings. The
owner of every occupied building with more than four (4) dwelling and/or rooming
units shall provide each week, minimum proper container or dumpster capacity
capable of holding not less than the volume indicated by the following:
0.25 cubic yard (uncompacted) per dwelling unit.
0.10 cubic yard (uncompacted) per rooming unit.
308.3.1 Container Capacity. Each container or dumpster shall be considered to
contribute the volume of garbage and rubbish that can be enclosed with the lid or
cover completely closed. Calculations of volume by the scavenger service providing
the container may be accepted in determining service capacity.
308.3.2 Minimum Service Schedule. All containers or dumpsters shall be emptied
and maintained at least once per week, or more often, as needed to maintain the
property and premises in a safe, clean and sanitary manner.
308.3.3 Pickup Calculations. A container shall be considered to provide its
capacity in volume each time it is regularly scheduled for pickup, and is picked up.
Upon a written request from the code official, the owner and/or operator of any
building or establishment shall promptly provide a written contract or documentation
from the utilized scavenger service indicating the address of the property serviced;
the party contracting the service; the number of containers provided, and the
capacity of each; the days of the week the containers are emptied by the scavenger
service.
308.3.4 Additional Capacity Requirements. Any container or dumpster in which
the volume of contents prevents full closure of the cover shall be deemed
overloaded. Rubbish or garbage stacked or piled near, on the exterior, or above the
sidewalls of the dumpster or container shall evidence an overloaded condition.
Overloaded containers or dumpsters shall be remedied immediately by the owner
and/or operator, and immediately thereafter supplemented by additional pickups
and/or containers of a sufficient amount so as to prevent any recurrence of the
overloaded condition.
The owner and/or operator of the building or establishment shall promptly provide
to the city upon request of the code official an executed written contract or
documentation from the utilized scavenger service indicating the address of the
property serviced; the party contracting for the service; itemization of the number of
existing and added number of containers and the capacity of each; itemization of
the number existing and the added number of pick-up days of the week, and
itemization of each day of the week that service is provided.
308.4 Additional Capacity Requirements for Commercial (Non -Residential)
Property. Any container or dumpster in which the volume of contents prevents full
closure of the cover shall be considered to be overloaded. Rubbish or garbage
stacked or piled near, on the exterior, or above the sidewalls of the dumpster or
container shall evidence an overloaded condition. Overloaded containers or
dumpsters shall be remedied promptly, and immediately thereafter supplemented
Title 5, Chapter 1, Property Maintenance Code
115
Page 92 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662felf15
Ordinance 29-0-22, Exhibit
by additional pickups and/or containers of a sufficient amount so as to prevent any
recurrence of the overloaded condition.
In addition, the owner and/or operator of the building or establishment shall
promptly provide to the city upon request by the code official: a written contract or
documentation from the utilized scavenger service indicating the address of the
property serviced; the party contracting the service; itemization of the existing and
the increase of the total number of containers and the capacity of each; itemization
of the existing and the increase of the total number of pick-up days of the week,
and itemization of each day of the week that service is provided.
308.5 Additional Capacity Requirements for Condominiums and Residential
Buildings of One (1) Through Four (4) Dwelling And/or Rooming Units. Any
container or dumpster in which the volume of contents prevents full closure of the
cover shall be considered to be overloaded. Rubbish or garbage stacked or piled
near, on the exterior, or above the sidewalls of the container or dumpster shall
evidence an overload condition. Overloaded containers or dumpsters shall be
remedied immediately, by the owner, and thereafter supplemented by additional
containers to prevent any recurrence of the overload condition. Additional
containers shall not exceed thirty-five (35) gallons in size and the total weight of the
container and the material placed within shall not exceed fifty (50) pounds. Special
additional pickups may be employed for occasional overload conditions.
308.6 Refrigerators, Discarded. Refrigerators and similar equipment not in
operation shall not be discarded, abandoned, kept or stored on any premises
without first removing the doors.
308.7 Tires, Discarded. Tires for use on any type of vehicle or equipment shall not
be discarded, abandoned, kept or stored on the exterior of any premises.
Chapter 4. Light, Ventilation and Occupancy Requirements.
402.4 Exterior lighting. Exterior lighting shall not cause light trespass and shall
protect adjacent properties and public ways from glare and excessive lighting. Light
level at any property line is limited to one-half (0.5) foot-candle unless otherwise
regulated by city code.
Exception:
1. Security lighting: Exterior lighting installed primarily for safety or
emergency shall be permitted provided that said lighting is solely for
security and activated by a motion or a controlled system and shall be
extinguished within 5 minutes of cessation of actual or perceived
emergency.
2. Holiday lighting: Holiday lighting subject to NFPA 70 National Electric
Code regulations as adopted and amended by the City of Evanston.
Section 403 Ventilation
Title 5, Chapter 1, Property Maintenance Code
116
Page 93 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
403.3 Cooking Facilities. Unless approved through the certificate of occupancy,
cooking or the preparation of food or beverages shall not be permitted in any
rooming unit or lodging unit or dormitory unit, and a cooking facility or appliance
including but not limited to stoves, ovens, microwave ovens, hot plates, coffee pots,
crock pots, blenders, shall not be permitted to be present in a rooming unit or
lodging unit or dormitory unit.
Exceptions:
1. Where specifically approved in writing by the code official.
2. Devices such as single -use or automatic shut-off coffee pots shall not
be considered cooking appliances.
404.1 Privacy. Dwelling units, hotel units, housekeeping units, rooming units, and
dormitory units shall be arranged to provide privacy, and be separate from other
adjoining spaces. Egress doors shall have operating locks to provide privacy.
404.7.1 Food Storage. In rooming and dormitory units, refrigerators shall not
exceed three (3) cubic feet in capacity as rated by the manufacturer. Not more than
one (1) refrigerator of such size shall be allowed per occupant of any rooming unit,
including dormitory rooming units.
Chapter 5. Plumbing Facilities and Fixture Requirements.
Section 501 General
501.2.1 Disconnection Notice. It shall be a violation of this code for any owner of
a non -owner occupied residential property who is issued or who is in receipt of a
notice of disconnection or termination for the utility service provided by the city or
the utility involved, to fail to promptly remedy the circumstance or situation upon
which the disconnection notice is based.
Section 505 Water System
505.3 Supply. The water supply system shall be installed and maintained to
provide a supply of water to plumbing fixtures, devices and appurtenances in
sufficient volume and at pressure adequate to enable the fixtures to function
properly, safely, and free from defects and leaks. Water pressure shall be no lower
at the fixture outlet than as follows: lavatory basins, two (2) gallons/minute; bathtub
faucets, four (4) gallons/minute; toilet pressure, as required by Title 4, Chapter 5 of
the Evanston City Code, as amended.
505.4 Water Heating Facilities. Water heating facilities shall be properly installed,
maintained and capable of providing an adequate amount of water to be drawn at
every required sink, lavatory, bathtub, shower and laundry facility at a temperature
of not less than 115 degrees F (46 degrees C). A gas -burning water heater shall
not be located in any bathroom, toilet room, bedroom or other occupied room
normally kept closed, unless adequate combustion air is provided. An approved
combination temperature and pressure relief valve and relief valve discharge pipe
shall be properly installed and maintained on water heaters. Relief valve discharge
pipe shall be of metallic material and shall discharge directly into a floor drain, hub
Title 5, Chapter 1, Property Maintenance Code
117
Page 94 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
drain, service sink, sump or a trapped and vented P-trap that is located in the same
room as the water heater per Illinois Plumbing Code section 890.1230.
Chapter 6. Mechanical and Electrical Requirements.
Section 601 General
601.2.1 Disconnection Notice. It shall be a violation of this code for any owner of
a non -owner occupied residential property who is issued or who is in receipt of a
notice of disconnection or termination for the utility service provided by the city or
the utility involved, to fail to promptly remedy the circumstance or situation upon
which the disconnection notice is based.
Section 602 Heating Facilities
602.2 Residential Occupancies. Dwellings shall be provided with heating facilities
capable of maintaining a room temperature of 68 degrees F. (20 degrees C) in all
habitable rooms, bathrooms and toilet rooms based on the winter outdoor design
temperature for the locality. Neither cooking appliances nor space heaters shall be
used to provide space heating to meet the requirements of this section.
602.3 Heat Supply. Every owner and operator of any building who rents, leases, or
lets one or more dwelling unit, lodging unit, rooming unit, dormitory or guest room
on terms, either expressed or implied, to furnish heat to the occupants thereof shall
supply heat during the period from September 15th to June 1st to maintain a
temperature of not less than 68 degrees F (20 degrees C) in all habitable rooms,
bathrooms and toilet rooms. Space heaters, whether portable or permanently
installed, shall not be utilized as the primary source of heat for any such unit or
room. Buildings or individual units shall employ central heating systems except
where a designed system is approved by the building official.
602.4 Occupiable Work Spaces. Indoor occupiable work spaces shall be supplied
with heat during the period from September 15th to June 1st to maintain a
temperature of not less than 68 degrees F 20 degrees C) during the period the
spaces are occupied.
Exceptions:
1. Processing, storage and operation areas that require cooling or special
temperature conditions.
2. Areas in which persons are primarily engaged in vigorous physical activities.
602.5 Room Temperature Measurement. The required room temperatures shall
be measured approximately 3 feet (914 mm) above the floor near the center of the
room, approximately 3 feet (914 mm) above the floor near the center of interior
walls of the room that are perpendicular to the exterior wall of the room.
Temperatures may be measured utilizing thermometers that measure air
temperature or thermometers that measure surface temperature.
Section 603 Mechanical Equipment
603.1.1 Forced -Air Systems. Forced -air heating and/or cooling systems shall not
serve more than one dwelling unit after the existing mechanical equipment is
118
Title 5, Chapter 1, Property Maintenance Code
Page 95 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
replaced due to age or failure. A Building Permit is required for equipment
replacement including for the addition of duct work to separate the systems.
603.7 Mechanical Appliance Connections. Every gas outlet for appliances,
including but not limited to heaters, stoves and clothes dryers, shall have an
individual shutoff valve. The shutoff valve shall be adjacent to the appliance with
access provided to the shutoff valve. In conjunction with the installation of a shutoff
valve any existing flexible gas connector shall be replaced with a new approved
flexible gas connector. All existing uncoated brass flexible gas connectors shall also
be replaced with approved gas connectors.
Section 604 Electrical Facilities
604.2 Service. The size and usage of appliances and equipment shall serve as a
basis for determining the need for additional facilities in accordance with the NFPA
70 National Electric Code as adopted by the City of Evanston. Dwelling units shall
be served by a three -wire, 120/240 volt, single-phase electrical service having a
rating of not less than 60 amperes. Each dwelling unit shall be served by not less
than four (4) branch circuits with a minimum of two (2) twenty -amp circuits.
604.5 Fuse Panels. In all electrical panels and boxes where plug -type fuses with
Edison base are utilized, such fuses shall be replaced with non -tampering type "S"
fuse adaptors which are properly sized for the gauge of wire that the fuse is
protecting.
604.6 Panel Identification. All electrical panels regardless of type of disconnecting
means shall be legibly marked to designate the address, space, tier or unit that
such panel is servicing. The marking shall be of sufficient durability to withstand the
environment involved.
604.7 Disconnecting Means Identification. All electrical disconnecting means
including circuit breakers and fuses shall be legibly marked to designate the
address, unit, space or rooms it is servicing. The marking shall be of sufficient
durability to withstand the environment involved.
Section 605 Electrical Equipment
605.2 Receptacles. Every habitable space in a dwelling shall contain at least two
separate and remote receptacle outlets. Every laundry area shall contain at least
one grounded -type receptacle or a receptacle with a ground fault circuit interrupter.
Every bathroom shall contain at least one receptacle. Any new bathroom or laundry
room receptacle outlet shall have ground fault circuit interrupter protection. When
an ungrounded -type receptacle exists in a bathroom or laundry area, a ground fault
interrupter receptacle shall be provided. Any existing worn, damaged, painted
and/or defective receptacles shall be replaced. All receptacle outlets shall have the
appropriate faceplate cover for the location.
Section 607 Duct Systems
607.2 Transition Ducts. Flexible air ducts used as a connector between clothes
dryer and its concealed duct shall be semi -ridged aluminum/metal.
Section 608 Meters
Title 5, Chapter 1, Property Maintenance Code
119
Page 96 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
608.1 Meter Identification. All meters, including but not limited to gas and electric
serving a building, structure or any portion thereof, shall be legibly marked to
designate the address, space, tier or unit that such meter is servicing. The marking
shall be of sufficient durability to withstand the environment involved.
Chapter 7. Fire Safety Requirements.
703.4 Opening Protectives. Required opening protectives shall be maintained in
an operative condition. All fire and smokestop doors shall be maintained in
operable condition, be rated as required and provided with approved self -closing
devices which shall force the door to close and latch. Fire doors and smoke barrier
doors shall not be blocked or obstructed or otherwise made inoperable.
704.6.1.2 Groups R-2, R-3, R-4 and 1-1. Single or multiple -station smoke alarms
shall be installed and maintained in Groups R-2, R-3, R-4 and 1-1 and in dwellings
not regulated in group R occupancies, regardless of occupant load, at all of the
following locations:
1. On the ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms.
2. In each room used for sleeping purposes.
3. In each story within a dwelling unit, including basements and cellars but
not including crawl spaces and uninhabitable attics. In dwellings or
dwelling units with split levels and without an intervening door between the
adjacent levels, a smoke alarm installed on the upper level shall suffice for
the adjacent lower level provided that the lower level is less than one full
story below the upper level.
4. On the ceiling above the top landing in each interior stairway that serves
dwelling, rooming or dormitory units.
CHAPTER 8. Building Security.
Section 801 General
801.1 Scope. The provisions of this chapter shall apply to:
1. All multi -unit non -owner occupied dwellings in residential buildings,
regardless of relationship of occupants to the owner.
2. All non -owner occupied single -unit dwellings, detached or attached,
regardless of relationship of occupants to the owner.
Exclusions:
1. Residence at a public or private medical, geriatric, educational, or religious
institution.
2. Occupancy in a structure operated for the benefit of a social or fraternal
organization.
3. Transient occupancy in a hotel or motel.
Title 5, Chapter 1, Property Maintenance Code
120
Page 97 of 99
Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
4. Owner -occupied units in multi -unit dwelling buildings including
condominiums, cooperatives, townhouse, rowhouse and single-family
homes.
Section 802 Building Security Application
802.1 Building Security. Doors, windows and hatchways shall be provided with
devices designed to provide security for the occupants and property within.
802.1.1 Intercoms. Multi -unit dwellings shall have an intercom system that is
maintained in good working condition. The removal of an intercom system is
prohibited and does not constitute repair or maintenance.
802.2 Locks. Doors providing access to individual units shall be equipped with a
deadbolt lock meeting specifications set forth herein. Such deadbolt locks shall be
operated only by the turning of a knob or a key and shall have a lock throw of not
less than 1-inch and hardened steel inserts or a surface/rim mounted vertical drop,
dead bolt lock. Cylinder guards shall be installed on all rim -type vertical dead bolt
locks whenever the cylinder projects beyond the face of the door or is otherwise
accessible to gripping tools. Strike plates shall be secured with hardened steel
screws four inches (4") long. For the purpose of this section, a sliding bolt shall not
be considered an acceptable deadbolt lock. Such deadbolt locks shall be installed
according to manufacturer's specifications and maintained in good working order.
All deadbolt locks required by this section shall be designed and installed in such a
manner so as to be operable inside of the unit without the use of a key, tool,
combination thereof or any other special knowledge or effort.
802.3 Window Locks. Accessible openable windows shall be equipped with
window locking devices.
802.4 Basement Hatchways. Basement hatchways shall be equipped with devices
that secure the hatchway from unauthorized entry.
802.5 Doors. Exterior doors, doors leading from garage areas into multi -unit
dwelling buildings, and doors leading into stairwells, shall be equipped with self -
closing devices. All doors leading to apartment doors shall also be equipped with
self-locking devices.
802.6 Vision Panels. Accessible vision panels in individual entrance doors to
individual units or within forty inches (40") of the inside activating device shall be of
rated burglary -resistant glazing material. Burglary bars may be used as an
alternative to burglary -resistant glazing material on the interior of transoms only.
802.7 Door Scope. An interviewer or door scope, providing a 180-degree field of
view, shall be provided in each individual unit entrance door which does not contain
a vision panel.
802.8 Sliding Door Panels. All accessible single sliding patio doors shall have the
movable section of the door sliding on the inside of the fixed portion of the door.
802.9 Sliding Door Locks. Accessible sliding glass doors shall be equipped with
locking devices and shall be so installed that the doors cannot be moved in any
direction or lifted from the track when the doors are in the locked position, and
121
Title 5, Chapter 1, Property Maintenance Code
Page 98 of 99 Doc ID: 89d95372ca21a88d7c7e45de8e6b363662fe1f15
Ordinance 29-0-22, Exhibit I
doors shall have an approved auxiliary locking device added to their primary locking
system to provide additional security when in the closed position.
802.10 Window Panels. Accessible windows shall be so constructed and/or
maintained so that when the window is locked it cannot be lifted from the frame.
802.11 Lighting. All exterior common entrances of multiple family buildings shall be
illuminated with a minimum sixty (60) watt incandescent light bulb or its equivalent
in other light sources, enclosed in a tamper -proof cover, located within ten (10') feet
of the doorway.
802.12 Window Sash Fasteners. All wooden double -hung windows which are at
ground level or otherwise accessible from the exterior via porches, fire escapes, trees,
or other existing means shall be equipped with approved window -ventilating sash
fasteners to allow each window to be locked at no more than four inches (4") open.
Such fasteners shall be movable to permit the window to be fully opened from the inside
of the dwelling unit.
CHAPTER 9. REFERENCED STANDARDS.
Chapter 8, Referenced Standards, of the International Property Maintenance Code
of 2021 is hereby adopted as if fully restated and re -numbered to be Chapter 9 herein.
5-1-4. SEVERABILITY.
It is the intention of the city council that the provisions of this chapter and the
International Code Council, ICC, International Property Maintenance Code 2021, are
severable and the invalidity of any section or part of any section of this chapter and the
code hereby adopted shall not affect any other section or portion of this chapter or code.
5-1-5. — IDENTIFICATION OF ORDINANCE WITH THE ILLINOIS CAPITAL BOARD.
The adoption of this Ordinance and code, by title and edition, shall be reported to the
Illinois Capital Development Board Illinois or any successor agency of the State of
Illinois pursuant to Section 1-2-3.1 of the Illinois Municipal Code, 651LCS 5/1-2-3.1.
5-1-6. — EFFECTIVE DATE.
This Ordinance shall be in full force and effect thirty (30) days after its approval and
passage.
Title 5, Chapter 1, Property Maintenance Code
122
Page 99 of 99